P/N 1580281 

SEC3120 Digital Transmitter 

Sensor Electronics Corporation 

Rev 10, 20150707 

 

 
ENTER  on  ‘SAVE  CHANGES’  to  retain 
the new settings 

or ‘ABORT CHANGES’ 

to discard them. 

 
 
Move cursor down to show next alarm sub menu. 
 
 
 
ENTER on ‘MUTE ON WARN’ to change how the 
transmitter  acts  when  it  goes  into  a  warning. 
Using up or down the value can be changed from 
YES to NO. 

 

ENTER  on  ‘PREVIOUS  MENU’  to  return  to  the 
MAIN MENU 
 

 

8.6.

 

Network ID (Sensor / Display Network Identities) 

The  SEC3120  may  be  addressed  on  Modbus  at  a  specific  network  ID,  as  any  other  Modbus  compliant 
device does. However, it may also be accessed using two network device IDs, one for each sensor if it is 
so configured. When communicating with the SEC3500 versions less than 4.0.0, one device ID must be 
assigned sequentially for each sensor attached, allowing the SEC3500 to depict two separate sensors and 
treat them as individual SEC3100 transmitters. In version 4.0.0  and higher, the SEC3500 will support a 
single network ID for all sensors attached to the SEC3500 and display all relevant information as a single 
transmitter, a dual-sensor hub. Likewise, Modbus compliant Master devices may choose to communicate 
with  the  SEC3120  Transmitter  using  a  single  network  ID.  Switching  between  these  modes  can  be  very 
tricky when legacy (versions older than 4.0.0) SEC3500 HMI panels are the master. 
 

The SEC3120 Modbus Network ID Modes are: 

 

Legacy  3100  Mode 

  This is  not  a  mode  that  is  selected  directly  by  the user interface menus, 

however this mode can be set by the SEC3500 HMI for communication with older legacy SEC3500 
HMI Panels. It is not a mode that should be intentionally set for use with Modbus Master’s other 
than legacy SEC3500 HMI Panels. In this mode, network IDs are force to be assigned sequentially 
for two sensors attached to each SEC3120.  Sequential IDs can be assigned in UNIQUE mode if 
desired, but in Legacy 3100 mode sequential IDs are forced. 

 

Unique Mode 

 This mode can be used for any Modbus Master or SEC3500 HMI version. In this 

mode, Modbus Network IDs can be assigned to both sensors of any valid value, and do not have 
to be sequential. When communicating with an SEC3500 of a version less than 4.0.0 however, the 
network IDs should be set sequentially in this mode. 

 

Single  Mode 

– 

This  mode  can  be  used  for any  Modbus  Master  or  for  an  SEC3500  HMI  Panel 

version 4.0.0 or higher. In this mode, only one Modbus Network ID is assigned to the SEC3120 
Transmitter and all sensor information for all sensors attached are accessible. 

 

Change Network ID Mode 

From the Initial/Top menu screen, move the cursor down 
to MAIN MENU and select ENTER. 
 
 
 

Move  the  cursor  down  to  the  NETWORK  Menu 
and select ENTER. 
 

 

  

MUTE ON WARN  YES/NO 

PREVIOUS MENU 

 

 

*  SAVE CHANGES 
   ABORT CHANGES 
 

  

FOR SENSOR:  ONE / TWO 

LOW 

 

MID 

 

HIGH 

*  

MUTE ON WARN  YES/NO 

 

PREVIOUS MENU 

 

 

        EJECT MEMORY CARD 
        ABORT WARMUP 
        INFO 
*      MAIN MENU 

 

CALIBRATION 

 

ALARM 

 

RELAY 

NETWORK 

Содержание SEC3120

Страница 1: ...Electronics Corporation Rev 10 20150707 SEC3120 Transmitter Dual Sensor Display Instruction and Operation Manual P N 1580281 Rev 10 20150707 Sensor Electronics Corporation 12730 Creek View Ave Savage...

Страница 2: ...FACTORY AND FOUND DEFECTIVE WITHIN THE WARRANTY WOULD BE REPAIRED OR REPLACED AT SEC S OPTION SEC WILL RETURN REPAIRED OR REPLACED EQUIPMENT PRE PAID LOWEST COST FREIGHT THIS WARRANTY DOES NOT APPLY...

Страница 3: ...ring Operation 12 8 1 Required Sequence for Changes to Configuration 12 8 2 Date and Time 12 8 3 Relay Settings Latching Delay and Control Logic 14 8 4 Sensor Mode Single Unique or Identical 17 8 5 Al...

Страница 4: ...as a Modbus RTU Slave Optional alarm and fault relays Non intrusive programming Non intrusive calibration Removable non volatile time stamped data logging Optional IS barrier Digital communication li...

Страница 5: ...ing Voltage 24 VDC Nominal Range 18 to 32 Vdc measured at the detector head Current Draw without sensors Average 250 mA Peak 500 mA Input Sensor Digital 0 5 V Sensor Electronics Corp SEC Proprietary S...

Страница 6: ...r it could also rise How rapidly will the gas diffuse into the ambient air Select a location for the sensor that is close to the anticipated source of a gas leak Wind or ventilation characteristics of...

Страница 7: ...trip wires to 3 8 inch Solder tin the exposed wire to increase durability Protective bonding is provided by an internal screw location for connection of a grounding wire Installation of this wire shou...

Страница 8: ...ARM N O 6 MID ALARM N C 5 MID ALARM COMMON 4 MID ALARM N O 3 LOW ALARM N C 2 LOW ALARM COMMON 1 LOW ALARM N O NC NORMALLY CLOSED NO NORMALLY OPEN TB 2 SENSOR 1 1 WHITE DATA CAL 2 BLUE OR GREEN 4 20 mA...

Страница 9: ...ormation display When sensor one information is displayed the alarm state LEDs indicate the alarm status for sensor one When sensor two s information is displayed the alarm state LEDs indicate the ala...

Страница 10: ...ged Inital Power Up Screen Sequence of the SEC3120 BRWN Brown Out Reset or SOFT RESET shown on bottom line for a software reset 005 Counts down to 000 second startup delay VER refers to the Firmware v...

Страница 11: ...ft of the screen The right side of the screen will display the ID Range Gas Type and Status The bottom line will scroll through the MC memory card status Date Time and if a sensor has a warning code w...

Страница 12: ...line turn Modbus mode to OFF 2 Delete this unit from the SEC3500 HMI or equivalent device if it was previously online or discovered Consult the SEC3500 manual for details 3 Change the Sensor Role to e...

Страница 13: ...edit the TIME field Use the UP and DOWN switches to choose the hour minutes or seconds to edit and select ENTER Use the UP and DOWN switches to set the value and select ENTER edit hour is shown in fi...

Страница 14: ...has cleared This causes the user to acknowledge the activation in order to clear any alarms Delay Delay can also be applied to the activation ON or deactivation OFF of the individual relays The delay...

Страница 15: ...condition or an SEC3120 unit fault condition Alarm and fault states of sensor two will NOT cause any relays to be engaged This relay mode is commonly used in conjunction with the Single Sensor Role a...

Страница 16: ...UP and DOWN switches to choose the desired logic option SENSOR ONE relays respond to sensor one alarm states only SENSOR TWO relays respond to sensor two alarm states only AND relays will activate on...

Страница 17: ...be issued and the fault relay will be engaged This mode is commonly used for redundancy such as two oxygen sensors used to ensure that the actual oxygen levels are truly at the same appropriate value...

Страница 18: ...screen for each field being changed Scroll down to bring up the next page of the Modbus Settings Menu Select ENTER on PREVIOUS MENU to return the screen to the Network Menu Scroll down to PREVIOUS ME...

Страница 19: ...shold has been met Turning the setting YES will keep the transmitter relays from activating and the LEDs from changing color when the unit is in a warning Alarm Menu Selected from the Main Menu Move t...

Страница 20: ...0 HMI panels are the master The SEC3120 Modbus Network ID Modes are Legacy 3100 Mode This is not a mode that is selected directly by the user interface menus however this mode can be set by the SEC350...

Страница 21: ...he SAVE CHANGES screen for each field being changed Scroll down to the 2nd page of the Modbus Settings Menu Select ENTER on PREVIOUS MENU to return the screen to the Network Menu Scroll down to and se...

Страница 22: ...the cursor to ID and select ENTER The IDs of the sensors may be set in the range 1 254 however they cannot be set to the same value Note Be sure to assign the sensor an ID number not shared by any oth...

Страница 23: ...tible with Modicon Modbus Specification PI MBUS 300 Rev J SEC3500 HMI Panels communicate using SEC standard RS485 or default configuration parameters as shown below since they provide the most reliabl...

Страница 24: ...dbus Settings Menu Page 2 Select ENTER on PREVIOUS MENU to exit the Modbus Settings Menu and return to the Network Settings Menu Screen Scroll down to and select ENTER on PREVIOUS MENU to return to th...

Страница 25: ...by moving the cursor to COMM ALTERNATE and selecting ENTER The alternate values are 9600 baud 8 data bits no parity and 1 stop bit The following display is shown This is just an informational box to...

Страница 26: ...of 1200 2400 4800 9600 19200 and 38400 Return to the 485 bus menu and save the changes by moving the cursor to the next screen and select ENTER Scroll down to PREVIOUS MENU and select ENTER to return...

Страница 27: ...lowing screens will be displayed Once complete the SEC3120 will return to the calibration menu The sensor has been successfully zeroed if no faults are indicated ZERO CAL SENSOR ONE 1 WAIT FOR START E...

Страница 28: ...the sensor or ABORT CHANGES to return to the previous screen The Following screens are displayed To Span calibrate the sensor move the cursor to SPAN and select ENTER Apply clean air N2 for an oxygen...

Страница 29: ...erator to command the SEC3120 to reboot toggle the LEDs typically Locator Mode with alternating flashing red green alarm fault lights and toggle the individual relays on and off to verify operation Re...

Страница 30: ...lscale In the self test mode the SEC3120 outputs are fully functional The SEC3120 will display the rising gas level the 4 20 mA output will increase to 20 mA the relays will activate and the RS485 inf...

Страница 31: ...R INFO displays the information for both of the sensors 003 counts down to 000 seconds DDD Device ID for sensor 1 EEE Device ID for sensor 2 TYP Sensor type 00 is a SEC3000 32 is SEC Millennium FW Ver...

Страница 32: ...rd to start storage over The SEC3120 will continue to log data to the flash card until it reaches 100 full At that time the status will change to MC FULLNOW indicating that there is no more room to st...

Страница 33: ...vent 03 Alarm High Level Triggered Event 04 Alarm Mid Level Triggered Event 05 Alarm Low Level Triggered Event 06 Change in Gas Level 5 of Sensor Range Event 07 Sensor Fault Missing Not Identical Dete...

Страница 34: ...31 yyyy Year 2000 2099 HH Hours 24 hour format 00 23 MM Minutes 00 59 SS Seconds 00 59 S1 Literal text for sensor one S1 S2 Literal text for sensor two S2 BB Literal text for both sensors BB ID Replac...

Страница 35: ...command and control etc This requires the SEC3120 to have sequential Modbus network IDs one assigned for each physical sensor attached to it If the SEC3500 HMI or its operator attempts to Discover an...

Страница 36: ...Transmitters replacement of SEC3100 Single Digital Transmitters with SEC3120 Dual Digital Transmitters and SEC3120 Digital Transmitters that may initially start out as Single Sensor Role configuratio...

Страница 37: ...Operator Manual Page 37 of 40 P N 1580281 SEC3120 Digital Transmitter Sensor Electronics Corporation Rev 10 20150707 APPENDIX A Supplement Certification Listed Data...

Страница 38: ...Operator Manual Page 38 of 40 P N 1580281 SEC3120 Digital Transmitter Sensor Electronics Corporation Rev 10 20150707...

Страница 39: ...Operator Manual Page 39 of 40 P N 1580281 SEC3120 Digital Transmitter Sensor Electronics Corporation Rev 10 20150707...

Страница 40: ...Operator Manual Page 40 of 40 P N 1580281 SEC3120 Digital Transmitter Sensor Electronics Corporation Rev 10 20150707...

Отзывы: