background image

www.senjusprinkler.com

Document No. U03688A • 01-06-2022 

Page 2 of 8 

•  Approvals:

 

{

 

c

UL

US

 Listed / as Quick Response

 

{

FM Approved / as Standard Response

•  Sprinkler Identification Number (SIN):

 SS9561

•  Maximum Working Pressure:

 175 psi (12.1 bar)

•  Discharge Coefficient (Nominal K-Factor):

 

{

K = 5.6 GPM / psi

1/2

 (80.6 LPM / bar

1/2

)

•  Temperature Rating: 

 

{

162°F (72°C) Sprinkler with 140°F (60°C) Cover Plate

 

{

205°F (96°C) Sprinkler with 140°F (60°C) Cover Plate

 

{

205°F (96°C) Sprinkler with 162°F (72°C) Cover Plate

•  Color Code:

 

{

162°F (72°C): Uncolored

 

{

205°F (96°C): White

•  Color Code (Cover Plate):

 

{

140°F (60°C): No Mark

 

{

162°F (72°C): White-Colored Mark

•  Vertical Adjustment:

 1/2 inch (12.8 mm)

•  Cover Plate Finishes:

 

{

Standard Finishes:

 White, Ivory, Beige, Brown, Black, 

Nickel, Copper, Wood Grain

 

{

Custom Finishes:

 Custom color and custom pattern 

cover plates are available on special order. Contact a 
Senju Sprinkler representative with any custom orders. 
Please see chart on page 8 for more detail.

•  Physical Characteristics:

 Ref. Figures 1 and 1.1

T E C H N I C A L  DATA

Figure 1:

 Model RC-QR, K = 5.6

Figure 1.1:

 Marking (Color Code)

It is the responsibility of the installing contractor to provide a copy of this document to the owner or their representative, 
and in turn, it is the obligation of the owner to provide a copy of this document to a succeeding owner.

The owner is responsible for maintaining their fire protection system and devices in proper operating condition. The 
installing contractor or sprinkler manufacturer should be contacted with any related questions.

O P E R AT I O N

In case of fire, the solder component that holds together the Cover Plate and the Retainer melts. Then the Cover Plate is 
released at once. As a result, the Deflector drops down to the intended position. Two Heat Collectors are exposed to fire, 
and when sufficient heat from the fire is reached, internal components of the sprinkler fall apart. This leads to the water 
flow to be distributed on the affected fire area. (Ref. Figure 2)

Color Code

Cover Plate

(Top View)

Sprinkler

(Bottom View)

Marking (Deflector)
  SIN: SS9561

  K-Factor: K5.6

  Temperature Rating: 

    162°F (72°C) or

  205°F 

(96°C)

  UL Mark

  FM Mark

1/2″ NPT

2-1/4″ (57.7 mm)

2-1/16″ (Ø52 mm)

Marking

 

Lot No.

 

 

Year of Manufacture

 

SIN: SS9561

 

K-Factor: K5.6

 

Temperature Rating: 

 

 

162°F (72°C) or

 

 

205°F (96°C)

 

Control No.: 177R

 

UL Mark

 

FM Mark

2-5/8″ (Ø68 mm)

or 3-1/4″ (Ø83 mm)

 or UL only: 2-5/8″ square (

68 mm)

 Body (Copper Alloy)

 Deflector (Phosphor Bronze)

 Gasket (PTFE)

 Fusible Metal (Solder)

 Heat Collector (Copper)

 Cover Plate Assembly

Содержание RC-QR

Страница 1: ...des 1 2 inch 12 8mm vertical adjustment This adjustment in installation decreases the need for precise cutting of the pipe that drops to the sprinkler and allows for a perfect fit with a range of pipe...

Страница 2: ...of this document to the owner or their representative and in turn it is the obligation of the owner to provide a copy of this document to a succeeding owner The owner is responsible for maintaining th...

Страница 3: ...his document may concern specifications which are more stringent and which take precedence over those specified in NFPA 13 or by the authority having jurisdiction The Model RC QR must not be used in a...

Страница 4: ...ected to a corrosive environment including the following 1 Chlorine ion and Chloride environment Stress corrosion cracking may be caused by exposure to environments with Chlorine ion and Chloride Expo...

Страница 5: ...ing has been lifted from its normal position in the process of tightening the Cover Plate Assembly readjust the cover plate assembly as necessary If the flange of the Cover Plate Assembly cannot conta...

Страница 6: ...ective Cap Removal Deflector 5 8 1 4 16 6 4 mm Mounting Surface 2 50 8 mm Cup Screw 2 5 8 68 mm or 3 1 4 83 mm or UL only 2 5 8 square 68 mm 2 50 8 mm Cover Plate Assembly 1 16 1 6 mm Figure 6 Install...

Страница 7: ...r duster or gently vacuuming with a soft bristle i e dusting brush attachment Exercise suitable safety precautions in the use and storage of highly flammable materials The rapid rate of fire developme...

Страница 8: ...ive ratchet not included Socket NR H Plastic for use with a 1 2 drive ratchet not included Cap Removal Tool for RC Cover Plate Installation Tool Sprinkler Model RC QR SIN SS9561 Quick Response Standar...

Отзывы: