The Model RC-QR sprinklers are listed by UL and C-UL as quick response / standard coverage for use in accordance 
with NFPA.

Also the Model RC-QR is FM Approved as a Standard Response for Non-Corrosive Atmospheres. The herein stated rules 
for use and installation of the Model RC-QR are provided by the manufacturer and must be strictly implemented for safe 
and full results.

D E S I G N   C R I T E R I A

Notes

Fire Sprinkler Systems should only be designed and installed by individuals who are completely familiar with automatic 
sprinkler system design, installation procedures, and techniques.

Several criteria may apply to the installation and usage of each sprinkler. Consequently, it is recommended that the sprinkler 
system designer review and develop a working understanding of the complete list of criteria prior to initiating the design of the 
sprinkler system.

Questions concerning sprinkler installation and usage criteria, which are not covered by the following instructions, should be 
submitted to your contracted company. Include sketches and technical details, as appropriate.

In some instances, the requirements of this document may concern specifications which are more stringent, and which take 
precedence over those specified in NFPA 13 or by the authority having jurisdiction.

The Model RC-QR must not be used in applications where the air pressure above the ceiling is greater than that below.

Inspect all sprinklers after installation to ensure that both the gap between the cover plate, ceiling and the 6 slots in the cup 
are open and free from any air flow impediment.

The spray from the sprinkler is distributed radially outward and downward from the sprinkler deflector. Consequently, the 
sprinklers must be located such that there will be no blind spaces shielded from spray by partitions, room dividers, overhangs 
or other parts of the dwelling structure.

The number of sprinklers within each compartment (as defined by NFPA 13) must be kept as few as possible while observing 
all guidelines relating to obstructions and spacing.

Use only the Cover Plate provided for the Model RC-QR. The sprinkler must be secured in place by firmly fastening the 
sprinkler system piping to the structure. If the sprinkler is not properly secured in position, reaction forces resulting from 
sprinkler operation could alter its orientation and its water distribution pattern.

Normal Condition                 Cover Plate Operation                   Sprinkler Operation                  Water Discharge

Figure 2:

 Operation Process (For illustrative purposes only)

Содержание RC-QR

Страница 1: ...des 1 2 inch 12 8mm vertical adjustment This adjustment in installation decreases the need for precise cutting of the pipe that drops to the sprinkler and allows for a perfect fit with a range of pipe...

Страница 2: ...of this document to the owner or their representative and in turn it is the obligation of the owner to provide a copy of this document to a succeeding owner The owner is responsible for maintaining th...

Страница 3: ...his document may concern specifications which are more stringent and which take precedence over those specified in NFPA 13 or by the authority having jurisdiction The Model RC QR must not be used in a...

Страница 4: ...ected to a corrosive environment including the following 1 Chlorine ion and Chloride environment Stress corrosion cracking may be caused by exposure to environments with Chlorine ion and Chloride Expo...

Страница 5: ...ing has been lifted from its normal position in the process of tightening the Cover Plate Assembly readjust the cover plate assembly as necessary If the flange of the Cover Plate Assembly cannot conta...

Страница 6: ...ective Cap Removal Deflector 5 8 1 4 16 6 4 mm Mounting Surface 2 50 8 mm Cup Screw 2 5 8 68 mm or 3 1 4 83 mm or UL only 2 5 8 square 68 mm 2 50 8 mm Cover Plate Assembly 1 16 1 6 mm Figure 6 Install...

Страница 7: ...r duster or gently vacuuming with a soft bristle i e dusting brush attachment Exercise suitable safety precautions in the use and storage of highly flammable materials The rapid rate of fire developme...

Страница 8: ...ive ratchet not included Socket NR H Plastic for use with a 1 2 drive ratchet not included Cap Removal Tool for RC Cover Plate Installation Tool Sprinkler Model RC QR SIN SS9561 Quick Response Standar...

Отзывы: