None, disables sensor.
•
Volt, old voltage sensor type where an internal table is used
to map signal to correct conversion formula.
•
Thrm, thermistor sensor to be used for all temperature
sensors.
•
GS-RA, Greystone return air sensor.
•
GS-RH, Greystone RH sensor.
•
SG-LP, Saginomiya Low Pressure transducer.
•
SG-HP, Saginomiya High Pressure transducer.
•
JC-RH, Johnson Controls RH sensor.
•
JC-LP, Johnson Controls Low Pressure transducer.
•
JC-HP, Johnson Controls High Pressure transducer.
•
BMS, Building Management System controlled sensor.
Future use and not fully implemented yet.
5.6.3.Analog Inputs
The
Samples
and
Sample Rate
properties are used to fine tune the
way analog inputs are read and translated into sensor readings. A
sensor reading is the average of all read samples.
5.6.4.Digital Inputs
The
Samples
and
Sample Rate
properties are used to fine tune the
way digital inputs are read and translated into alarms or other
inputs. A digital input will signal a state change when all samples
are the same and are different from current saved state.
6. Service
To reach these settings you need to enter a service password.
6.1. Force Demands
Use Force Demand to simulate compressor demands. This feature is used
to test the mechanics of the compressors. Select compressor to test.
Three properties can be changed for each compressor. Reheat controls the
Reheat valve, A/C controls the A/C valve and Pool Heat controls the Pool
Heat/Pool Bypass valves. Turning on just Pool Heat will not turn on the
compressor.
6.2. Force Contacts
Force Contacts is used to test all the Digital Outputs. This overrides any
internal control of corresponding features and is just a away to physically
test that a contact is working. One exception is the Compressor Power
contact that will cause the compressor control state machine to go into a
special forced mode state. We need to do this to ensure that we still will