6.0 BACnet or Modbus setup
6.1 Setup BACnet address using the address switch
Remove the unit’s faceplate. You will see an address switch (pictured below). If you wish to set
the address of the unit using this switch, you must first identify and make note of an available
address found on your network.
SRH200
Default=2
Permitted=0...127 (BACnet)
SRH300
Default=1
Permitted=0...127 (BACnet)
Before connecting the device to your network, set the address you wish to have on the switch
following the above format and table below.
Note:
You will see from the table there are 8 positions. For this device, the 8
th
position (or 8
th
bit) is ignored.
For Example:
ID 127=0111111
BACnet PICS for this unit are available for download at www.setra.com. This unit’s ID as well
as many other properties are also read/writable from your BACnet console.