SenseAir aSENSE Скачать руководство пользователя страница 2

 

 

 

 

 

Document 
UMA 139 
 
 

Rev 

Page 
2 (7)

 

 

 

Terminal 

 

Default Output 

 

Default Output 

Range 

 

Outputs of this 

sensor 

 

Output Range of 

this sensor 

 

Out(1) 

 

0-10VDC 

 

0-2000 ppm CO

2

 

 

 

 

Out(2) 

 

0-10VDC 

 

0-50 

o

32-122 

o

 

 

Table I.  Default output configurations for aSENSE  

 

 

 

Formulas for calculation of output values 

 

 
Configuration 

 
Output Range

 

 
Formula for calculation

 

 
0-10 VDC 

 
0-2000 ppm CO

 
0-50 

o

32-122 

o

 
CO

2

 value = Volt/10*2000 

 
Temperature value in

 o

C = Volt/10*50 = Volt*5 

Temperature value in

 o

F = Volt*9+32 

 
2-10 VDC 

 
0-2000 ppm CO

 
0-50 

o

32-122 

o

F

 

 
CO

2

 value = (Volt 

–2)/8*2000  

 
Temperature value in

 o

C = (Volt 

–2)/8*50 

Temperature value in

 o

F = (Volt 

–2)/8*(122-32)+32 

 
4-20 mA 

 
0-2000 ppm CO

 
0-50 

o

32-122 

o

F

 

 
CO

2

 value = (mA-4)*2000/16  

 
Temperature value in

 o

C = (mA-4)*50/16 

Temperature value in

 o

F = (mA-4)/16*(122-32)+32 

 
a-b 

 
c

–d 

 
Value = (reading-a)/(b-a)*(d-c)+c 

 

 

a = lowest value of the configuration 
b = highest value of the configuration 
c = lowest value of the range 
d = highest value of the range 

Table II. Calculation of CO

2

 value and temperature value for aSENSE

 

 
 

Output Configurations

 

 
The sensors/controllers are supplied from the factory (unless otherwise ordered) with 
0...10VDC  linear  outputs  for  Out(1)  and  Out(2

)

  (see  Table  I).  If  other  options  are 

needed for the application, the output jumpers have to be configured before the unit 
is powered up. Each jumper selection is independent from the others, except for the 
“Start  point  selection”  jumper,  which  affects  both  Out(1)  and  Out(2

)

  linear  outputs. 

Alternative  measuring  ranges  of  the  outputs  can  be  selected  with  the  software  UIP 
(version 5 or later).

 

 

 

Содержание aSENSE

Страница 1: ...well as for duct mounting The unit is designed for connecting to Direct Digital Control DDC The linear output functions are pre programmed as CO2 and temperature transmitters with jumper selected outp...

Страница 2: ...o F CO2 value mA 4 2000 16 Temperature value in o C mA 4 50 16 Temperature value in o F mA 4 16 122 32 32 a b c d Value reading a b a d c c a lowest value of the configuration b highest value of the...

Страница 3: ...erature measurements accuracy is valid only for units configured in voltage outputs mode Table II Configuration jumpers for aSENSE Self diagnostics The system contains complete self diagnostic procedu...

Страница 4: ...of Range Error Accompanies most of other errors Resets automatically after source of error disappearance Try sensor in fresh air Check connections of temperature and relative humidity probe Check deta...

Страница 5: ...e cable is to be connected to the UART port slide connector see Fig 5 For change of control parameters and re calibration CO2 and temperature this PC tool has to be used The check can be done on site...

Страница 6: ...n must be taken in order not to damage the temperature probe in the sampling tube When putting the PCB back in the protective housing the probe must be gently positioned in the sampling tube Figure 3...

Страница 7: ...hall ship them to Buyer s designated return destination freight pre paid 2 Warranty Limitations This warranty does not extend to any unit that has been subject to misuse neglect or accident that has b...

Отзывы: