Presence detector 1-channel, 41-700

Operation

Presence detector 360° 1-channel master, consists of an integral 
unit, featuring On/Off control of 1 channel, presence detector, 
light sensor and integrated IR receiver. 

Pushbutton power switch and light fi ttings are connected directly 
to the detector which is fi tted fl ush with the ceiling. The detector 
can be installed and operated using the factory settings. 

However, for optimal light regulation, it is recommended 
that you adjust the detector settings to the conditions of the 
premises (light requirements). This is done via the integrated 
potentiometers or IR remote control type 41-926 (accessory).

Installation

Location:
The detector responds to movement and heat in relation to the 
surroundings. Avoid placing the detector close to heat sources 
such as cookers, electric radiators or ventilation systems, or 
moving objects such as hanging mobiles etc. This may cause 
unwanted activation. 

Fig. 1.

 

Range:
The recommended installation height for this detector is 2–3.4 m.
2.5 m is the optimal installation height. At this height the detector 
has a range of Ø 20 m on ground level and Ø 13.5 at 80 cm table 
height (without the lens cover). 

Fig. 2.

Extending the coverage area:
It is possible to increase the coverage area by using presence 
detector 41-702 (slave). It is possible to connect 10 slaves 
(41-702) to one 41-700 (master) which will control the load 
with its settings.

Master and slave presence detectors have the same range.

To achieve complete coverage by using several detectors, 
it is recommended that an overlap of approximately 30% is 
calculated. 

Fig. 3.

Installation:
The detector is designed for fl ush mounting in a PL/Euro socket. 

Fig. 4.

Connection:
The detector must only be connected to a power supply once 

all wire connections have been connected. After connection 
to the power supply, the detector will be ready to operate after 
approximately 40 seconds (warm-up time). 
 
The red LED fl ashes during warm-up. The end of the warm-up 
time is indicated with two short fl ashes from the green LED. 
Wiring diagram. 

Fig. 5.

Glossary

App. = Application, the method by which the detector will 
function.

Active on = The detector only switches on the light if the push-
button power switch is activated, depending on the lux setting. 
The light switches off automatically after a predetermined time 
after the last registered activity.
 
Auto on/off = The detector switches the light on automatically 
depending on the lux setting when activity is registered in the 
coverage area. The light switches off automatically after a 
predetermined time after the last registered activity.

Short press on = Press the pushbutton power switch < 1 second. 
This may switch on the light, depending on the setting.

Long press = Press the pushbutton power switch > 1 second 
and is light-independent. 

ECO off = Short press < 1 second, switches off the light at the 
same time. The detector will be blocked for 10 seconds.

Settings

Functions are confi gured via DIP switch.

Factory settings: 

Fig. 6.

App.: Auto On/Off with the option for short press On and ECO 
Off. 
Short press is light-dependent.
Lux: 200 lux
Time (Off-delay): 10 minutes
Sensitivity: High sensitivity
 
Settings:
Settings can be changed via potentiometers under the cladding 
or by using the IR remote control type 41-926 (accessory).

Selection of applications:
The detector can be set to function as: Active On/Auto Off or 
Auto On/Auto Off. This is done via DIP switch 1. 

Fig. 6.

It is also possible to select various functions using the connected 
operating button. This is done via the DIP switch 3. 

Fig. 6.

Setting of applications:
DIP switch 1:
On: Auto On/Off
Off: Active On/Auto Off

DIP switch 2:
Not used

DIP switch 3:
On: Only short press On. (ECO Off and long press deactivated) 
Off: Option for short press On and ECO Off. For long press > 1 
 

second the light will be switched on or off constantly for two  

 

hours + the set cut-off time, switched on or off.

The detector is supplied with a lens cover – this can 
be adjusted or removed for correct coverage.

Содержание 5703102207630

Страница 1: ...ar efter ca 40 sek opvarmningstid Den r de LED blinker under opvarmning Opvarmningstidens afslutning indikeres med 2 korte blink fra den gr nne LED Tilslutningsskema Fig 5 Ordliste App Applikation den...

Страница 2: ...r sensoren registrerer aktivitet i d kningsomr det og belysningsniveauet er under indstillet v rdi Lyset slukker automatisk efter en forudbestemt tid n r registre ring af aktivitet i sensorens d kning...

Страница 3: ...betjening Indstillinger via IR fjernbetjening Fig 8 Lock unlock Der trykkes 3 gange for at l se unlock sensoren op indstillingsmode Hvert tryk indikeres med gr nt blink i sensoren N r sensoren er i pr...

Страница 4: ...k On og 30 sek Off Alle vrige funktioner er blokeret For at oph ve funktionen inden de 8 timer er g et aktiveres 8 Hours igen n r sensoren er l st op Unlock Den r de LED stopper med at blinke og senso...

Страница 5: ...n A S Tel 45 7442 4726 Fax 45 7442 4035 info servodan dk www servodan com Fig 4 27 46 4 100 Gasket for IP54 Fig 3 Fig 1 30 Fig 2 24 m 6 m 3 4 m 9 m2 13 5 m 140 m2 2 5 m 0 8 m 20 m 300 m2 3 m 6 m 28 m2...

Страница 6: ...e d faut ou de perturbation du fonctionnement contacter un installateur lectricien agr Sous r serve de modifications Fig 5 Fig 7 Fig 6 Fig 8 Fig 9 41 700 Presence detector 360 1ch L1 L2 N L1 L1 L1 L1...

Страница 7: ...the power supply the detector will be ready to operate after approximately 40 seconds warm up time The red LED flashes during warm up The end of the warm up time is indicated with two short flashes f...

Страница 8: ...d when the detector detects movement the red LED and connected lighting will switch on for five seconds NB The walk test is daylight independent Examples Example 1 E g classroom DIP switch settings 1...

Страница 9: ...gent Avoid putting pressure on the lens If the lens or other parts of the detector are defective it they must be replaced Technical data Input Power supply 230 V AC 50 Hz 10 Power consumption 0 2 W Ou...

Страница 10: ...gs Pulse 2 min 5 min 10 min 15 min 30 min and 60 min There is also an eight hour 8 Hours constant illumination for operating a ventilation system HVAC system The detector must be unlocked Unlock first...

Страница 11: ...b 4 Anschluss Der Melder darf erst an Spannung angeschlossen werden wenn alle Leitungsverbindungen angeschlossen sind Nach dem Anschluss der Spannung ist der Melder nach ca 40 Sek Aufw rmzeit betriebs...

Страница 12: ...7 Test Um zu kontrollieren ob der Melder Bewegungen korrekt erkennt kann ein sogenannter Geh Test durchgef hrt werden Sie k nnen den Geh Test entweder ber das Time Potentiometer Minimumposition oder...

Страница 13: ...vom Tageslichtniveau immer mit dem Bet tigungsdrucktaster eingeschaltet werden 230 V Bet tigungsdrucktaster muss angeschlossen werden Die Einstellung des Lichtniveaus und der Ausschaltverz gerung wird...

Страница 14: ...Licht eingeschaltet werden soll weil das Tageslicht im Raum nicht mehr ausreicht Time Zeit Tasten Einstellen der Ausschaltverz gerung Es gibt 7 feste Einstellungen Pulse 2 Min 5 Min 10 Min 15 Min 30 M...

Страница 15: ...europ en ou PL Fig 4 Raccordement Le d tecteur ne doit tre mis sous tension que lorsque tous les raccordements ont t effectu s Apr s la mise sous tension le d tecteur est pr t fonctionner l issue de 4...

Страница 16: ...le d tecteur fonctionne correctement il est possible de faire un test de bon fonctionnement S lectionner le test de bon fonctionnement soit via le potentiom tre Time position minimum soit via le bouto...

Страница 17: ...ram trage du niveau de luminosit naturelle et de la temporisation de d connexion s effectue via les potentiom tres int gr s ou la t l commande IR 41 926 accessoire Exploitation et entretien La salet n...

Страница 18: ...osit minimale souhait e au moment o l clairage doit s allumer du fait que la luminosit naturelle n est plus suffisante dans la pi ce Touches Time temporisation de d connexion R glage de la temporisati...

Отзывы: