 4.3 Current Output Zero Adjustment

While monitoring the current output, and with both pressure ports open to atmosphere, the zero may be
adjusted by turning the zero adjustment screw. (See Diagram 5 for location of zero adjustment.) Factory
settings are:

Unidirectional Pressure Ranges

Bidirectional Pressure Ranges

Zero Adjustment

Output

Zero Adjustment

Output

4mA (0.08 mA)

4-20 mA

12 mA (0.08 mA)

4-20 mA

4.4

Current Output Span Adjustment

Span or full scale output adjustments should only be performed by using an accurate pressure standard
(electronic manometer, digital pressure gauge, etc.) with at least comparable accuracy to the 267 or
267MR transducer (<

±

1% full scale).  With full range pressure applied to the high pressure port (reference

port open to atmosphere), the span may be adjusted by turning the SPAN adjustment screw. (See
Diagram 1 for location of Span adjustment.) Factory Settings are:

Unidirectional Pressure Ranges

Bidirectional Pressure Ranges

Span Adjustment

Output

Zero Adjustment

Output

20mA (0.08 mA)

4-20 mA

20 mA (0.08 mA)

4-20 mA

Example 1:

Unidirectional pressure range of 0 to 1” W.C. with 4 to 20 mA output
Apply 1.00” W.C., adjust span to 20 mA (±0.08mA)

Example 2:

Bi-directional pressure range of 5” W.C. with 4 to 20 mA output
Apply 5.00” W.C., adjust span to 20 mA (±0.08mA)

5.0  MODEL 267 OPTIONAL LCD DISPLAY

The 267MR is available with an optional 3-1/2 digit LCD display.  The LCD is adjusted at the factory
prior to shipment. The LCD is connected to the zero and span adjustment potentiometers. Therefore,
adjustment of the zero and span according to Section 4 adjusts the LCD display.

6.0  Multi-Range Operation – Model 267MR only

The 267MR is re-rangeable by accessing the switches located internal to the transducer housing. To access
the “Dip” switches, remove the screws on the top of the case and lift off the cover.  The “Dip” switches are
located on the electronics board as show in Diagrams 1 and 5.  The voltage output version has 5 switches,
while the current version has 4.  The location of these switches, “on” (up position) or “off” (down
position) determine what range has been selected.  See Table 1 below for switch positions for in.W.C.

Multi-Range units are factory set to the highest range. As an example, an MR2 range is factory set to 0 to
1” W.C.

If the 267MR Range is re-configured from the factory calibration, place the correct range label (enclosed) on
the over label, over the area indicating the factory default range.

Notes: Voltage output is set based upon ordering code. See switch settings below to confirm voltage output.

If it is a 0-5 VDC
output, the
switches are set:

To change the range
to 0 to 0.25 in.WC
with a 0-10 VDC
output change the
switches to:

Содержание DPT267 Series

Страница 1: ...ng temperature limits of the 267 and 267MR are as follows Operating Temperature 0 F to 150 F 18 C to 65 C Compensated Temperature Range 40 F to 150 F 5 C to 65 C 2 3 Pressure Fittings The Model 267 and 267MR can be supplied with three different pressure fitting configurations 1 3 16 O D Barbed Brass Pressure Fittings Typically installed with 1 4 push on tubing 2 1 4 NPT Brass Pressure Fittings Typ...

Страница 2: ...e Excitation and Output are commoned on the circuit see Diagram 2 The excitation output specifications are Excitation Output 9 to 30 VAC 11 5 to 42 VDC 0 to 5 VDC 12 to 30 VAC 13 to 42 VDC 0 to 10 VDC The 267MR has field selectable 0 5 or 0 10 VDC output See Section 6 0 for switch settings to determine whether the voltage output is set to 0 5 or 0 10 VDC The 267 has either a 0 5 VDC or 0 10 VDC ou...

Страница 3: ... 3 3 3 Current Output Units 1 2 Conduit Opening PG 9 or Pg 13 5 Electrical Termination The Model 267 and 267MR is a two wire loop powered 4 to 20mA current output unit see Diagram 5 The current flows into EXC terminal and returns back to the power supply through the EXC Terminal see Diagram 6 The power supply must be a DC voltage source with a voltage range between 9 and 30 measured between termin...

Страница 4: ...d a 250ohm load The current output 9 pin D sub connector pin designations are shown in Diagram 8 CONNECTION 9 pin D sub Connector Electrical Termination EXCITATION 4 OUTPUT 9 Diagram 7 Diagram 8 3 5 4 20 mA Circuit Diagram Minimum Supply Voltage VDC 9 0 02 x resistance of receiver plus line Maximum Supply Voltage VDC 30 0 004 x resistance of receiver plus line If the current loop has a current lim...

Страница 5: ...er both zero and span adjustments are accessible under the cover of the unit below and to the right of the terminal strip The 267 and 267MR transducer is calibrated in the vertical position at the factory mounting tabs vertical 4 1 Voltage Output Zero Adjustment While monitoring the voltage between the positive output SIG and common GND and with both pressure ports open to atmosphere the zero may ...

Страница 6: ...utput Apply 5 00 W C adjust span to 20 mA 0 08mA 5 0 MODEL 267 OPTIONAL LCD DISPLAY The 267MR is available with an optional 3 1 2 digit LCD display The LCD is adjusted at the factory prior to shipment The LCD is connected to the zero and span adjustment potentiometers Therefore adjustment of the zero and span according to Section 4 adjusts the LCD display 6 0 Multi Range Operation Model 267MR only...

Страница 7: ...ability and Hyseresis Thermal Effects Compensated Range F C 40 to 150 5 to 65 Zero Span Shift FS F C 0 033 0 06 Maximum Line Pressure 10 psi in positive or negative Overpressure 10 psi in positive or negative direction Warm up Shift 0 1 FS Total Position Effects Unit is factory calibrated at 0g effect in the vertical position Range Zero Offset FS G 0 to 0 1 W C 2 1 0 to 1 W C 0 22 0 to 5 W C 0 14 ...

Отзывы: