background image

    +EXC

GND

    +SIG

3.1 Voltage Output Units – 1/2” Conduit Opening, PG-9 or PG-13.5 Electrical Termination

Wiring terminations are identified on the circuti board below the terminal strip (see Section 3.1 for
voltage output units or Section 3.3 for current units). To access the terminal strip, turn the screws on
top of the case counter clockwise until the cover can be removed. The screws are captured and will be
secured in the top of the case.

Diagram 1

The Model 267 and 267MR voltage output is a 3-wire circuit, with three terminals available for wiring
(see Diagram 1).  The -Excitation and -Output are commoned on the circuit (see Diagram 2).  The
excitation/output specifications are:

Excitation

Output

9 to 30 VAC / 11.5 to 42 VDC

0 to 5 VDC

12 to 30 VAC / 13 to 42 VDC

0 to 10 VDC

The 267MR has field selectable 0-5 or 0-10 VDC output. (See Section 6.0 for switch settings to determine
whether the voltage output is set to 0-5 or 0-10 VDC.) The 267 has either a 0-5 VDC or 0-10 VDC
output, calibrated at the factory.

Voltage Circuit Diagram

Diagram 2

+EXC 

Connected to positive terminal of DC or AC Power Supply

GND

Connect as the reference port for power supply and output signal

+SIG

Connect to positive terminal of Control or Pressure Monitor

Power
Supply

Readout or

DAS

Model

267MR

Range Select Switches
(267MR version only)

Electrical
Connections

Содержание DPT267 Series

Страница 1: ...ng temperature limits of the 267 and 267MR are as follows Operating Temperature 0 F to 150 F 18 C to 65 C Compensated Temperature Range 40 F to 150 F 5 C to 65 C 2 3 Pressure Fittings The Model 267 and 267MR can be supplied with three different pressure fitting configurations 1 3 16 O D Barbed Brass Pressure Fittings Typically installed with 1 4 push on tubing 2 1 4 NPT Brass Pressure Fittings Typ...

Страница 2: ...e Excitation and Output are commoned on the circuit see Diagram 2 The excitation output specifications are Excitation Output 9 to 30 VAC 11 5 to 42 VDC 0 to 5 VDC 12 to 30 VAC 13 to 42 VDC 0 to 10 VDC The 267MR has field selectable 0 5 or 0 10 VDC output See Section 6 0 for switch settings to determine whether the voltage output is set to 0 5 or 0 10 VDC The 267 has either a 0 5 VDC or 0 10 VDC ou...

Страница 3: ... 3 3 3 Current Output Units 1 2 Conduit Opening PG 9 or Pg 13 5 Electrical Termination The Model 267 and 267MR is a two wire loop powered 4 to 20mA current output unit see Diagram 5 The current flows into EXC terminal and returns back to the power supply through the EXC Terminal see Diagram 6 The power supply must be a DC voltage source with a voltage range between 9 and 30 measured between termin...

Страница 4: ...d a 250ohm load The current output 9 pin D sub connector pin designations are shown in Diagram 8 CONNECTION 9 pin D sub Connector Electrical Termination EXCITATION 4 OUTPUT 9 Diagram 7 Diagram 8 3 5 4 20 mA Circuit Diagram Minimum Supply Voltage VDC 9 0 02 x resistance of receiver plus line Maximum Supply Voltage VDC 30 0 004 x resistance of receiver plus line If the current loop has a current lim...

Страница 5: ...er both zero and span adjustments are accessible under the cover of the unit below and to the right of the terminal strip The 267 and 267MR transducer is calibrated in the vertical position at the factory mounting tabs vertical 4 1 Voltage Output Zero Adjustment While monitoring the voltage between the positive output SIG and common GND and with both pressure ports open to atmosphere the zero may ...

Страница 6: ...utput Apply 5 00 W C adjust span to 20 mA 0 08mA 5 0 MODEL 267 OPTIONAL LCD DISPLAY The 267MR is available with an optional 3 1 2 digit LCD display The LCD is adjusted at the factory prior to shipment The LCD is connected to the zero and span adjustment potentiometers Therefore adjustment of the zero and span according to Section 4 adjusts the LCD display 6 0 Multi Range Operation Model 267MR only...

Страница 7: ...ability and Hyseresis Thermal Effects Compensated Range F C 40 to 150 5 to 65 Zero Span Shift FS F C 0 033 0 06 Maximum Line Pressure 10 psi in positive or negative Overpressure 10 psi in positive or negative direction Warm up Shift 0 1 FS Total Position Effects Unit is factory calibrated at 0g effect in the vertical position Range Zero Offset FS G 0 to 0 1 W C 2 1 0 to 1 W C 0 22 0 to 5 W C 0 14 ...