Operator Manual 

Page 

19

 of 

40

 

P/N 1580281 

SEC3120 Digital Transmitter 

Sensor Electronics Corporation 

Rev 10, 20150707 

 

 
Scroll down to and select ENTER on EXIT to return the 
screen to the Normal Operating Display. 
 
 

8.5.

 

Alarm Settings – Threshold Values and Active Mode 

In the ‘ALARM’ menu the user can set the thresholds for the Low, Mid and High alarms for both sensors. 
The default values for these settings are Low = 20% full scale, Mid = 40% of full scale and High = 60% of 
full scale.  

The ‘Active Mode’ of each alarm set point can also be changed in this menu.  An Active High 

setting will trigger the alarm when the gas concentration is rising and crosses the threshold set point.  An 
Active Low setting will trigger the alarm when the gas concentration is falling and crosses the threshold 
set point. 

The user can also change the “MUTE ON WARN” setting. This setting determines how the 

transmitter acts when the attached sensor goes into a warning (only applies to SEC5000 Evolution and 
SEC3300)

. The default for this setting is “NO” meaning that if the unit goes into a warning but still senses 

gas, the transmitter relays will activate (LEDs will also change) and communicate to the SEC3500 when 
an alarm threshold has been met. Turning the setting 

“YES” will keep the transmitter relays from 

activating and the LEDs from changing color when the unit is in a warning. 
 

Alarm Menu (Selected from the Main Menu) 

Move the cursor to ALARM and select ENTER to open the 
alarm menu. 
 

 

ENTER  on  ‘FOR  SENSOR’  ‘ONE/TWO’  to 
choose  which  sensor  to  perform  alarm 
configuration operations. 

DOWN switch to select sensor one 
Up switch to select sensor two 
 

Move the cursor to the alarm to set (LOW, MID or 
HIGH) and select ENTER. 
 

 
To  set  the  alarm  set-point  move  the 
cursor  to  THRESHOLD  and  select 
ENTER. 
 
 

Using  the  UP  and  DOWN 
switches  set  the  desired  value 
then select ENTER. 
 

Selecting  ACTIVE  MODE  will  allow  the 
operator  to  change  the  operation  of  the 
alarm  activation  operation  from  Active 
HIGH  to  Active  LOW.  Once  the  correct 
operation is selected select ENTER. 
 

-

 HIGH activates the alarm on a rising gas level. 

-

 LOW actives the  alarm  when the gas level falls below the 

alarm set point. 

 
ENTER on ‘PREVIOUS MENU’ to return 
to the Alarm Menu and choose to save or 
abort the changes. 
 

*  THRESHOLD 

‘value’ 

  ACTIVE MODE  HIGH/LOW 
  PREVIOUS MENU 
 

*  THRESHOLD 

‘value’ 

  * 

  ACTIVE MODE  HIGH/LOW 
  PREVIOUS MENU 
 

  THRESHOLD 

‘value’ 

*  ACTIVE MODE  HIGH/LOW* 
  PREVIOUS MENU 
 

 

CALIBRATION 

ALARM 

 

RELAY 

 

NETWORK 

FOR SENSOR:  ONE / TWO 

  

LOW 

 

MID 

 

HIGH 

  

FOR SENSOR:  ONE / TWO 

LOW 

 

MID 

 

HIGH 

  THRESHOLD 

‘value’ 

   ACTIVE MODE  HIGH/LOW 
*  PREVIOUS MENU 
 

     SEC DIAGNOSTICS 
     RESET RELAYS 
    FORMAT FLASH CARD 
*   EXIT 

Содержание SEC3120

Страница 1: ...Electronics Corporation Rev 10 20150707 SEC3120 Transmitter Dual Sensor Display Instruction and Operation Manual P N 1580281 Rev 10 20150707 Sensor Electronics Corporation 12730 Creek View Ave Savage...

Страница 2: ...FACTORY AND FOUND DEFECTIVE WITHIN THE WARRANTY WOULD BE REPAIRED OR REPLACED AT SEC S OPTION SEC WILL RETURN REPAIRED OR REPLACED EQUIPMENT PRE PAID LOWEST COST FREIGHT THIS WARRANTY DOES NOT APPLY...

Страница 3: ...ring Operation 12 8 1 Required Sequence for Changes to Configuration 12 8 2 Date and Time 12 8 3 Relay Settings Latching Delay and Control Logic 14 8 4 Sensor Mode Single Unique or Identical 17 8 5 Al...

Страница 4: ...as a Modbus RTU Slave Optional alarm and fault relays Non intrusive programming Non intrusive calibration Removable non volatile time stamped data logging Optional IS barrier Digital communication li...

Страница 5: ...ing Voltage 24 VDC Nominal Range 18 to 32 Vdc measured at the detector head Current Draw without sensors Average 250 mA Peak 500 mA Input Sensor Digital 0 5 V Sensor Electronics Corp SEC Proprietary S...

Страница 6: ...r it could also rise How rapidly will the gas diffuse into the ambient air Select a location for the sensor that is close to the anticipated source of a gas leak Wind or ventilation characteristics of...

Страница 7: ...trip wires to 3 8 inch Solder tin the exposed wire to increase durability Protective bonding is provided by an internal screw location for connection of a grounding wire Installation of this wire shou...

Страница 8: ...ARM N O 6 MID ALARM N C 5 MID ALARM COMMON 4 MID ALARM N O 3 LOW ALARM N C 2 LOW ALARM COMMON 1 LOW ALARM N O NC NORMALLY CLOSED NO NORMALLY OPEN TB 2 SENSOR 1 1 WHITE DATA CAL 2 BLUE OR GREEN 4 20 mA...

Страница 9: ...ormation display When sensor one information is displayed the alarm state LEDs indicate the alarm status for sensor one When sensor two s information is displayed the alarm state LEDs indicate the ala...

Страница 10: ...ged Inital Power Up Screen Sequence of the SEC3120 BRWN Brown Out Reset or SOFT RESET shown on bottom line for a software reset 005 Counts down to 000 second startup delay VER refers to the Firmware v...

Страница 11: ...ft of the screen The right side of the screen will display the ID Range Gas Type and Status The bottom line will scroll through the MC memory card status Date Time and if a sensor has a warning code w...

Страница 12: ...line turn Modbus mode to OFF 2 Delete this unit from the SEC3500 HMI or equivalent device if it was previously online or discovered Consult the SEC3500 manual for details 3 Change the Sensor Role to e...

Страница 13: ...edit the TIME field Use the UP and DOWN switches to choose the hour minutes or seconds to edit and select ENTER Use the UP and DOWN switches to set the value and select ENTER edit hour is shown in fi...

Страница 14: ...has cleared This causes the user to acknowledge the activation in order to clear any alarms Delay Delay can also be applied to the activation ON or deactivation OFF of the individual relays The delay...

Страница 15: ...condition or an SEC3120 unit fault condition Alarm and fault states of sensor two will NOT cause any relays to be engaged This relay mode is commonly used in conjunction with the Single Sensor Role a...

Страница 16: ...UP and DOWN switches to choose the desired logic option SENSOR ONE relays respond to sensor one alarm states only SENSOR TWO relays respond to sensor two alarm states only AND relays will activate on...

Страница 17: ...be issued and the fault relay will be engaged This mode is commonly used for redundancy such as two oxygen sensors used to ensure that the actual oxygen levels are truly at the same appropriate value...

Страница 18: ...screen for each field being changed Scroll down to bring up the next page of the Modbus Settings Menu Select ENTER on PREVIOUS MENU to return the screen to the Network Menu Scroll down to PREVIOUS ME...

Страница 19: ...shold has been met Turning the setting YES will keep the transmitter relays from activating and the LEDs from changing color when the unit is in a warning Alarm Menu Selected from the Main Menu Move t...

Страница 20: ...0 HMI panels are the master The SEC3120 Modbus Network ID Modes are Legacy 3100 Mode This is not a mode that is selected directly by the user interface menus however this mode can be set by the SEC350...

Страница 21: ...he SAVE CHANGES screen for each field being changed Scroll down to the 2nd page of the Modbus Settings Menu Select ENTER on PREVIOUS MENU to return the screen to the Network Menu Scroll down to and se...

Страница 22: ...the cursor to ID and select ENTER The IDs of the sensors may be set in the range 1 254 however they cannot be set to the same value Note Be sure to assign the sensor an ID number not shared by any oth...

Страница 23: ...tible with Modicon Modbus Specification PI MBUS 300 Rev J SEC3500 HMI Panels communicate using SEC standard RS485 or default configuration parameters as shown below since they provide the most reliabl...

Страница 24: ...dbus Settings Menu Page 2 Select ENTER on PREVIOUS MENU to exit the Modbus Settings Menu and return to the Network Settings Menu Screen Scroll down to and select ENTER on PREVIOUS MENU to return to th...

Страница 25: ...by moving the cursor to COMM ALTERNATE and selecting ENTER The alternate values are 9600 baud 8 data bits no parity and 1 stop bit The following display is shown This is just an informational box to...

Страница 26: ...of 1200 2400 4800 9600 19200 and 38400 Return to the 485 bus menu and save the changes by moving the cursor to the next screen and select ENTER Scroll down to PREVIOUS MENU and select ENTER to return...

Страница 27: ...lowing screens will be displayed Once complete the SEC3120 will return to the calibration menu The sensor has been successfully zeroed if no faults are indicated ZERO CAL SENSOR ONE 1 WAIT FOR START E...

Страница 28: ...the sensor or ABORT CHANGES to return to the previous screen The Following screens are displayed To Span calibrate the sensor move the cursor to SPAN and select ENTER Apply clean air N2 for an oxygen...

Страница 29: ...erator to command the SEC3120 to reboot toggle the LEDs typically Locator Mode with alternating flashing red green alarm fault lights and toggle the individual relays on and off to verify operation Re...

Страница 30: ...lscale In the self test mode the SEC3120 outputs are fully functional The SEC3120 will display the rising gas level the 4 20 mA output will increase to 20 mA the relays will activate and the RS485 inf...

Страница 31: ...R INFO displays the information for both of the sensors 003 counts down to 000 seconds DDD Device ID for sensor 1 EEE Device ID for sensor 2 TYP Sensor type 00 is a SEC3000 32 is SEC Millennium FW Ver...

Страница 32: ...rd to start storage over The SEC3120 will continue to log data to the flash card until it reaches 100 full At that time the status will change to MC FULLNOW indicating that there is no more room to st...

Страница 33: ...vent 03 Alarm High Level Triggered Event 04 Alarm Mid Level Triggered Event 05 Alarm Low Level Triggered Event 06 Change in Gas Level 5 of Sensor Range Event 07 Sensor Fault Missing Not Identical Dete...

Страница 34: ...31 yyyy Year 2000 2099 HH Hours 24 hour format 00 23 MM Minutes 00 59 SS Seconds 00 59 S1 Literal text for sensor one S1 S2 Literal text for sensor two S2 BB Literal text for both sensors BB ID Replac...

Страница 35: ...command and control etc This requires the SEC3120 to have sequential Modbus network IDs one assigned for each physical sensor attached to it If the SEC3500 HMI or its operator attempts to Discover an...

Страница 36: ...Transmitters replacement of SEC3100 Single Digital Transmitters with SEC3120 Dual Digital Transmitters and SEC3120 Digital Transmitters that may initially start out as Single Sensor Role configuratio...

Страница 37: ...Operator Manual Page 37 of 40 P N 1580281 SEC3120 Digital Transmitter Sensor Electronics Corporation Rev 10 20150707 APPENDIX A Supplement Certification Listed Data...

Страница 38: ...Operator Manual Page 38 of 40 P N 1580281 SEC3120 Digital Transmitter Sensor Electronics Corporation Rev 10 20150707...

Страница 39: ...Operator Manual Page 39 of 40 P N 1580281 SEC3120 Digital Transmitter Sensor Electronics Corporation Rev 10 20150707...

Страница 40: ...Operator Manual Page 40 of 40 P N 1580281 SEC3120 Digital Transmitter Sensor Electronics Corporation Rev 10 20150707...

Отзывы: