2.2)
Detector installation
At the mounting and installation phase be sure all safety precautions have been
considered.
Always consider how important it is the correct positioning of gas detectors to get the
optimum response. Be careful never to install gas detectors close to air intakes or fans
causing strong air currents.
Be sure the detectors are attached to a firm base to prevent vibration that can damage
them, producing unreliable results.
Although the electronics comply with the electromagnetic compatibility rules, it is
advised to keep the detectors at a distance from any radio frequency senders (such as
radio links or similar).
Please be also sure that detectors are placed in a convenient location for future
maintenance and calibration requirements.
We recommend you mount the Smart P detector at nose level (about 150 cm off the ground)
since this is the position suited to detect CO and NO2. The Petrol Vapour detector should, on
the other hand, be installed about 30 cm off the ground
. the CO+PETROL VAPOUR detector
comes with an extension kit to mount the Petrol Vapour sensor 30 cm off the ground.
Also remember that correct detector positioning is essential to ensure prompt and accurate
detection.
The gas detector is always to be mounted with the sensing element placed downward.
For no reasons at all the enclosure can be drilled.
Wall mount the detectors by employing the existing holes