When  installing,  make  sure  power  is  off  when  connecting  the  sensor,  field,  and  relay  wiring  to  the 
appropriate terminal blocks. DO NOT turn the power back on until the 3100 is secured to the housing using 
all four hex head screws. 
 

 

What  are  the  characteristics of  the gas that  is  to  be detected?   Is  it  lighter  or  heavier  than  air?   If  it  is 
lighter than air the sensor should be placed above the potential gas leak.  Place the sensor close to the 
floor for gases that are heavier than air.  Note that air currents can cause a gas that is heavier than air to 
rise.    In addition,  if  the  temperature  of  the gas  is  hotter  than  ambient  air  or mixed  with  gases  that are 
lighter than air, it could also rise. 

 

 

How rapidly will the gas diffuse into the ambient air?  Select a location for the sensor that is close to the 
anticipated source of a gas leak. 

 

 

Wind or ventilation characteristics of the immediate area must also be considered.  Movement of air may 
cause gas to accumulate more heavily in one area than in another. The detector should be placed in the 
areas  where  the  most  concentrated  accumulation  of  gas  is  anticipated.  For  outdoor  applications  with 
strong wind conditions, it may require the sensors to be mounted closer together and on the  downwind 
side, to the anticipated area of a gas leak.  Also take into consideration for indoor applications, the fact 
that many ventilation systems do not operate continuously. 

 

 

The sensor should be accessible for maintenance. 

 

 

Excessive heat or vibration can cause premature failure of any electronic device and should be avoided 
if possible.

  

 

 

Follow all national and local installation codes and practices

.

 

 
The  SEC  3100  has  three  (3

)  ¾”  NPT  threaded  connectors  for  mounting  and  wiring  the  sensor  and 

transmitter into a permanent installation. 
 
Field wiring connections are made on the backside of the SEC 3100 printed circuit board (PCB).  For wiring 
details refer to Figure 2 in the back of the manual. ¾ NPT threads must pass L1 thread/plug gauge.    
 

Mounting: 

Mount  the  SEC310

0  to  rigid  wall  (wood  based  or  stronger)  or  bulkhead  structures  using  1”  or  longer 

fasteners  with  a  minimum  3/16”  diameter.    Mounting  to  drywall  (wallboard,  plasterboard,  etc.)  or  similar 
material is not recommended. 
 

Wiring: 

Wire  insulation  for  relay  contacts  should  have  a  minimum  breakdown  voltage  of  twice  that  of  the  working 
voltage of the signal.  E.g. 110v lines should have a minimum insulation breakdown voltage of 220v, 240v 
signals should have a minimum insulation breakdown voltage of 480v. 
 
Wire insulation should be temperature rated for greater than or equal to 70°C. 

 
There are 2 earth screws on the SEC 3100. One is on the outside of the enclosure and the other is 
located  on  the  inside  of  the  enclosure.  Both  are  marked  with  earth  ground  symbols  and  green 
screws. Installation of this wire should include the use of a locking feature (i.e. locking washer). 

 

Power wire sizing: 
0 to 500 feet, recommended wire gauge size 16 AWG 
501 to 1000 feet, recommended wire gauge size 14 AWG 
Shielded  cable  is  recommended.    Wiring  should  be  installed  in  medal  conduit  with  no  other  cabling  in  the 
same conduit. Use copper conductors only on all terminal blocks. 
 
Colder  applications  may  require  an  optional  LCD  heater  for  the  SEC  3100  to  make  sure  the  LCD  can  be 
always  visible.  This  is  a  closed  loop  heater  that  will  turn  on  when  the  temperature  drops  below 

Содержание SEC 3100

Страница 1: ...460105 REV A SEC 3100 Transmitter Instruction and Operation Manual Sensor Electronics Corporation 12730 Creek View Avenue Savage Minnesota 55378 USA 952 938 9486 Fax 952 938 9617 Web site www sensorel...

Страница 2: ...MENT FROM THE FACTORY ANY PARTS RETURNED FREIGHT PRE PAID TO THE FACTORY AND FOUND DEFECTIVE WITHIN THE WARRANTY WOULD BE REPAIRED OR REPLACED AT SEC S OPTION SEC WILL RETURN REPAIRED OR REPLACED EQUI...

Страница 3: ...History Table Add Page Numbers Many Changes for Approval Update Give Standard P N 1460105 and Revision A 3 All All All Table of Contents I SPECIFICATIONS II GENERAL DESCRIPTION III OPERATION Installat...

Страница 4: ...Fault Rated for 8 Amps 30 VDC or 250VAC Display LCD backlit Construction Epoxy coated aluminum Operating Temperature Rating CUS 40 to 60 C at 0 to 99 RH non condensing IECEx 40 to 70 C Operating Volt...

Страница 5: ...em 4 20 mA ouput RS 485 Interface Isolated Optional alarm and fault relays Non intrusive programming Non intrusive calibration Removable non volatile time stamped data logging Optional IS barrier Digi...

Страница 6: ...voided if possible Follow all national and local installation codes and practices The SEC 3100 has three 3 NPT threaded connectors for mounting and wiring the sensor and transmitter into a permanent i...

Страница 7: ...ARE ALIVE GARDER LE COUVERCLE BIEN FERME TANT QUE LES CIRCUITS SONT SOUS TENSION Warm up When power is applied to the SEC 3100 it enters a one 1 minute warm up mode The output current will be 0 8 mA...

Страница 8: ...1 Attempt Unit Span with no gas 2 Attempt Unit Zero with gas 8 NA NA Currently Not Used 9 0 0ma Unit Fault Hard Fault refer to gas sensor manual 10 1 0ma Optics Fault Clean sensor s windows 11 1 2ma Z...

Страница 9: ...ceplate shown above on the front side LCD side of PCB to the left of the LCD Gas Sensor Port 1 x SEC 3000 SEC Millenium Magnetic Switch 3 UP Arrow DOWN Arrow ENTER Field Wiring Port 2 x Power 4 20 mA...

Страница 10: ...tatus During Warm Up FAULT LED will be solid Blue and ALARM LED will be falshing Yellow Blue MC REMOVED indicates the MEMORY CARD MC in not installed in the SEC 3100 Other MC indications are OK FAULT...

Страница 11: ...3100 software version number Selecting Enter again will return the display to the main info menu Sensor Status Menu TYP Sensor type 0 0 is a SEC 3000 32 0 is SEC Millenium SN Sensor serial number VER...

Страница 12: ...blank the display up to low alarm setting Down Arrow Self Test Menu Generates a signal on the display RS485 4 20 mA Down Menu Date Time Menu Sets the date and time in the real time clock Down Arrow 4...

Страница 13: ...CAL VAL to verify the span gas calibration value matches the value of the span gas calibration on hand If not select Enter and the following screen will appear Using the Up and Down arrows will allow...

Страница 14: ...nter This will go the display If calibration span gas is still present the display will read Apply clean air to the sensor to reduce this reading The display will advance to the following This complet...

Страница 15: ...point Once the correct set point is displayed select Enter and the new value will be accepted Arrow Down Selecting Enter will allow the operator to change the operation of the relay operation from Non...

Страница 16: ...low the alarm set point Once the correct operation is selected use the Down arrow to advance to the next menu item Arrow Down Selecting Exit will advance to the next menu This menu will allow the oper...

Страница 17: ...Enter Select Enter Using the Up and Down arrows the operator can change the ON delay time for the relay to actuate after the alarm threshold has been exceeded The time is measured in seconds 0 255 Onc...

Страница 18: ...red Arrow Down Selecting Enter will allow the operator to change the operation of the relay coil from normally de energized ENERGIZED NO to normally energized ENERGIZED YES Once the correct operation...

Страница 19: ...ct Enter Use the Up and Down Arrows to change the ID number 0 255 Once the correct ID number is displayed select Enter Arrow Down to Online Using Enter the operator can toggle between Online YES and O...

Страница 20: ...t will make the sensor generate a 4 20 mA input into the SEC 3100 from 4 mA to 20 mA 0 fullscale In the self test mode the SEC 3100 outputs are fully functional The SEC 3100 will display the rising ga...

Страница 21: ...Time is HH MM SS Below is an example Enter from above display Arrow Up one number Enter Continue with the sequence until the correct date appears Then select Enter and the following will be displayed...

Страница 22: ...Part Number 1460105 REV A Select Enter Selecting Enter again will return the SEC 3100 to normal operation EXIT...

Страница 23: ...cept the new settings The display will be the following To adjust the full scale 20 mA current output arrow down and select ENTER Using the UP DOWN arrows will increase UP arrow or decrease DOWN arrow...

Страница 24: ...rt Number 1460105 REV A V FIGURES Figure 1 Overall Layout Figure 2 SEC 3100 Wiring Figure 3 SEC Sensor Separation Kit Figure 4 Mounting SEC 3100 and SEC Millenium Figure 5 Mounting SEC 3100 and SEC 30...

Страница 25: ...tch 3 Mounting holes 2 Fault LED Green OK Red Fault SENSOR ELECTRONICS CORPORATION 12730 Creek View Avenue Savage Minnesota 55378 USA T 952 938 9486 F 952 938 9617 sales sensorelectronic com FIGURE 1...

Страница 26: ...3100 WIRING TB 3 SENSOR WIRING TB 1 RELAY WIRING TB 2 POWER DATA HWY ANALOG OUTPUT TB 1 12 LOW ALARM N C 11 LOW ALARM COMMON 10 LOW ALARM N O 9 MID ALARM N C 8 MID ALARM COMMON 7 MID ALARM N O 6 HIGH...

Страница 27: ...Part Number 1460105 REV A SENSOR ELECTRONICS CORPORATION 12730 Creek View Avenue Savage Minnesota 55378 USA T 952 938 9486 F 952 938 9617 sales sensorelectronic com FIGURE 3 SEC SENSOR SEPARATION KIT...

Страница 28: ...Part Number 1460105 REV A FIGURE 4 SEC 3100 SEC Millenium Mounting...

Страница 29: ...Part Number 1460105 REV A FIGURE 5 SEC 3100 SEC 3000 Mounting...

Отзывы: