Sentry Sample Sentry II 33
Figure 27. Channel Configuration on Sample Sentry II CPU Board
Terminals labeled V# are not used during calibration.
Calibrate each channel per Table 3 and instructions below.
Table 3. Channel Calibration Reference
Channel #
Range
Input
P&ID Ref
+
–
Channel 1
4-20 mA
Flow
FT-1
1+
1-
Channel 2
4-20 mA
Outlet Pressure
PT-2
2+
2-
Channel 3
4-20 mA
Inlet Pressure
PT-1
3+
3-
Channel 4
0-2.5 V
Inlet Temp
TE-2
T1
COM
Channel 5
0-2.5 V
OutletTemp
TE-1
T2
COM
Channel 6
0-2.5 V
Cooling Temp
TE-3
T3
COM
3.
For calibration of channels 1–3 connect a calibrated milliamp supply to TB1 terminals
of the CPU board and – for the appropriate channel. Input 4 mA. Press the
Enter key.
4.
The controller is done calibrating the 4 mA when the Offset value stops adjusting and
the input value on the screen changes from 4 mA to 20 mA. Input 20 mA for selected
channel. Press the Enter key.
5.
The controller is done calibrating the 20 mA when the Gain value stops adjusting.
Press the Enter screen to go to the channel selection screen.
6.
Repeat steps 4-6 for remaining channels requiring 4-20 mA calibration.
7.
For calibration of channels 4-6 connect a calibrated voltage supply to TB1 terminals of
the CPU board marked T1-T3 and COM for the appropriate channel.
Содержание Sample Sentry II High Pressure
Страница 7: ...Sentry Sample Sentry II 7 Figure 1 Typical P ID of a Sample Sentry II System...
Страница 8: ...8 Sentry Equipment Corp Figure 2 P ID of a Sample Sentry II system with Secondary Cooling...
Страница 11: ...Sentry Sample Sentry II 11 Figure 3 Controller Front Panel...
Страница 24: ...24 Sentry Equipment Corp Figure 25 General Arrangement High Pressure Model...
Страница 26: ...26 Sentry Equipment Corp Figure 26 Electrical Wiring Diagram...
Страница 43: ...Sentry Sample Sentry II 43 This page is intentionally left blank...
Страница 44: ...44 Sentry Equipment Corp This page is intentionally left blank...