AirDistSys 5000

 

 

7 – Operator’s Manual

 

 

max analog output resistance:  

 

100 Ohm 

 

power supply: 

 

 

 

3.3…9 VDC 

 

power consumption:   

 

 

typ.60mA, peak. 110mA, economy mode 6mA 

 

 

1) 

  The  error  of  directional  sensitivity  occurs  when  the  direction of  air  flow  is  other  than  during  the  calibration  of  the 

probe. When measuring low velocity characteristic for indoor environment, this error is negligible (see the above graph). 
For  velocity  above  2  m/s,  this  error  can  be  up  to  2.5%  and  it  should  be  taken  into  account  when  measuring.  At  such 
velocity the flow direction may be easily determined. In order to minimize this error, place the probe (transducer) in the 
same position as at the time calibration procedure. The probes position in calibration procedure are the following:  
- for probe integrated with transducer casing - flow directed on the front wall (logo) of the transducer casing, 
- for probe with cable – flow directed on the sign (dot) on the handle of the probe. 

 

2)

 The upper frequency is defined as the highest frequency of speed fluctuation up to which the instrument measures the 

standard  deviation  of  the  fluctuations  not  more  than  10%  different  than  the  true  standard  deviation    (see  EN  13182 
Ventilation  in  buildings  –  Instrumentation  requirements  for  air  velocity  measurements  in  ventilated  spaces,  2002, 
European Committee for Standardization, Brussels). 

 
 

B

B

.

.

 

 

S

S

e

e

n

n

s

s

o

o

D

D

A

A

C

C

o

o

n

n

 

 

c

c

o

o

n

n

v

v

e

e

r

r

t

t

e

e

r

r

 

 

 

SensoDACon  converter  series  5400  allows  to 

change  a  digital  signal  from  Sensoanemo  transducer 
(socket  RJ45)  on  the  analog  signal  of  temperature  and 
velocity  (output  terminal  block).    There  are  offered  the 
following type: 

-

 

SensoDACon 5420 with voltage output 0-2V 

-

 

SensoDACon 5450 with voltage output 0-5V 

-

 

SensoDACon 54C0 with current output 0-20mA 

Each  of  above  types  can  be  made  from  one  of  the 
following speed ranges: 0-1 m/s, 0-5 m/s or 0-10 m/s. 

Both outputs (one for speed air and one for temperature) 
are linearized, this  means that the  temperature and  speed 
are a linear function of the voltage or current output (see 
table below).  

 

 

Type 

Range 

Output 

Speed 

Temperature 

 

SensoDACon 

5420 

 

0-1m/s 

0-5m/s 

 

0-2V 

V[m/s]=0.5U

v

[V] 

V[m/s]=2.5U

v

[V] 

 

t[

O

C]=25U

t

[V] 

 

SensoDACon 

5450 

0-1m/s 

0-5m/s 

 

0-5V 

V[m/s]=0.2U

v

[V] 

V[m/s]=U

v

[V] 

 

t[

O

C]=10U

t

[V] 

 

SensoDACon 

54C0 

0-1m/s 

0-5m/s 

 

0-20mA 

V[m/s]=0.05I

v

[mA] 

V[m/s]=0.25I

v

[mA] 

 

t[

O

C]=2.5I

t

[mA] 

 
 

Remark: 

 

First  connect  the  converter  to  SensoAnemo  transducer  and  next  turn  on  the  power  to  the  terminal  block. 
After  turning  on  the  power  converter  establishes  communication  with  anemo  transducer  and    initializes  a 
read-mode instantaneous values.  

 
 

Содержание AirDistSys 5000

Страница 1: ...ectronic pl office sensor electronic pl PL 44 100 Gliwice Poland Edition 19 4 A Ai ir r D Di is st tr ri ib bu ut ti io on n M Me ea as su ur ri in ng g S Sy ys st te em m A Ai ir rD Di is st tS Sy ys s 5 50 00 00 0 O Op pe er ra at to or r s s M Ma an nu ua al l ...

Страница 2: ...nd the PC for data logging the built in TCP IP connection enables transfer data from server AirDistSys program to different computers by the networks the DataSocket technology compatible with LabView platform provides converting measurement data into a stream of bytes that is sent across the network to another application Optionally the system may be equipped with transducer SensoBar 5301 which ma...

Страница 3: ...ic 1 Sens oAnemo trans du ce r e le c t ron ic 1 Sens oAnemo trans du ce r e le c t ron ic 1 Sens oAnemo trans du ce r e le c t ron ic 1 max 8 max 8 SensoConnect USB interface Se nsoBee U S B recei v er e l e ctro n ic 60m SensoBee t ra ns m itter e l e ctr o n i c Sens oBee transmi t te r el e ctro ni c SensoCables 5601 length 0 75m SensoCables 5601 length 0 75m max 60m SensoBee transmitter Power...

Страница 4: ...s shape is cylindrical The temperature sensor measures temperature of the ambient air The two sensors are vacuum covered with a special aluminium coating that increases their resistance to contamination and decreases the effect of thermal radiation on the accuracy of velocity measurement Both sensors can be also protected against mechanical damage using a openwork basket 4 made with wire circles I...

Страница 5: ...f 0 f 30 f 60 f 90 f 120 f 150 f 180 f 150 f 120 Directional sensitivity vs yaw angle reference mean velocity of 1 m s 0 0 2 0 4 0 6 0 8 1 w 90 w 60 w 30 w 0 w 30 w 60 w 90 w 120 w 150 w 180 w 150 w 120 Directional sensitivity vs roll angle reference mean velocity of 1 m s 0 04 0 03 0 02 0 01 0 0 01 0 02 0 0 1 0 2 0 3 0 4 0 5 Deviation m s Velocity m s Impact of natural convection horizontal flow ...

Страница 6: ...n between the transducers 7 Turn on the power supply The power led on the casing should blink firstly for a few seconds and next will remain ON If the led blinks permanently it means that is the error The case of the error might to be too low voltage of power supply caused for example by unloaded batteries Remarks 1 The speed sensor 1 must be protected during transport by the shielding tube 3 Note...

Страница 7: ...entilation in buildings Instrumentation requirements for air velocity measurements in ventilated spaces 2002 European Committee for Standardization Brussels B B S Se en ns so oD DA AC Co on n c co on nv ve er rt te er r SensoDACon converter series 5400 allows to change a digital signal from Sensoanemo transducer socket RJ45 on the analog signal of temperature and velocity output terminal block The...

Страница 8: ...f humidity 4s interface port RS485 baud rate 115000 bps power supply 3 3 9 VDC power consumption 6mA economy mode 1mA Connecting to the measuring system The SensoBar 5301transducer can be connected at any place of the RS485 bus to the measuring system for example to SensoAnemo transducer either SensoBee wire less transmitter or SensoBox adapter using the Cable adapter 1W 2G or another see figure b...

Страница 9: ...latch for mounting it in the DIN rail Connecting to the measuring system Remark Pay attention that the power supply adapter should have the voltage polarity on the plug compatible with power socket in the casing out F F S Se en ns so oB Be ee e w wi ir re e l le es ss s t tr ra an ns sm mi it tt te er r The SensoBee transmitter contains an RF module for wire less data transmission The RF module op...

Страница 10: ... connected to USB port therefore it doesn t require the use of external power supply adapter The SensoBeeUSB can also be used for wired data transmission see example D or F in the chapter 2 In this case you should connect to the RJ45 socket one end of the connecting cable and the other end depending on the configuration either the SensoBox adapter or SensoBee wire less transmitter either directly ...

Страница 11: ... capacity Capacity due to reduced efficiency when converting from battery voltage 3 6 V to output voltage 5V theoretical capacity of the battery is 10000 13000mAh Remarks 1 Turn off the PowerBank by disconnecting the power cable when you are finished working Otherwise this may lead to rapid discharge of the battery 2 Charge and discharge the device once every 3 months if it is not used for a longe...

Страница 12: ...n the photos below Attention should be paid to the pipes D1 D3 turn in the order corresponding to the incisions ie D1 pipe single to the D2 dual and D2 to D3 pipe triple D1 pipe should be inserted to the base of the tripod and locked by the knob Then place the grips for fastening the measuring transducers and DIN grips for the accessories and lock them using the knobs C C S St ta an nd da ar rd d ...

Страница 13: ...o ou un nt te ed d g gr ri ip p The rail mounted grip enables to mount the devices equipped with latch for DIN rail so as SensoBar transducer SensoBee wire less receiver SensoBox adapter or PowerBank You can mount it on a tripod in two positions vertical or horizontal ...

Страница 14: ...ce is properly installed and to determine the COM port assignment for the device follow the steps click Settings and Control Panel and then double click on the System icon once the System Properties window is displayed select the Device Manager button double click on Ports COM LPT if the device is correctly installed you should now see the USB device listing and the assigned COM port 6 If you need...

Страница 15: ...nt results Averaging is continuous i e the oldest result is being replaced with the youngest result in the cycle of averaging Averaging Time is independent from Interval Time which is a parameter of logging Logged Data Only logged results are displayed according to logging parameters Interval Time and Logging Time Data Graph Results are shown as vertical strips Numbers of a probe are presented on ...

Страница 16: ... io on n When you use this protocol the program communicates with the DataSocket Server You must provide a named tag for the data which is appended to the URL The data connection uses the named tag to address a particular data item on a DataSocket Server To use this protocol you must run a DataSocket Server In order to enable or disable the DataSocket connection select DataSocket from the menu ite...

Страница 17: ... Data Client is available in the Program Menu Folder SENSOR Electronic Examples C Ca al lc cu ul la at ti io on n o of f R Re es su ul lt ts s Air temperature average speed and standard deviation of speed are calculated as shown in the below figure The sampling rate is a constant and is 8 Hz regardless of the selected mode to display the results To increase the bandwidth of the communications the ...

Страница 18: ...s results are shown on the charts with delayed 1s D Da at ta aS So oc ck ke et t C Co on nn ne ec ct ti io on n When you use this protocol the program communicates with the DataSocket Server You must provide a named tag for the data which is appended to the URL The data connection uses the named tag to address a particular data item on a DataSocket Server To use this protocol you must run a DataSo...

Страница 19: ...TCP connection The part of string with column headers is ended by CR carriage return element On the end of result string is EOL Example data string with results 23 1 TAB 23 2 TAB 22 9 EOL Example data string with column headers ta degC TAB tnw degC TAB tg degC CR 23 1 TAB 23 2 TAB 22 9 EOL The example of TCP Data Client is available in the Program Menu Folder SENSOR Electronic Examples 7 7 G GU UA...

Отзывы: