ENGLISH
Pag. 65
the system has been switched on and the Control panel programmed, some communication
faults may arise from the remote Input modules or detectors connected on the RS485 buses.
This situation would generate a large amount of Faults (FLT) that could hardly be managed
and would require all Faults to be acknowledged before starting an adequate troubleshoo-
ting routine.
The Zone TEST mode allows to overcome this situation the following way: select the Test
Mode, the system zones and automatically all detectors belonging to these zone are set in
test mode.
In the main window, close to each channel (detector) its status will appear: TST (under TEST)
or FLT (fault). Now it will be easy to verify, directly in field, which modules or detectors are
not communicating on the RS485 bus and so fix the issues.
When these fault are fixed, the channels status in the main window will change from FLT to
TEST.
3.18
Modules
In the Zones screen, moving up and down with the arrow keys through the zones list and
pressing ENTER one gets into the modules screen. For the SET / UNSET and TEST / EXIT TEST
operations, see previous paragraph. The procedure is the same.
Figure 36) Modules screen and available options pressing 3-Module
3.19
Relay outputs
In the modules screen, moving up and down with the arrow keys through the modules list,
choosing RIO OUTP and pressing ENTER one gets into the Relays screens.
Figure 37) Outputs screen and options available pressing 3-Relay
Using the up/down arrow keys one may scroll through the list choosing one of the channel