Waterflow Dly

 property is the number of seconds unit will wait 

before checking for a waterflow problem after pool water heating 
is started (using compressor pool heating valve).

Waterflow Rec

 property controls for how long a waterflow alarm 

will stay active and pool heating will remain in recovery mode. 
After this time, the pool heating control will go back trying to heat 
pool again if there still is a demand for it and compressor is 
running. Note that auxiliary pool heater will still be used when 
recovering from a waterflow alarm.

Min Out Temp

 and 

Max Out Temp

 properties controls the range 

in which the Pool Out temperature has to be in relation to the Pool 
In temperature when using compressor to heat the pool. If outside 
this range, a Waterflow Alarm will be tripped with reason Pool 
Out.

5.3.5.Deadbands

This section is used to configure setpoint deadbands. Air 
temperature and pool temperature setpoints can be set in 1/10

th

 of a 

degree.

5.3.6.Sensors

Outdoor Air 

property control whether the outdoor air sensor 

should be used in control logic.

Supply Air 

property control whether the outdoor air sensor should 

be used in control logic.

Refresh Sensor

 property sets how often sensors will be read. 

Sensor reading will also be generated  when there is a change in 
the sensor reading. Refreshing sensors on a regular basis prevents 
us from getting stuck with no sensor readings for a long time when 
the system is stable.

Min Sample

 property controls for how many seconds we will wait 

at the minimum between two sensor readings before using a new 
sensor value sample in our calculations.

5.4. Compressor

Use

 Enabled

 property to enable or disable usage of compressors. 

Compressors are disabled by default when unit is shipped and still in 
Commission mode.

Compressors

 configures number of compressors used in the system.

OperatorPanel_4.15.14.doc

Page 19

7/12/2012

Содержание CommandCenter

Страница 1: ...l start otherwise blower will remain off and there will be a voltage monitor fault alarm Navigation Mode and Edit Mode The menu system implements two different modes where the keys have different mean...

Страница 2: ...hen you press the Back key Enter key will save the data and most of the time take you directly back to navigation mode covered under data types Data Types Most of the data properties you can change ar...

Страница 3: ...essages will popup over current menu screen The message can be cleared by pressing either key 1 or 2 Key 1 will clear current message and key 2 will clear all queued messages Messages can be of three...

Страница 4: ...s displayed in the summary 1 Setpoints 1 1 Temperature 1 2 Humidity 1 3 Pool Temp Optional 1 4 Economizer Optional 1 5 Freeze Stat Optional 1 6 Purge Temp Optional 1 7 Heat Recovery 2 Schedule 2 1 Emp...

Страница 5: ...ote OP Only visible on Remote OP 4 4 1 Version Info 4 4 2 RS 232 Port 4 4 3 RS 485 Port 5 Factory Settings 5 1 System 5 1 1 Role 5 1 2 Fire Reset 5 1 3 Temp Unit 5 1 4 Rem Control 5 1 5 Rem Cntrl 2 5...

Страница 6: ...ting 5 3 2 13 Learning 5 3 2 14 Emergency Heat 5 3 3 Humidity 5 3 3 1 Deg Min On 5 3 3 2 Deg Min Off 5 3 3 3 Temp Offset 5 3 3 4 High Humidity 5 3 3 5 Float Setpoint 5 3 4 Pool Heating 5 3 4 1 Enabled...

Страница 7: ...5 4 12 Alarm Stop 5 4 13 Anti Block 5 4 14 Wakeup Mode 5 4 15 Wakeup Time 5 4 16 SucTempL Dly 5 4 17 SucTempH Dly 5 4 18 DisTempL Dly 5 4 19 LP Alarm 5 4 20 LP Start 5 4 21 LP Max 5 4 22 HP Min 5 4 23...

Страница 8: ...o Test 5 5 2 3 Port D RS 485 5 5 2 3 1 User 5 5 2 3 2 Baud Rate 5 5 2 3 3 Databits 5 5 2 3 4 Parity 5 5 2 3 5 Echo Test 5 5 3 WebSentry 5 5 3 1 Enabled 5 5 3 2 Use DNS 5 5 3 3 IP 5 5 3 4 Port 5 5 3 5...

Страница 9: ...1 16 Discharge 2 5 6 1 17 Exhaust Air 5 6 1 18 Reheat Temp 5 6 1 19 Pool 2 In 5 6 1 20 Pool 2 Out 5 6 2 Sensor Type 5 6 2 1 Rel Humidity 5 6 2 2 Return Air 5 6 2 3 Outdoor Air 5 6 2 4 HP 1 5 6 2 5 LP...

Страница 10: ...Damper 6 2 2 3 Open Damper 6 2 2 4 Close Damper 6 2 2 5 Exhaust Fan 1 6 2 2 6 Exhaust Fan 2 6 2 2 7 OACC 6 2 3 Heating 6 2 3 1 Heater 1 6 2 3 2 Heater 2 6 2 3 3 Mod Heat 6 2 3 4 Pool 1 Heater 6 2 3 5...

Страница 11: ...6 4 Clear Alarm Log 6 5 Clear All Logs 6 6 Commission 6 6 1 Tested 6 6 2 Commissioned OperatorPanel_4 15 14 doc Page 11 7 12 2012...

Страница 12: ...ault does not apply e g Weekends Sunday 3 System 3 1 Ventilation Currently you can only turn the blower on or off on this screen Note that the blower might not come when turning it on There can be an...

Страница 13: ...s The status screen shows the status for different internal system components It s main purpose is for troubleshooting a running system where the information here can be passed back to tech support Th...

Страница 14: ...settings are Time zone can be set to 3 30 4 00 to 10 00 and GMT time The daylight property only determines if an extra hour should be added to the current time No automatic detection if we need to add...

Страница 15: ...vice password 5 1 System The Role property is used in units with more than 2 compressor circuits or when two units control the same space One unit or master board is configured as Master while second...

Страница 16: ...verload alarm BP Damper 50 sets the time it takes to open the bypass damper halfway starting from fully closed BP Damp Stable timer is the amount of time the bypass damper will wait after it has adjus...

Страница 17: ...t Delay to control for how long a heating issue condition need to last before heating control will be reset and start all over again Use Reset Time to control for how long the heating control will be...

Страница 18: ...ity setpoint based on the outdoor air temperature as follows More than 50 F 50 Between 30 F and 50 F 45 Between 10 F and 30 F 40 Less than 10 F 35 There is a 2 degree deadband when moving to a higher...

Страница 19: ...d to configure setpoint deadbands Air temperature and pool temperature setpoints can be set in 1 10th of a degree 5 3 6 Sensors Outdoor Air property control whether the outdoor air sensor should be us...

Страница 20: ...e is not closing properly Using this timer will close both solenoid valves when one valves needs to be closed After timeout the other valve is opened Typically you will not set this one to more than 3...

Страница 21: ...gh suction temperature alarm DisTempL Dly is the debounce delay timer for the low discharge temperature alarm LP Alarm pressure setting controls at what Low Pressure level compressor will trip on Low...

Страница 22: ...seconds means valve will open for 5 seconds and then be closed for 55 seconds Valve Open timer determines for how long valve will be open in a full valve cycle see Valve Cycle 5 5 Network 5 5 1 TCP IP...

Страница 23: ...e the port even with the hardware error Reply Delay defines for how long we will wait for a reply message before considering it a communication fault 5 5 3 WebSentry These properties controls WebSentr...

Страница 24: ...o set a unique device ID for unit on the BACnet network Port can be used to change the default port setting 5 5 5 Modbus Use these properties to configure Modbus communication 5 5 6 LON Use these prop...

Страница 25: ...ts are read and translated into alarms or other inputs A digital input will signal a state change when all samples are the same and are different from current saved state 6 Service To reach these sett...

Страница 26: ...to monitor by using the arrows keys Select 1 to start monitoring To stop pause messages you can press key 2 anytime Press Enter to clear the screen Select back top stop console or to go back and selec...

Страница 27: ...tarted anytime but to enable the compressors and to be able to change the Commissioned option a factory password is required When changing Commissioned to Yes all the logs will be cleared and the unit...

Отзывы: