HOLDING REGISTERS

16

Minimum relative 

humidity range

unsigned int.

Minimum value of the rH range; cannot be 

set higher than max. rH range minus 5

 

50 — (Max. range — 50) 

50

200 = 

20,0 % rH

17

Maximum relative 

humidity range

unsigned int.

Maximum value of rH range; cannot be set 

lower than min. rH range plus 5% 

(Min. range + 50) – 850

850

850= 

85,0 % rH

18—19

Reserved, return “0”.

20

Minimum temperature

alert

unsigned int. Minimum temperature alarm value

Min. temperature range — Max. 

temperature alarm

0

100 = 

10,0 

º

21

Maximum 

temperature alert

unsigned int. Maximum temperature alarm value

Min. temperature alarm — Max. 

temperature range

500

500 = 

50,0 

º

C

22

Minimum relative

humidity alert

unsigned int. Minimum relative humidity alarm value

Min. relative humidity range —

Max. relative humidity alarm

50

200 = 

20,0 % rH 

23

Maximum relative

humidity alert

unsigned int. Maximum relative humidity alarm value.

Min. relative humidity alarm —

Max. relative humidity range

850

850 = 

85,0 % rH 

24—25

Reserved, return “0”.

26

LED indication 

unsigned int. LED indication related to one of the 

parameters

1—2 

1

1 = 

2 =

Temperature

rH

27—29 

Reserved, return “0”. 

30

Modbus network 

resistor termination 

(NBT)

unsigned int. Sets device as ending the line or not by 

connecting NBT

0—1

0

0 = 

1 = 

NBT disconnected

NBT connected

31—33

Reserved, return “0”. 

34

Active light level 

unsigned int. The ambient light level above which 

‘Active’ is indicated in input register 6

0—32.000

100

100= 

100 lx

35

Standby light level

unsigned int. The ambient light level below which 

‘Standby’ is indicated in input register 6

0—32.000

10

10 = 

10 lx

36

Modbus registers 

reset

unsigned int.

Resets Modbus Holding registers to 

default values. When finished this register 

is automatically reset to ‘0’

0—1

0

0 = 

1 = 

Idle

Reset Modbus registers

37—40

Reserved, return “0”

If you want to find out more about Modbus over serial line, please visit:

 

http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf

TRANSPORT AND STORAGE

Avoid shocks and extreme conditions; stock in original packing.

WARRANTY AND RESTRICTIONS

Two years from the delivery date against defects in manufacturing. Any modifications 
or alterations to the product after the date of publication relieve the manufacturer 
of any responsibilities. The manufacturer bears no responsibility for any misprints or 
mistakes in this data. 

MAINTENANCE

In normal conditions this product is maintenance-free. If soiled, clean with a dry or 
damp cloth. In case of heavy pollution, clean with a non-aggressive product. In these 
circumstances the unit should be disconnected from the supply. Pay attention that 
no fluids enter the unit. Only reconnect it to the supply when it is completely dry.

RSTHM-2

COMBINED T AND RH 
ROOM TRANSMITTER

Содержание RSTHM-2

Страница 1: ...Mounting and operating instructions RSTHM 2 COMBINED T AND RH ROOM TRANSMITTER ...

Страница 2: ...DES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAMS 5 MOUNTING OPERATING INSTRUCTIONS IN STEPS 5 OPERATING INSTRUCTIONS 7 VERIFICATION OF INSTALLATION INSTRUCTIONS 8 MODBUS REGISTER MAPS 8 TRANSPORT AND STORAGE 10 WARRANTY AND RESTRICTIONS 10 MAINTENANCE 10 RSTHM 2 COMBINED T AND RH ROOM TRANSMITTER ...

Страница 3: ... possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts always treat the product as if it is live Always disconnect the power sup...

Страница 4: ...oor use only TECHNICAL DATA Maximum power consumption 0 0 312 W Nominal power consumption in normal operation 0 0 234 W Imax 13 mA Selectable temperature range 0 50 C Selectable relative humidity range 5 85 Ambient light sensor with adjustable active and standby level Bootloader for updating the firmware via Modbus RTU communication 3 LEDs for status indication Accuracy 0 4 C 0 50 C 3 rH 5 85 rH d...

Страница 5: ...G INSTRUCTIONS IN STEPS Before you start mounting the RSTHM 2 room transmitter read carefully Safety and Precautions Choose a smooth surface for installation a wall panel and etc Follow these steps 1 Using a flat screwdriver remove the front white cover by releasing the snap fits on its both sides see Fig 1 Snap fits release 2 Insert the crimped RJ45 cable through the opening on the rear plate and...

Страница 6: ...floor 4 Do the wiring according to the wiring diagram see Fig 4 Fig 4 Wiring diagram B A GND 24 VDC 8 mm 8 mm 8 mm 8 mm RJ45 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 24 VDC GND A B Supply voltage 24 VDC Ground Modbus RTU communication signal A Modbus RTU communication signal B B A GND 24 VDC 8 mm 8 mm 8 mm 8 mm RJ45 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 5 Put back the cover and snap it in 6 Switch on the mains s...

Страница 7: ... enter Boot mode put a jumper onto pins 3 and 4 of the P1 header and restart the power supply see Fig 5 Once Boot mode is activated the firmware can be updated via SM Boot application part of 3SModbus software suite or Sensistant Fig 5 P1 header 1 2 3 4 5 Put a jumper onto pins 1 and 2 and wait for at least 5 seconds to reset the Modbus communication parameters 1 2 3 4 5 Put a jumper onto pins 3 a...

Страница 8: ...in luxes If the measured light level is below the Standby level Input Register 6 indicates Standby If the measured ambient light level is above the Active level Input Register 6 indicates Active If the measured ambient light level is between the Active and Stand by level Input Register 6 indicates Low intensity therefore it is advisable to set Active and Standby levels in Holding Registers 34 and ...

Страница 9: ...int Flag indicates that measured temperature is outside set range limit values Set to 1 when the measured value is outside the temperature range limit values defined by holding registers 14 and 15 0 1 0 1 Temperature range is OK Temperature range is too high low 18 Relative humidity range limit flag unsigned int Flag indicates that measured relative humidity is outside set range limit values Set t...

Страница 10: ...y connecting NBT 0 1 0 0 1 NBT disconnected NBT connected 31 33 Reserved return 0 34 Active light level unsigned int The ambient light level above which Active is indicated in input register 6 0 32 000 100 100 100 lx 35 Standby light level unsigned int The ambient light level below which Standby is indicated in input register 6 0 32 000 10 10 10 lx 36 Modbus registers reset unsigned int Resets Mod...

Отзывы: