OPERATING INSTRUCTIONS

NOTE

For detailed information and settings, refer to the product Modbus register map, 
which is attached to the article code on our website. 

Calibration procedure:

Sensor calibration is not necessary.
In the unlikely event of CO

2

 sensor element failure, this component can be replaced. 

All sensor elements are calibrated and tested in our factory.

Bootloader

Thanks to the bootloader functionality, the unit firmware can be updated via Modbus 
RTU communication. With 3SM boot Application (part of 3SM Center software 
suite), ‘boot mode’ is automatically activated and the firmware can be updated.

NOTE

Make sure the power supply does not get interrupted during “bootload” procedure, 
otherwise you risk losing unsaved data. 

LED indications

1. 

 When the green LED is on, the measured value (temperature, relative humidity or 
CO

2

) is between the minimum and maximum alert range values (

Fig. 5 - 1

).

2. 

 When the yellow LED is on, the measured value (temperature, relative humidity 
or CO

2

) is in the alert range (

Fig. 5 - 2

).

3. 

 When the red LED is on, the measured value (temperature, relative humidity or 
CO

2

) is below the minimum measurement range value or above the maximum 

value. Blinking red LED indicates loss of communication with a sensor (

Fig. 5 - 3

). 

Fig. 5 LED indications

3

2

1

NOTE

By default, the LED indication refers to temperature measurements. This can be 
changed to relative humidity values via Modbus Holding Register 79 (see 

Table

 

Holding registers).

NOTE

Green LED intensity can be adjusted between 0 and 100 % with a step of 10 % 
according to the value set in Holding register 80.

Ambient light sensor

The measured light intensity in lux is available in Input Register 41. Additionally, 
an active and standby level can be defined in Holding registers 35 and 36. Input 
Register 42  indicates if the measured value is below standby level, above active 
level or in between both levels:

 

 Ambient light level < standby level: Input Register 42 indicates “Standby”.

 

 Ambient light level > active level:  Input Register 42 indicates “Active”. 

 

 Standby level < Ambient light level < Active level: Input Register 42 indicates “Low 
intensity”. 

RSMFH-2R

MULTIFUNCTIONAL 
ROOM TRANSMITTER 

Содержание RSMFH-2R

Страница 1: ...Mounting and operating instructions RSMFH 2R MULTIFUNCTIONAL ROOM TRANSMITTER ...

Страница 2: ...ES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 OPERATIONAL DIAGRAMS 5 WIRING AND CONNECTIONS 6 MOUNTING OPERATING INSTRUCTIONS IN STEPS 6 OPERATING INSTRUCTIONS 9 VERIFICATION OF INSTALLATION INSTRUCTIONS 10 TRANSPORT AND STORAGE 10 WARRANTY AND RESTRICTIONS 10 MAINTENANCE 10 RSMFH 2R MULTIFUNCTIONAL ROOM TRANSMITTER ...

Страница 3: ... work environment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconnect the power supply before c...

Страница 4: ... load 50 kΩ RL 50 kΩ 0 20 mA mode max load 500 Ω RL 500 Ω PWM open collector type mode PWM Frequency 1 kHz min load 50 kΩ RL 50 kΩ PWM voltage level 3 3 VDC or 12 VDC Selectable temperature range 0 50 C Selectable relative humidity range 5 85 Selectable CO2 range 0 2 000 ppm Ambient light sensor with adjustable active and standby level Replaceable CO2 sensor element 3 LEDs for status indication Ac...

Страница 5: ...al commercial and light industrial environments Amendments A1 2011 and AC 2012 to EN 61000 6 3 EN 61326 1 2013 Electrical equipment for measurement control and laboratory use EMC requirements Part 1 General requirements EN 61326 2 3 2013 Electrical equipment for measurement control and laboratory use EMC requirements Part 2 3 Particular requirements Test configuration operational conditions and pe...

Страница 6: ...C 0 20 mA PWM GND Ground AO3 The unit needs to be supplied via the RJ45 connector or via the connection terminals Do not connect the device via the RJ45 connector and the terminal block simultaneously MOUNTING OPERATING INSTRUCTIONS IN STEPS Before you start mounting the unit read carefully Safety and Precautions Choose a smooth surface for installation a wall panel and etc Follow these steps 1 Us...

Страница 7: ... 9 8 74 5 104 5 20 104 5 25 6 70 5 Fig 3 Mounting position Correct Incorrect Position at min 1 5 m from the floor 4 Do the wiring according to the wiring diagram see Fig 4 Fig 4 Wiring and connections Correct connections 24 VDC GND A B Output 1 T Output 2 rH Output 3 CO2 Output 1 T Output 2 rH Output 3 CO2 24 VDC GND A B RSMFH 2R MULTIFUNCTIONAL ROOM TRANSMITTER ...

Страница 8: ...cument attached to the article code on the website and contains the registers list Products with earlier firmware versions may not be compatible with this list NOTE 5 Optional settings To assure correct communication the NBT needs to be activated in only two devices on the Modbus RTU network If necessary enable the NBT resistor via 3SModbus or Sensistant Holding register 9 Example 1 Example 2 RX Т...

Страница 9: ...easured value temperature relative humidity or CO2 is in the alert range Fig 5 2 3 When the red LED is on the measured value temperature relative humidity or CO2 is below the minimum measurement range value or above the maximum value Blinking red LED indicates loss of communication with a sensor Fig 5 3 Fig 5 LED indications 3 2 1 NOTE By default the LED indication refers to temperature measuremen...

Страница 10: ...gainst defects in manufacturing Any modifications or alterations to the product after the date of publication relieve the manufacturer of any responsibilities The manufacturer bears no responsibility for any misprints or mistakes in this data MAINTENANCE In normal conditions this product is maintenance free If soiled clean with a dry or damp cloth In case of heavy pollution clean with a non aggres...

Отзывы: