Leaking or corroded sprinklers must be replaced.
Automatic Sprinklers must be kept in a cool and dry place.
Automatic sprinkler must never be physically altered, such as painted, plated, or coated, once shipped from the
factory. If the sprinklers have been in any way modified, they must be replaced.
Great caution must be applied to prevent damage to the sprinklers at all stages - before, during, and after installation.
Damaged units because of dropping, hitting, over-tightening, or wrench slippage, must be replaced.
The Model FR-RES must only be replaced with pendent sprinklers which are listed for residential fire protection
service and which have the same nominal K-Factor, the same coverage area, and the same or lower flow ratings (as
indicated under TABLE A “Hydraulic Design Criteria”).
When remodeling, such as by adding false beams or light fixtures or changing the location of compartment walls, first
verify that the new construction will not violate the installation requirements of the applicable standards of NFPA.
Alter the new construction and/or the sprinkler system to suit the requirements of this document and the applicable
NFPA regulations.
The owner is responsible for the maintenance of the sprinkler system, including inspection and testing of its
compliance with this document, as well as the standards of the National Fire Protection Association (e.g., NFPA 25),
and the regulations of any other authorities having jurisdiction. The owner should direct any questions regarding the
above rules and regulations to the installing contractors or the sprinkler manufacturer. It is recommended that
automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service in accordance
with NFPA 25.
Limited Warranty
For details of warranty, refer to Sales Contract.
ORDER PROCEDURE
When placing an order, please contact a local distributor with the following information (Model Name, Temperature Rating and
Finish).
Sprinkler
Model: FR-RES K4.9
Temperature Rating: 162°F (72°C), 175°F (79°C), 205°F (96°C)
Finishes: Natural Brass, White Painted, Black Painted, Chrome Plated
For SIN and combination of Recessed Escutcheon, refer to the table below.
Type
SIN
Temperature
Recessed Escutcheon
Pendent
162°F, 175°F, 205°F
―
Recessed Pendent
162°F, 175°F
D1 (1/2” total adjustment)
Recessed Pendent
SS4451
162°F, 175°F, 205°F
D3 (1/2” total adjustment)
Recessed Escutcheon
Model: D1 Recessed Escutcheon (Inner Ring and Outer Ring, 1/2” total adjustment)
Model: D3 Recessed Escutcheon (Inner Ring and Outer Ring, 1/2” total adjustment)
Finishes: Brass Plated, White Painted, Black Painted, Chrome Plated
Tools for Installation
・
Wrench FR-S (Open-end wrench type)
・
Socket FR-H (Socket wrench type)
For use with a 1/2" drive ratchet (not included)