23
Zero Calibration
“Tares” out any Zero pressure error. This must
be done with Zero pressure applied to the unit.
Duct Area
Manually enter the area of the duct where the
probe is mounted. The ducts area is necessary
for calculating the flow rate. The menu will
flash, then press the “down arrow” to select
desired digit. Press “enter” to select and move to
next digit.
Room Volume
E
nter the Room Volume (multiply width by
length by height)
Default is 68, range is 0 to 99.9
ACH Alarm High Limit
Sets the alarm for the high side ACH limit.
Choose “enter” to activate the A Alarm H Limit
menu. The menu will flash, then press the “down
arrow” to select desired digit. Press “enter” to
select and move to next digit. Default is 99.
ACH Alarm Low Limit
Sets the alarm for the low side ACH limit. Choose
“enter” to activate the A Alarm L Limit menu.
The menu will flash, then press the “down arrow”
to select desired digit. Press “enter” to select and
move to next digit. Default is 0.
ACH Alarm Enable
Enables or disables the ACH alarm. Choose
“enter” to activate the A Alarm Enable menu. The
menu will flash, then press the “down arrow” to
select desired mode. Press “enter” to select.