6(18)

Servodan A/S | Tel +45 7442 4726 | Fax + 45 7442 4035 | [email protected] | www.servodan.com

Advarsel:

 Indbygning og montering af elektriske apparater må kun foretages af aut. elinstallatør. Ved fejl eller driftforstyrelser kontakt den aut. elinstallatør. 

! Ret til ændringer forbeholdes !

Warning:

 Installation and assembly of electrical equipment must be carried out by qualifi ed electricians. 

Contact a qualifi ed electrician in the event of fault or breakdown. 

Reserving the right to make changes !

Achtung:

 Einbau und Montage elektrischer Geräte dürfen nur durch Elektrofachkräfte erfolgen. 

Wenden Sie sich bei Störungen bzw. Ausfall an einen Elektrofachkraft. 

Änderungen vorbehalten !

Avertissement:

 L’installation et le montage d’appareils électriques doivent exclusivement être exécutés par un électricien agréé. En cas de défaut ou de perturbation du 

fonctionnement, contacter un installateur électricien agréé. 

! Sous réserve de modifi cations !

Fig. 5

Fig. 7

Fig. 6

Fig. 8

Fig. 9

41-700 Presence detector 360° 1ch

L

1

L

2

N

L

1

L

1

L

1

L

1

N

N

L’

2

L

2

T

1

/S T

1

/S

41-700 Presence detector 360° 1ch

L

1

L

2

N

L

1

L

1

L

1

L

1

N

N

L’

2

L

2

41-702 Presence detector 360° Slave

L

1

L

1

N

N

T

1

/S T

1

/S

T

1

/S T

1

/S

Factory setting,:
Lux: 200 lux
Time (Off-delay): 10 min.

20

100

300

500

1k

Test

5

15

60

20

100

300

500

1k

Test

5

15

60

Lux Ch 1

Time Ch 1

DIP 1     2
 

Off  Off: Min.

 

Off  On: Low 

 

On  Off: High (Factory setting)

 

On  On: Max.

DIP switch:
Application

Factory setting:

1 = On
2 = On
3 = Off
4 = Off

DIP switch:

Sensitivity

Lock/

unlock

Short

push

Learn actual lux

20

Lux

50

Lux

100
Lux

300
Lux

400
Lux

200
Lux

500
Lux

700
Lux

1000

Lux

No

Lux

Fact.

setting

Long
push

Test

On/Off

Time

30min

60min

15min

8

Hours

Pulse

2min

5min

10min

Ch 1

Ch 2

Status

Ch 1

Status

Ch 2

Light 1
On/Off

Light 2
On/Off

LED

On/Off

Off

On

Relay

Time

5

sec.

55

sec.

5

sec.

55

sec.

Movement

5 Minutes

off delay

Содержание 5703102207630

Страница 1: ...ar efter ca 40 sek opvarmningstid Den r de LED blinker under opvarmning Opvarmningstidens afslutning indikeres med 2 korte blink fra den gr nne LED Tilslutningsskema Fig 5 Ordliste App Applikation den...

Страница 2: ...r sensoren registrerer aktivitet i d kningsomr det og belysningsniveauet er under indstillet v rdi Lyset slukker automatisk efter en forudbestemt tid n r registre ring af aktivitet i sensorens d kning...

Страница 3: ...betjening Indstillinger via IR fjernbetjening Fig 8 Lock unlock Der trykkes 3 gange for at l se unlock sensoren op indstillingsmode Hvert tryk indikeres med gr nt blink i sensoren N r sensoren er i pr...

Страница 4: ...k On og 30 sek Off Alle vrige funktioner er blokeret For at oph ve funktionen inden de 8 timer er g et aktiveres 8 Hours igen n r sensoren er l st op Unlock Den r de LED stopper med at blinke og senso...

Страница 5: ...n A S Tel 45 7442 4726 Fax 45 7442 4035 info servodan dk www servodan com Fig 4 27 46 4 100 Gasket for IP54 Fig 3 Fig 1 30 Fig 2 24 m 6 m 3 4 m 9 m2 13 5 m 140 m2 2 5 m 0 8 m 20 m 300 m2 3 m 6 m 28 m2...

Страница 6: ...e d faut ou de perturbation du fonctionnement contacter un installateur lectricien agr Sous r serve de modifications Fig 5 Fig 7 Fig 6 Fig 8 Fig 9 41 700 Presence detector 360 1ch L1 L2 N L1 L1 L1 L1...

Страница 7: ...the power supply the detector will be ready to operate after approximately 40 seconds warm up time The red LED flashes during warm up The end of the warm up time is indicated with two short flashes f...

Страница 8: ...d when the detector detects movement the red LED and connected lighting will switch on for five seconds NB The walk test is daylight independent Examples Example 1 E g classroom DIP switch settings 1...

Страница 9: ...gent Avoid putting pressure on the lens If the lens or other parts of the detector are defective it they must be replaced Technical data Input Power supply 230 V AC 50 Hz 10 Power consumption 0 2 W Ou...

Страница 10: ...gs Pulse 2 min 5 min 10 min 15 min 30 min and 60 min There is also an eight hour 8 Hours constant illumination for operating a ventilation system HVAC system The detector must be unlocked Unlock first...

Страница 11: ...b 4 Anschluss Der Melder darf erst an Spannung angeschlossen werden wenn alle Leitungsverbindungen angeschlossen sind Nach dem Anschluss der Spannung ist der Melder nach ca 40 Sek Aufw rmzeit betriebs...

Страница 12: ...7 Test Um zu kontrollieren ob der Melder Bewegungen korrekt erkennt kann ein sogenannter Geh Test durchgef hrt werden Sie k nnen den Geh Test entweder ber das Time Potentiometer Minimumposition oder...

Страница 13: ...vom Tageslichtniveau immer mit dem Bet tigungsdrucktaster eingeschaltet werden 230 V Bet tigungsdrucktaster muss angeschlossen werden Die Einstellung des Lichtniveaus und der Ausschaltverz gerung wird...

Страница 14: ...Licht eingeschaltet werden soll weil das Tageslicht im Raum nicht mehr ausreicht Time Zeit Tasten Einstellen der Ausschaltverz gerung Es gibt 7 feste Einstellungen Pulse 2 Min 5 Min 10 Min 15 Min 30 M...

Страница 15: ...europ en ou PL Fig 4 Raccordement Le d tecteur ne doit tre mis sous tension que lorsque tous les raccordements ont t effectu s Apr s la mise sous tension le d tecteur est pr t fonctionner l issue de 4...

Страница 16: ...le d tecteur fonctionne correctement il est possible de faire un test de bon fonctionnement S lectionner le test de bon fonctionnement soit via le potentiom tre Time position minimum soit via le bouto...

Страница 17: ...ram trage du niveau de luminosit naturelle et de la temporisation de d connexion s effectue via les potentiom tres int gr s ou la t l commande IR 41 926 accessoire Exploitation et entretien La salet n...

Страница 18: ...osit minimale souhait e au moment o l clairage doit s allumer du fait que la luminosit naturelle n est plus suffisante dans la pi ce Touches Time temporisation de d connexion R glage de la temporisati...

Отзывы: