background image

www.senjusprinkler.com

Document No. U03688A • 01-06-2022 

Page 4 of 8 

Obstruction to Water Distribution

Locations of sprinklers must follow the obstruction rules of NFPA 13.

General Service Conditions

The Model RC-QR must only be utilized in sprinkler systems per NFPA 13 guidelines.

Operational Sensitivity Criteria

For proper operational sensitivity, the Model RC-QR must be installed beneath a solid ceiling having a smooth or textured 
surface.

Heat Source Criteria

Refer to NFPA 13 for the requirements relating to the prevention of possible activation of the Heat Responsive Element of 
Model RC-QR, due to the exposure of a heat source other than an actual fire.

Available Sprinkler Temperature Ratings

Sprinkler Temperature 

Classification

Sprinkler Nominal 

Temperature Rating

Maximum Ambient Ceiling 

Temperature

Temperature Rating of the 

Cover Plate Assembly

Ordinary

162°F (72°C)

100°F (38°C)

140°F (60°C)

Intermediate

205°F (96°C)

150°F (66°C)

140°F (60°C) 

1)

Intermediate

205°F (96°C)

150°F (66°C)

162°F (72°C)

1) Maximum ambient temperature for the Cover Plate Assembly is 100°F (38°C).

Precautionary Warnings for Corrosive Environments

Model RC-QR sprinklers should not be installed where they may be subjected to a corrosive environment including the 
following:

1. Chlorine ion and Chloride environment

Stress corrosion cracking may be caused by exposure to environments with Chlorine ion and Chloride. Exposure to 
this environment may result in sprinklers operating under Non-Fire conditions or Not Operating when exposed to an 
actual fire.

2. Sprinkler system piping with Copper

Sprinkler systems should be constructed in compliance with the applicable standards and the requirements for 
copper piping when copper piping is used in the sprinkler system. (Reference standards NFPA 13, ASTM B813, B828, 
and CDA (Copper Development Association) – Solder Joint)

All residual flux must be removed from the interior and exterior of the copper piping by thoroughly flushing before 
installation of the Sprinkler Heads. Otherwise, residues of flux may cause corrosion and/or leakage in the sprinkler 
system.

I N S TA L L AT I O N

The Model RC-QR must be installed in accordance with the following instructions:

NOTES

Do not use any sprinklers which have been subjected to potential mechanical damage. Do not use any sprinklers which show 
deformation or cracking in either the Sprinkler or the Protective Cap.

Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the potential for 
damage to the sprinklers that could cause improper operation or non-operation.

Содержание RC-QR

Страница 1: ...des 1 2 inch 12 8mm vertical adjustment This adjustment in installation decreases the need for precise cutting of the pipe that drops to the sprinkler and allows for a perfect fit with a range of pipe...

Страница 2: ...of this document to the owner or their representative and in turn it is the obligation of the owner to provide a copy of this document to a succeeding owner The owner is responsible for maintaining th...

Страница 3: ...his document may concern specifications which are more stringent and which take precedence over those specified in NFPA 13 or by the authority having jurisdiction The Model RC QR must not be used in a...

Страница 4: ...ected to a corrosive environment including the following 1 Chlorine ion and Chloride environment Stress corrosion cracking may be caused by exposure to environments with Chlorine ion and Chloride Expo...

Страница 5: ...ing has been lifted from its normal position in the process of tightening the Cover Plate Assembly readjust the cover plate assembly as necessary If the flange of the Cover Plate Assembly cannot conta...

Страница 6: ...ective Cap Removal Deflector 5 8 1 4 16 6 4 mm Mounting Surface 2 50 8 mm Cup Screw 2 5 8 68 mm or 3 1 4 83 mm or UL only 2 5 8 square 68 mm 2 50 8 mm Cover Plate Assembly 1 16 1 6 mm Figure 6 Install...

Страница 7: ...r duster or gently vacuuming with a soft bristle i e dusting brush attachment Exercise suitable safety precautions in the use and storage of highly flammable materials The rapid rate of fire developme...

Страница 8: ...ive ratchet not included Socket NR H Plastic for use with a 1 2 drive ratchet not included Cap Removal Tool for RC Cover Plate Installation Tool Sprinkler Model RC QR SIN SS9561 Quick Response Standar...

Отзывы: