3.2
Voltage Output Units – 9 pin D-sub Connector Electrical Termination
The Model 267 and 267MR voltage output is a 3-wire circuit with three pins available for wiring (see
Diagram 3). The voltage output pin designations are shows in Diagram 4.
Diagram 4
CONNECTION
9 pin D-sub Connector
Electrical Termination
+EXCITATION
4
+OUTPUT
1
COMMON
9
Excitation
Output
9 to 30 VAC/11.5 to 42 VDC
0 to 5 VDC
12 to 30 VAC/13 to 42 VDC
0 to 10 VDC
Diagram 3
3.3 Current Output Units 1/2” Conduit Opening, PG-9 or Pg-13.5 Electrical Termination
The Model 267 and 267MR is a two-wire loop-powered 4 to 20mA current output unit (see Diagram
5). The current flows into +EXC. terminal and returns back to the power supply through the -EXC.
Terminal (see Diagram 6). The power supply must be a DC voltage source with a voltage range
between 9 and 30 measured between teEXC. and -EXC. The unit is calibrated with a 24 VDC
loop supply voltage and a 250 ohm load.
Diagram 5
Diagram 6
PIN 4
PIN 9
- EXC
PIN 1
Range Select Switches
(267MR version only)
Electrical
Connections
267MR
Current
Monitoring
Device
9 to 30 VDC