MRP4 / MRP5 / MRP6

P. 4 / 8

EM-4824 Rev.7

OUTPUT SPAN ADJUSTABILITY

The servo-control circuit compares and amplifies input sig-
nal (setpoint) and feedback signal from a potentiometer, and 

drives the motor to such direction to minimize difference of 

the two signals.

The general operational range is 0 – 90 deg. or 0 – 180 deg. 

with a 5-deg. margin at both limits.  See Figure 5.

INSTALLATION

The following is a general procedure for mounting the MRP 

to a valve with a yoke and coupling.

Be sure NOT TO CHANGE factory adjusted setting of the 
MRP.

Remove power supply during the procedure unless other-
wise specified.

0

25

50

75

100

25

50

75

100

0

INPUT SIGNAL (%)

STEM POSITION (%)

Span Counterclockwise

Zero Clockwise

Zero Counterclockwise

Span Clockwise

Adjustable Zero Range

Adjustable Span Range

Figure 4.  I/O Characteristics (Adjustable Range)

Table 1.  Available Span Range for Each Model
 

MODEL 

MIN. SPAN 

MAX. SPAN

 

MRP4-1 

 

 

 

 

MRP5-1 

45° 

90°   

 

MRP6-1 

 

MRP4-2 

90° 

180°

  

 

MRP6-2

Standard Zero Position

M

in

im

um

 s

pa

n

M

ax

im

um

 s

pa

n

M

ax

im

um

 O

pe

ra

tio

R

an

ge

5 deg.

5 deg.

Adjustable Zero Range

Adjustable Span Range

Figure 5.  Minimum & Maximum Span

MRPx

Bolts (M5)

Output Stem

Coupling

Yoke

Valve Bonnet

Figure 6.  Example of the MRP Mounted to a Valve

1)  Supply power to the MRP and apply 0% input (100% for 

direct action).  Turn the output stem fully clockwise (seen 
from the cover).

2) Turn the valve stem to fully closed position (fully clock-

wise).

3)  Set the yoke to the MRP.
4)  Set the coupling to the valve stem and fit the MRP out

-

put stem into the coupling.  Then fix the yoke and valve 
temporarily.

5)  Fix the coupling so that there is no eccentricity between 

both stems.

6)  Fix the yoke and valve firmly after checking the eccen

-

tricity of both stems again.

7)  Attach the position indicator if required.

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Содержание M-SYSTEM DANAGE

Страница 1: ...h 0 Without 5 INPUT Current A 4 20 mA DC Input resistance 250 Ω Z Specify current See INPUT SPECIFICATIONS Voltage 6 1 5 V DC Input resistance approx 1 MΩ 0 Specify voltage See INPUT SPECIFICATIONS 6 CE MARKING C With 0 Without 7 POWER INPUT AC Power K3 100 120 V AC Operational voltage range 90 132 V 47 66 Hz Not selectable for CE L3 200 240 V AC Operational voltage range 180 264 V 47 66 Hz Not se...

Страница 2: ...sed signals Limit switch contact Rating 125 V AC 0 75 A cos ø 1 30 V DC 0 6 A resistive load Mechanical life 3 10 7 cycles Maximum operation frequency 60 cycles min INSTALLATION Power consumption AC Approx 25 VA DC Approx 0 6 A Operating temperature 5 to 55 C 23 to 131 F Operating humidity 30 to 85 RH non condensing Vibration 0 5 G max Mounting position All directions Do not mount the actuator wit...

Страница 3: ...or above 100 Limiters are set at approx 0 5 for the full closed side approx 100 5 for the full open side TERMINAL CONNECTIONS black 1 U V COM1 COM2 white 2 red 3 green 4 yellow 5 blue 6 gray 7 brown 8 1 to 8 Terminal No of terminal box Full open closed signals and forced open close signals are optional POWER INPUT POSITION OUTPUT 1 5V DC FULL OPEN or FULL CLOSED SIGNAL output stem turned CCW outpu...

Страница 4: ...15 59 dia 22 87 67 2 64 12 0 043 sq 70 2 76 dia 0 MANUAL HANDLE STEM 6 24 sq 2 G 1 2 CONDUIT 4 M6 12 47 deep 90 deg pitch YOKE CONNECTION 110 4 33 136 5 35 199 7 83 16 63 YOKE SURFACE 35 1 38 60 2 36 7 5 30 23 91 34 134 20 79 32 5 1 28 Cable connector or leadwires not provided with terminal box TERMINAL BOX TYPE Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox se...

Страница 5: ...COM2 CCW CW FULL OPEN or FULL CLOSED SIGNAL POSITION OUTPUT 1 5V DC POWER MODE SELECTOR POWER INPUT STATUS POT MOTOR LIMIT SW Full open closed signals and forced open close signals are optional Disregard the switching regulator circuit for DC power input Specifications are subject to change without notice Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox sentronic...

Страница 6: ...eters 6 inches above the cover OUTDOOR USE When installing the MRP outdoor or where it is exposed to rain or water drops be sure to fasten the cable connector tightly and leave a slack of the cable Do not mount the MRP in such direction that the output stem or cable connector is at the top of the MRP unit ELECTRICAL CONNECTION With DC power type unit power supply and signal lines are not isolated ...

Страница 7: ... life of the actuator FUSE A fuse is equipped for protection against overload current When you turn the power supply on check that the power LED is on If it is off check that the fuse is melted Replace it with a new one If the new fuse is melted again soon after it has been re placed there may be problems with the control PCB or the motor Contact M System or sales representative RE STARTING TIMER ...

Страница 8: ...erse Actions Operation at Abnormally Low Input Power Indicator green with power supplied Input Indicator green with input applied Status Indicator red blinks in 2 sec intervals blinks in 0 5 sec intervals with mechanical lock detected Remark Turning adjustment potentiom eters and switches with a torque exceed ing their tolerance may destroy their stop pers Turn them carefully and stop where they h...

Страница 9: ...EL MIN SPAN MAX SPAN MRP4 1 MRP5 1 45 90 MRP6 1 MRP4 2 90 180 MRP6 2 Standard Zero Position M i n i m u m s p a n M a x i m u m s p a n M a x i m u m O p e r a t i o n R a n g e 5 d e g 5 d e g Adjustable Zero Range Adjustable Span Range Figure 5 Minimum Maximum Span MRPx Bolts M5 Output Stem Coupling Yoke Valve Bonnet Figure 6 Example of the MRP Mounted to a Valve 1 Supply power to the MRP and ap...

Страница 10: ...gnal COM2 COM1 COM2 POWER black 1 U V white 2 red 3 INPUT COM1 green 4 POSITION OUTPUT 1 5V DC yellow 5 blue 6 gray 7 brown 8 FULL OPEN or FULL CLOSED SIGNAL output stem turned CCW output stem turned CW FORCED OPEN CLOSE SIGNAL output stem turned CCW output stem turned CW OVERLOAD FULL CLOSED FULL CLOSED or OVERLOAD SIGNAL Remark The yellow wire must be left unconnected if the position output sign...

Страница 11: ... The following explanation applies to reverse action For di rect action read the value in the brackets Remark Applying an over torque to the adjustments may destroy stoppers or other sections of them Use a small sized screwdriver and be sure to stop turning as soon as they hit the stoppers ADJUSTMENT PROCEDURE A Zero and Span Apply power supply voltage and 0 100 input Turn ZERO adjustment until th...

Страница 12: ...and Check input signal Narrow the deadband ON Flash 0 5 sec Actuator mechanism is damaged Repair Overload cause by a foreign object caught in the valve Check the valve Control PCB damaged Repair or replace Wiring error at the motor or position sensor Check the connector Low power voltage or insufficient capacity Check the power supply ON OFF Flash 2 sec Abnormal input signal Check the input signal...

Отзывы: