4.4. Remote OP
This menu selection is only visible on a remote OP (operator panel
connected to the board using a serial port).
Under version info you can see the software version of the remote OP as
well as the minimum main board software version required to be able to
communicate with a main board.
RS-232 and RS-235 are used to configure the remote OP end of the serial
port interface. Only a subset of the serial port parameters are available
compared to what you can configure from the main board serial port
configuration. See 5.5.2 for description of parameters.
5. Factory Settings
To reach these settings you need to enter a service password.
5.1. System
The
Role
property is used in units with more than 2 compressor circuits or
when two units control the same space. One unit (or master board) is
configured as Master while second unit (or slave board) is configured as a
slave. Default role is Single Unit.
Fire Reset
property controls how the system will recover after a Fire
Alarm. Set to auto, system will automatically go back to normal once the
alarm is cleared. If set to Manual, a System Restart is required to make the
system operational again.
Use
Temp Unit
property to set temperature unit to be used in the system
(Celsius or Fahrenheit).
Use the
Rem Control
and
Rem Cntrl 2
properties to enable remote
control for a specific device or option. The remote input signal is used to
control the selected device or option.
OperatorPanel_4.15.14.doc
Page 15
7/12/2012