6.4 Setting Modbus address using the address switch
Remove the unit’s faceplate. You will see an address switch (pictured below). If you wish to set
the address of the unit using this switch, you must first identify and make note of an available
address found on your network.
SRH200
Default=245
Permitted=1...247 (Modbus)
SRH300
Default=242
Permitted=1...247 (Modbus)
Before connecting the device to your network, set the address you wish to have on the switch
following the above format and table below.