Sensor Electronics SEC3120 Скачать руководство пользователя страница 15

 
Operator Manual 

Page 

15

 of 

40

 

P/N 1580281 

SEC3120 Digital Transmitter 

Sensor Electronics Corporation 

Rev 10, 20150707 

 

 
 
 
 
 
 

Within the LOW, MID, HIGH and FAULT 
pages the user can set: 

-

  the relay latching style ** 

-

  the on delay in seconds (0-255)  

-

  the off delay in seconds (0-255)  

-

  the  energized  state  (NO  =  relay  not 

energized until activated {resembles 
normally open contact action}, YES = 
relay  energized  until  activated  { 
resembles  normally  closed  contact 
action }) 

** Latching Mode:  
- Normal =  

relays do not latch. 

- Latching =  

relays remain activated until forced reset. 

- Audible =  

relays can be silenced by user (forced off). 

 

 
ENTER on ‘PREVIOUS MENU’ to return 
to  the  Relay  Menu  and  choose  to 
permanently save or abort the changes. 
 
ENTER  on  ‘SAVE  CHANGES’  to  retain 
new  settings  or  ‘ABORT  CHANGES’  to 
cancel  them.  Either  choice  will return  to 
the Relay Menu. 

 

Logic: 

A key feature in the SEC3120 is the Sensor Role because only one set of relays is provided to service both 
attached sensors. Therefore, in determining the sensor mode, a decision regarding how the relays will be 
used must be considered and a decision concerning what relay mode is used must be made. Below is a 
list of possible relay modes: 

 

Sensor One 

 All alarm relays are  determined exclusively from the alarm status of sensor one. 

The fault relay is engaged by either a sensor one fault condition or an SEC3120 unit fault condition.  
Alarm and fault states of sensor two will NOT cause any relays to be engaged. This relay mode is 
commonly used in conjunction with the Single Sensor Role, and must be set PRIOR to setting the 
Single Sensor Role. 

 

Sensor Two 

 All alarm relays are controlled exclusively from the alarm status of sensor two. The 

fault relay is engaged by either a sensor one fault condition or an SEC3120 unit fault condition.  
Alarm and fault states of sensor one will NOT cause any relays to be engaged.  CAUTION:  Sensor 
Two relay logic must not be used when the sensor mode is SINGLE. 

 

Logical AND 

 All alarm relays are controlled by the logical AND condition of BOTH sensors one 

and  two  states.  This  means  that  for  a  low-alarm  relay  to  be  engaged,  BOTH  sensors  must  be 
reporting low relay alarm states (gas levels above the low alarm threshold). For a mid-alarm relay 
to be engaged, BOTH sensors must be reporting at least mid-relay alarm states. For a high-alarm 
relay to be engaged, BOTH sensors must be reporting high alarm states. This relay mode is best 
utilized in the Identical Sensor Role, and should be set PRIOR to setting the Identical Sensor Role. 
The fault relay will engage if EITHER sensor is reporting a fault condition, or if the SEC3120 unit is 
in a fault state.  CAUTION:  AND or SENSOR TWO relay logic must not be used when the sensor 
mode is SINGLE. 

 

LOGIC MODE 

 

PREVIOUS MENU 

 

 

LATCH 

       

‘NORMAL’ 

 

ON   DLY 

XXX 

 

OFF DLY 

XXX 

        ENERGIZED      YES / NO 

*      PREVIOUS MENU 

         

 

 

*  SAVE CHANGES 
   ABORT CHANGES 
 

Содержание SEC3120

Страница 1: ...Electronics Corporation Rev 10 20150707 SEC3120 Transmitter Dual Sensor Display Instruction and Operation Manual P N 1580281 Rev 10 20150707 Sensor Electronics Corporation 12730 Creek View Ave Savage...

Страница 2: ...FACTORY AND FOUND DEFECTIVE WITHIN THE WARRANTY WOULD BE REPAIRED OR REPLACED AT SEC S OPTION SEC WILL RETURN REPAIRED OR REPLACED EQUIPMENT PRE PAID LOWEST COST FREIGHT THIS WARRANTY DOES NOT APPLY...

Страница 3: ...ring Operation 12 8 1 Required Sequence for Changes to Configuration 12 8 2 Date and Time 12 8 3 Relay Settings Latching Delay and Control Logic 14 8 4 Sensor Mode Single Unique or Identical 17 8 5 Al...

Страница 4: ...as a Modbus RTU Slave Optional alarm and fault relays Non intrusive programming Non intrusive calibration Removable non volatile time stamped data logging Optional IS barrier Digital communication li...

Страница 5: ...ing Voltage 24 VDC Nominal Range 18 to 32 Vdc measured at the detector head Current Draw without sensors Average 250 mA Peak 500 mA Input Sensor Digital 0 5 V Sensor Electronics Corp SEC Proprietary S...

Страница 6: ...r it could also rise How rapidly will the gas diffuse into the ambient air Select a location for the sensor that is close to the anticipated source of a gas leak Wind or ventilation characteristics of...

Страница 7: ...trip wires to 3 8 inch Solder tin the exposed wire to increase durability Protective bonding is provided by an internal screw location for connection of a grounding wire Installation of this wire shou...

Страница 8: ...ARM N O 6 MID ALARM N C 5 MID ALARM COMMON 4 MID ALARM N O 3 LOW ALARM N C 2 LOW ALARM COMMON 1 LOW ALARM N O NC NORMALLY CLOSED NO NORMALLY OPEN TB 2 SENSOR 1 1 WHITE DATA CAL 2 BLUE OR GREEN 4 20 mA...

Страница 9: ...ormation display When sensor one information is displayed the alarm state LEDs indicate the alarm status for sensor one When sensor two s information is displayed the alarm state LEDs indicate the ala...

Страница 10: ...ged Inital Power Up Screen Sequence of the SEC3120 BRWN Brown Out Reset or SOFT RESET shown on bottom line for a software reset 005 Counts down to 000 second startup delay VER refers to the Firmware v...

Страница 11: ...ft of the screen The right side of the screen will display the ID Range Gas Type and Status The bottom line will scroll through the MC memory card status Date Time and if a sensor has a warning code w...

Страница 12: ...line turn Modbus mode to OFF 2 Delete this unit from the SEC3500 HMI or equivalent device if it was previously online or discovered Consult the SEC3500 manual for details 3 Change the Sensor Role to e...

Страница 13: ...edit the TIME field Use the UP and DOWN switches to choose the hour minutes or seconds to edit and select ENTER Use the UP and DOWN switches to set the value and select ENTER edit hour is shown in fi...

Страница 14: ...has cleared This causes the user to acknowledge the activation in order to clear any alarms Delay Delay can also be applied to the activation ON or deactivation OFF of the individual relays The delay...

Страница 15: ...condition or an SEC3120 unit fault condition Alarm and fault states of sensor two will NOT cause any relays to be engaged This relay mode is commonly used in conjunction with the Single Sensor Role a...

Страница 16: ...UP and DOWN switches to choose the desired logic option SENSOR ONE relays respond to sensor one alarm states only SENSOR TWO relays respond to sensor two alarm states only AND relays will activate on...

Страница 17: ...be issued and the fault relay will be engaged This mode is commonly used for redundancy such as two oxygen sensors used to ensure that the actual oxygen levels are truly at the same appropriate value...

Страница 18: ...screen for each field being changed Scroll down to bring up the next page of the Modbus Settings Menu Select ENTER on PREVIOUS MENU to return the screen to the Network Menu Scroll down to PREVIOUS ME...

Страница 19: ...shold has been met Turning the setting YES will keep the transmitter relays from activating and the LEDs from changing color when the unit is in a warning Alarm Menu Selected from the Main Menu Move t...

Страница 20: ...0 HMI panels are the master The SEC3120 Modbus Network ID Modes are Legacy 3100 Mode This is not a mode that is selected directly by the user interface menus however this mode can be set by the SEC350...

Страница 21: ...he SAVE CHANGES screen for each field being changed Scroll down to the 2nd page of the Modbus Settings Menu Select ENTER on PREVIOUS MENU to return the screen to the Network Menu Scroll down to and se...

Страница 22: ...the cursor to ID and select ENTER The IDs of the sensors may be set in the range 1 254 however they cannot be set to the same value Note Be sure to assign the sensor an ID number not shared by any oth...

Страница 23: ...tible with Modicon Modbus Specification PI MBUS 300 Rev J SEC3500 HMI Panels communicate using SEC standard RS485 or default configuration parameters as shown below since they provide the most reliabl...

Страница 24: ...dbus Settings Menu Page 2 Select ENTER on PREVIOUS MENU to exit the Modbus Settings Menu and return to the Network Settings Menu Screen Scroll down to and select ENTER on PREVIOUS MENU to return to th...

Страница 25: ...by moving the cursor to COMM ALTERNATE and selecting ENTER The alternate values are 9600 baud 8 data bits no parity and 1 stop bit The following display is shown This is just an informational box to...

Страница 26: ...of 1200 2400 4800 9600 19200 and 38400 Return to the 485 bus menu and save the changes by moving the cursor to the next screen and select ENTER Scroll down to PREVIOUS MENU and select ENTER to return...

Страница 27: ...lowing screens will be displayed Once complete the SEC3120 will return to the calibration menu The sensor has been successfully zeroed if no faults are indicated ZERO CAL SENSOR ONE 1 WAIT FOR START E...

Страница 28: ...the sensor or ABORT CHANGES to return to the previous screen The Following screens are displayed To Span calibrate the sensor move the cursor to SPAN and select ENTER Apply clean air N2 for an oxygen...

Страница 29: ...erator to command the SEC3120 to reboot toggle the LEDs typically Locator Mode with alternating flashing red green alarm fault lights and toggle the individual relays on and off to verify operation Re...

Страница 30: ...lscale In the self test mode the SEC3120 outputs are fully functional The SEC3120 will display the rising gas level the 4 20 mA output will increase to 20 mA the relays will activate and the RS485 inf...

Страница 31: ...R INFO displays the information for both of the sensors 003 counts down to 000 seconds DDD Device ID for sensor 1 EEE Device ID for sensor 2 TYP Sensor type 00 is a SEC3000 32 is SEC Millennium FW Ver...

Страница 32: ...rd to start storage over The SEC3120 will continue to log data to the flash card until it reaches 100 full At that time the status will change to MC FULLNOW indicating that there is no more room to st...

Страница 33: ...vent 03 Alarm High Level Triggered Event 04 Alarm Mid Level Triggered Event 05 Alarm Low Level Triggered Event 06 Change in Gas Level 5 of Sensor Range Event 07 Sensor Fault Missing Not Identical Dete...

Страница 34: ...31 yyyy Year 2000 2099 HH Hours 24 hour format 00 23 MM Minutes 00 59 SS Seconds 00 59 S1 Literal text for sensor one S1 S2 Literal text for sensor two S2 BB Literal text for both sensors BB ID Replac...

Страница 35: ...command and control etc This requires the SEC3120 to have sequential Modbus network IDs one assigned for each physical sensor attached to it If the SEC3500 HMI or its operator attempts to Discover an...

Страница 36: ...Transmitters replacement of SEC3100 Single Digital Transmitters with SEC3120 Dual Digital Transmitters and SEC3120 Digital Transmitters that may initially start out as Single Sensor Role configuratio...

Страница 37: ...Operator Manual Page 37 of 40 P N 1580281 SEC3120 Digital Transmitter Sensor Electronics Corporation Rev 10 20150707 APPENDIX A Supplement Certification Listed Data...

Страница 38: ...Operator Manual Page 38 of 40 P N 1580281 SEC3120 Digital Transmitter Sensor Electronics Corporation Rev 10 20150707...

Страница 39: ...Operator Manual Page 39 of 40 P N 1580281 SEC3120 Digital Transmitter Sensor Electronics Corporation Rev 10 20150707...

Страница 40: ...Operator Manual Page 40 of 40 P N 1580281 SEC3120 Digital Transmitter Sensor Electronics Corporation Rev 10 20150707...

Отзывы: