www.sentera.eu
MIW-GTE-EN-000 - 17 / 01 / 2018
8 - 11
back to the table of contents
-DT version mounting steps:
Back to -DM version
▶
1.
Make sure the GTE controller is not connected to the mains supply.
2.
Unscrew the front cover and open the enclosure. Mind the wires that connect
the potentiometer with the printed circuit board.
3.
Fix the unit to the wall or panel using the provided screws and dowels. Mind the
correct mounting position and unit mounting dimensions. (See
Fig. 6
Mounting
dimensions
and
Fig. 7
Mounting position
.)
Fig. 6 Mounting dimensions
Fig. 7 Mounting position
140
102
140
97
140
204
Acceptable
Not acceptable
4.
Set the maximum speed trimmer to the desired value (see
Fig. 8 Max. speed
trimmer
). You can choose from the range 170—230 VAC. The factory setting is
230 VAC.
Fig. 8 Max. speed trimmer
Vmax set from 170 VAC (left) to 230 VAC
(right) (factory pre-set to max.)
6.
Put back the front cover and fix it.
7.
Plug the motor / fan cable into the Schuko socket.
ELECTRONIC
FAN SPEED CONTROLLER
GTEX1-60