WIRING AND CONNECTIONS
Wiring diagram
RJ45 sockets (Power over Modbus)
Pin 1
24 VDC
Supply voltage
Pin 2
Pin 3
A
Modbus RTU communication, signal A
Pin 4
Pin 5
/B
Modbus RTU communication, signal /B
Pin 6
Pin 7
GND
Ground, supply voltage
Pin 8
/B
A
GND
24 VDC
8 mm
8 mm
8 mm
8 mm
RJ45
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Terminal Block 1
VIN
Supply voltage 24 VDC
GND
Supply voltage, ground
A
Modbus RTU communication, signal A
/B
Modbus RTU communication, signal /B
Terminal Block 2
AO1
Analogue / modulating output 1 for temperature
measurement (0—10 VDC / 0—20 mA / PWM)
GND
Ground AO1
AO2
Analogue / modulating output 2 for relative humidity
measurement (0—10 VDC / 0—20 mA / PWM)
GND
Ground AO2
AO3
Analogue / modulating output 3 for CO
2
measurement
(0—10 VDC / 0—20 mA / PWM)
GND
Ground AO3
The unit needs to be supplied via the RJ45 connector or via the connection
terminals. Do not connect the device via the RJ45 connector and the terminal block
simultaneously!
MOUNTING & OPERATING INSTRUCTIONS IN STEPS
Before you start mounting the unit, read carefully
“Safety and Precautions”
.
Choose a smooth surface for installation (a wall, panel and etc.).
Follow these steps:
1.
Using a flat screwdriver, remove the front white cover by releasing the snap-fits
on its both sides (see
Fig. 1
Snap-fits release
).
2.
Insert the crimped RJ45 cable through the opening on the rear plate and plug it
into the socket (see
Fig. 2
Mounting dimensions
).
3.
Using suitable fastening materials (not supplied), position the room sensor at
least 1,5 m from the floor. When planning the installation, allow enough clearance
for maintenance and service. Mount the sensor in a well-ventilated area. Mind
the correct mounting position and unit dimensions. See
Fig. 2
and
Fig. 3
.
ATTENTION
RSMFH-2R
MULTIFUNCTIONAL
ROOM TRANSMITTER