Part Number: 1460105
REV: A
Select Enter
Select Enter
Using the Up and Down arrows the operator can change the OFF delay time for the relay to turn OFF after
the reading has decreased below the alarm point threshold. The time is measured in seconds (0-255).
Once the correct time is displayed select Enter to accept the new value. Then Exit the menu and proceed
on to the next selection.
In this example the Low alarm relay will stay energized for 60 seconds after the alarm has cleared.
Arrow Down
Selecting Enter will allow the operator to change the operation of the relay coil from normally de-energized
(ENERGIZED NO) to normally energized (ENERGIZED YES). Once the correct operation is selected, use
the Down arrow to advance to the EXIT menu. Select Enter to go back to the Relay Menu
This menu will allow the operator to select another relay to program. Or select Exit and the next display will
be:
Arrow Down to Exit
Enter
Selecting Enter will return the SEC 3100 into normal operation.
ON DLY LOW
* OFF DLY 0
ENERGIZED
EXIT
ON DLY LOW
* OFF DLY 0 *
EXIT
ON DLY LOW
* OFF DLY 60
ENERGIZED
EXIT
ON DLY LOW
OFF DLY
* ENERGIZED NO
EXIT
* LOW
MID
HI
* FAULT
EXIT
* EXIT
FAULT
* EXIT