Using Enter the operator can toggle between Hide YES and Hide NO.
The Hide function allows the operator to not display the gas reading until the Low Alarm threshold is
exceeded. All outputs will function as normal when the Hide mode selected to YES.
Self Test Menu
Selecting Enter for the Self Test will make the sensor generate a 4-20 mA input into the SEC 3100 from 4
mA to 20 mA (0-fullscale). In the self test mode the SEC 3100 outputs are fully functional. The SEC 3100
will display the rising gas level, the 4-20 mA output will increase to 20 mA, the relays will actuate and the
RS485 information will be transmitted to the control system. The following screen will be displayed
Once the unit reaches full scale the SEC 3100 automatically returns to normal.
NETWORK
* HIDE
NO
* SELF TEST
DATE TIME
ID: 1
0-20.0 PPM
WF6
MC - REMOVED
10.4