Waterflow Dly
property is the number of seconds unit will wait
before checking for a waterflow problem after pool water heating
is started (using compressor pool heating valve).
Waterflow Rec
property controls for how long a waterflow alarm
will stay active and pool heating will remain in recovery mode.
After this time, the pool heating control will go back trying to heat
pool again if there still is a demand for it and compressor is
running. Note that auxiliary pool heater will still be used when
recovering from a waterflow alarm.
Min Out Temp
and
Max Out Temp
properties controls the range
in which the Pool Out temperature has to be in relation to the Pool
In temperature when using compressor to heat the pool. If outside
this range, a Waterflow Alarm will be tripped with reason Pool
Out.
5.3.5.Deadbands
This section is used to configure setpoint deadbands. Air
temperature and pool temperature setpoints can be set in 1/10
th
of a
degree.
5.3.6.Sensors
Outdoor Air
property control whether the outdoor air sensor
should be used in control logic.
Supply Air
property control whether the outdoor air sensor should
be used in control logic.
Refresh Sensor
property sets how often sensors will be read.
Sensor reading will also be generated when there is a change in
the sensor reading. Refreshing sensors on a regular basis prevents
us from getting stuck with no sensor readings for a long time when
the system is stable.
Min Sample
property controls for how many seconds we will wait
at the minimum between two sensor readings before using a new
sensor value sample in our calculations.
5.4. Compressor
Use
Enabled
property to enable or disable usage of compressors.
Compressors are disabled by default when unit is shipped and still in
Commission mode.
Compressors
configures number of compressors used in the system.