ENGLISH
Pag. 67
Figure 39) Screen with the output operative details
Unlike the above, this screen seen as “Engineer” level, allows changing the relay’s timings.
Refer to the separate cofiguration software manual for more details.
3.20
Detectors (Channels)
In the modules screen, moving up and down with the arrow keys through the modules list
and pressing ENTER, the user gets into the detectors screen with a list of all the detectors
connected to the selected module.
Figure 40) Detectors screen and options available pressing 3-Channel
Using the up/down arrow keys one may scroll through the list choosing one of the channel
and press 3-Channel for the SET / UNSET and TEST / EXIT TEST operations. In the “Operator”
level, the options 3-CHANNEL, is not present. The user should be in “Maintenance” or “Engi-
neer” level to see and to use these options.
By the options of this screen, unlike the Operator level, the “Maintenance” level and the “En-
gineer” level may:
-
Put in Set or Unset the selected channel
-
Put in Test/Maintenance and take out of Test/Maintenance the selected channel
SET / UNSET
Pressing 3-Channel in the Maintenance or the Engineer level it is possible to Set or Unset
parts of the system.
An user with the MAINTENANCE level cannot UNSET more than 50% of the system’s channels
and relays. The only exception is the ENGINEER level, which may UNSET the whole system if
necessary.It is required to do so for maintenance operations in the installation where the gas
detection systems is installed.
TEST / EXIT TEST
This will put to TEST mode or take out of the TEST (EXIT TEST) mode the selected channel. It
is possible to put in TEST mode just parts of the system when user level is “Maintenance” or