www.sentera.eu

MIW-EVSS-DM-EN-000 - 18 / 12 / 2018

9 - 16

back to the table of contents

5. 

 Select the required analog input type and mode, start mode and OFF level 
mode by the DIP switch on the board. (See 

Fig. 4

 

DIP switch settings

.)

Fig. 4 DIP switch settings

Ascending / descending 
mode selection  
(DIP switch, position 1)

ON

1   2   3   4

ON - Descending mode:  

10—0 VDC / 20—0 mA

OFF - Ascending mode:  

0—10 VDC / 0—20 mA

OFF level selection  
(DIP switch, position 2)

ON

1   2   3   4

ON - enabled

OFF - disabled

Kick start / soft start 
selection  
(DIP switch, position 3)

ON

1   2   3   4

ON - Kick start

OFF - Soft start

Input mode selection  
(DIP switch, position 4)

ON

1   2   3   4

ON - Current mode  

(0—20 mA)

OFF - Voltage mode 

(0—10 VDC)

VR3

Off 

level

adj

Min.

speed

adj

Max.

speed

adj

ON

0 - 10v / 10 - 0v

0 - 10v / 0 - 20 m

A

Off

 level

NB

T

Kicksta

rt

1 2 3 4

VR2

VR1

1

6. 

 The Network Bus Terminator (NBT) is used to set the device as an end device 
and by default the NBT is disconnected. It is put manually onto the pins to 
be connected (see 

Fig. 5

). To assure correct communication, the NBT jumper 

needs to be activated in only two devices on the Modbus RTU network (see 

Example 1 

and

 Example 2

). 

Example 1

Example 2

Fig. 5 Network bus 

resistor jumper

RX

ТX

NBT

NBT

NBT

Slave 2

Master

Slave n

Slave 1

Slave 2

Slave 1

RX

ТX

NBT

NBT

Master

Slave n

ATTENTION

On a Modbus RTU network, two bus terminators (NBTs) need to be activated

ATTENTION

If an AC power supply is used with any of the units in a Modbus network, the 
GND terminal should NOT BE CONNECTED to other units on the network or 
via the CNVT‑USB‑RS485 converter. This may cause permanent damage to the 
communication semiconductors and / or the computer!

7. 

Connect the power supply cable.

8. 

 Adjust the max. speed by trimmer (if necessary). The default setting is Us 
(230  VAC). See 

Fig. 6

 

Max. speed trimmer

.

9. 

 Adjust the min. speed by trimmer (if necessary). The default setting is 30 % Us 
(69 VAC). See 

Fig. 7

 

Min. speed trimmer

.

10. 

 Adjust the OFF level value by trimmer (if necessary). The default setting is 
0  VAC. See 

Fig. 8

 

Off level trimmer

.

EVSS

ELECTRONIC FAN SPEED 
CONTROLLER WITH TK

Содержание EVSS Series

Страница 1: ...EVSS ELECTRONIC FAN SPEED CONTROLLER WITH TK Mounting and operating instructions ...

Страница 2: ...NDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 WIRING AND CONNECTIONS 5 OPERATIONAL DIAGRAMS 6 MOUNTING INSTRUCTIONS IN STEPS 8 VERIFICATION OF INSTALLATION INSTRUCTIONS 10 OPERATING INSTRUCTIONS 11 MODBUS REGISTER MAPS 12 TRANSPORT AND STORAGE 16 WARRANTY AND RESTRICTIONS 16 MAINTENANCE 16 EVSS ELECTRONIC FAN SPEED CONTROLLER WITH TK ...

Страница 3: ...ment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconnect the power supply before connecting ser...

Страница 4: ...speed control in ventilation systems For indoor use only TECHNICAL DATA Power supply 230 VAC 10 50 60 Hz Analog input voltage 0 10 VDC 10 0 VDC current 0 20 mA 20 0 mA Analog input modes ascending or descending Analog input functionality Normal mode Logic mode Remote control input normal or timer functionality Regulated output 30 100 Us Max output load depends on the version Unregulated output L1 ...

Страница 5: ...C EN 61326 WEEE Directive 2012 19 EU RoHs Directive 2011 65 EU WIRING AND CONNECTIONS L Supply voltage 230 VAC 10 50 60 Hz N Neutral PE Earth terminal L1 Unregulated output 230 VAC max 2 A U1 U2 Regulated output to the motor TK TK Thermal contact N Neutral AL Alarm output 230 VAC 1 A SW Remote control switch A Modbus RTU RS485 signal A B Modbus RTU RS485 signal B V Supply output 12 VDC 1 mA Ai Ana...

Страница 6: ...C mA 10 VDC 20 mA 6 VDC 12 mA U out 100 75 70 30 Umax range Umin range Off level Off level enabled Ascending mode calculation formula Uout Umax Aimax Off level Ai Off level Umax Umin Descending mode calculation formula Uout Umax Aimax Off level Ai Off level Umax Umin t s Umax Umin 0 Ai 10 VDC 20 mA Uout 100 75 70 30 0 VDC 0 mA Umax range Umin range Kick start time t s Umax Umin 0 Ai 10 VDC 20 mA U...

Страница 7: ... off level Timer mode Logic mode 0 t s 5 VDC 2 5 VDC Remote Switch VDC Stand by Operate Voltage amplitude range Switch control signal t s 0 Uout 100 75 Umax range Kick start time Operation timer Controller is off Kick start enabled Soft start enabled t t t t SW ON ON Holding register 18 Holding register 21 Soft start duration Soft start duration Start Output Umax Timer Soft start Stop Start Stop O...

Страница 8: ...ng position and Fig 2 Mounting dimensions Fig 1 Mounting dimensions Fig 2 Mounting position 140 102 4 x 4 5 0 124 205 92 Correct Incorrect 3 Connect the motor fan 4 The unregulated output L1 N can be used to connect a light indicator or to control a damper actuator a valve etc if necessary See Fig 3 Fig 3 Wiring and connections VR3 Off level adj Min speed adj Max speed adj ON 0 10v 10 0v 0 10v 0 2...

Страница 9: ...manually onto the pins to be connected see Fig 5 To assure correct communication the NBT jumper needs to be activated in only two devices on the Modbus RTU network see Example 1 and Example 2 Example 1 Example 2 Fig 5 Network bus resistor jumper RX ТX NBT NBT NBT Slave 2 Master Slave n Slave 1 Slave 2 Slave 1 RX ТX NBT NBT Master Slave n ATTENTION On a Modbus RTU network two bus terminators NBTs n...

Страница 10: ...ck start disabled Input voltage mode 0 10 VDC Min setting of the Min speed trimmer Max setting of the Max speed trimmer Min setting of the Off level trimmer 3 Set the analog input signal to the maximum value of 10 VDC or 20 mA 4 The connected motor will run at maximum speed or minimum speed depending on the analog input mode ascending descending 5 If OFF level is enabled and descending analog inpu...

Страница 11: ... switched on When Timer mode is selected the controller receives a pulse control signal from the remote control switch When Logic mode is selected the controller receives a pulse control signal from the Ai input In both modes Timer mode and Logic mode the pulse width is to be more than 30 ms otherwise the signal is filtered FRONT PANEL LED INDICATION When the green LED on the front cover Fig 10 gi...

Страница 12: ...ximum output voltage 75 100 75 100 75 Us 100 Us 6 Minimum output voltage unsigned int Minimum output voltage 30 70 30 70 30 Us 70 Us 7 Enable off level unsigned int Enables off level 0 1 0 1 Disabled Enabled 8 Off level value unsigned int Off level value depending on the selected analog input type and ascending descending analog input mode 0 40 60 100 Ascending mode 0 400 0 200 Voltage 0 VDC 4 0 V...

Страница 13: ...s settable Active only if holding register 7 is set to 1 0 1 0 0 1 Disabled Enabled 16 Off level value unsigned int Off level value Depends on the selected analog input type and ascending descending analog input mode Always settable Active only if holding register 7 is set to 1 0 40 60 100 0 Ascending mode 0 40 0 40 Voltage 0 VDC 4 0 VDC Current 0 mA 8 0 mA Descending mode 100 60 100 60 Voltage 10...

Страница 14: ... 4 according to the selected operating mode The values are 0 for descending mode or 1 for ascending mode Input register 5 30005 shows the value of the maximum output voltage This input register is defined by holding register 13 or the hardware setting of the Max trimmer Fig 6 according to the selected operating mode The register values vary in range of 75 100 75 100 Us VAC Input register 6 30006 s...

Страница 15: ... Single Register with address 1 and write the new address value 2 Connect only your unit to a master controller or PC application and send the command Write Single Register to address 0 Modbus broadcast address and write a new address value The next two registers 2 and 3 contain Modbus settings Changing these registers you change the communication settings The default Modbus settings are 19200 E 1...

Страница 16: ...ly in timer mode and or logic mode The default value is 60 60 seconds The register values can vary from 0 to 200 0 200 seconds This setting is accessible only in Modbus mode The working time is equal to the sum of the kick start soft start duration and the time value of the operation timer When a working time expires only a remote control input or analog input can restart the unit The next holding...