Page

8  of  8 

Document  No.U087143

     

Date

Oct/18/2019 

Leaking or corroded sprinklers must be replaced.   
Automatic Sprinklers must be kept in a cool and dry place. 
Automatic  sprinkler  must  never  be  physically  altered,  such  as  painted,  plated,  or  coated,  once  shipped  from  the 
factory. If the sprinklers have been in any way modified, they must be replaced. 
Great caution must be applied to prevent damage to the sprinklers at all stages - before, during, and after installation. 
Damaged units because of dropping, hitting, over-tightening, or wrench slippage, must be replaced. 

The  Model  FR-RES  must  only  be  replaced  with  pendent  sprinklers  which  are  listed  for  residential  fire  protection 
service and which have the same nominal K-Factor, the same coverage area, and the same or lower flow ratings (as 
indicated under TABLE A “Hydraulic Design Criteria”). 

When remodeling, such as by adding false beams or light fixtures or changing the location of compartment walls, first 
verify  that  the  new construction will  not  violate  the  installation  requirements  of  the  applicable  standards  of NFPA. 
Alter the new construction and/or the sprinkler system to suit the requirements of this document and the applicable 
NFPA regulations. 
The  owner  is  responsible  for  the  maintenance  of  the  sprinkler  system,  including  inspection  and  testing  of  its 
compliance with this document, as well as the standards of the National Fire Protection Association (e.g., NFPA 25), 
and the regulations of any other authorities having jurisdiction. The owner should direct any questions regarding the 
above  rules  and  regulations  to  the  installing  contractors  or  the  sprinkler  manufacturer.  It  is  recommended  that 
automatic  sprinkler  systems  be  inspected,  tested,  and  maintained  by  a qualified  Inspection  Service  in  accordance 
with NFPA 25. 

 
 

Limited Warranty   

 

For details of warranty, refer to Sales Contract. 

 
 

ORDER PROCEDURE 

 

When placing an order, please contact a local distributor with the following information (Model Name, Temperature Rating and 
Finish). 

 

Sprinkler 

Model: FR-RES K4.9 
Temperature Rating: 162°F (72°C), 175°F (79°C), 205°F (96°C) 
Finishes: Natural Brass, White Painted, Black Painted, Chrome Plated 

For SIN and combination of Recessed Escutcheon, refer to the table below. 

Type 

SIN 

Temperature 

Recessed Escutcheon 

Pendent 

162°F, 175°F, 205°F 

― 

Recessed Pendent 

162°F, 175°F 

D1 (1/2” total adjustment) 

Recessed Pendent 

SS4451 

162°F, 175°F, 205°F 

D3 (1/2” total adjustment) 

 

Recessed Escutcheon 

Model: D1 Recessed Escutcheon (Inner Ring and Outer Ring, 1/2” total adjustment) 
Model: D3 Recessed Escutcheon (Inner Ring and Outer Ring, 1/2” total adjustment) 
Finishes: Brass Plated, White Painted, Black Painted, Chrome Plated 

 

Tools for Installation 

  Wrench FR-S (Open-end wrench type) 

  Socket FR-H (Socket wrench type) 

For use with a 1/2" drive ratchet (not included) 

 
 

Содержание FR-RES

Страница 1: ...residential fire sprinkler systems are not a substitute for fire safety awareness or fire safety construction required by building codes WARNINGS The Model FR RES must be installed and maintained in a...

Страница 2: ...nk is comprised of two link halves that are joined together with a thin layer of solder When the rated temperature is reached the solder melts and the two link halves separate This leads to the water...

Страница 3: ...o cover a particular space The sprinkler must be secured in place by firmly fastening the sprinkler system piping to the structure If the sprinkler is not properly secured in position reaction forces...

Страница 4: ...ture Rating 162 F 72 C Intermediate Temperature Rating 175 F 79 C Intermediate Temperature Rating 205 F 96 C Maximum Coverage Area a Ft Ft m m Maximum Spacing Ft m Flow b GPM LPM Pressure b PSI bar Fl...

Страница 5: ...djustment of the D1 or D3 Recessed Escutcheon Re adjust the sprinkler fitting to correct the position Installing Procedure Install Model FR RES sprinklers by the steps and figures shown below Use only...

Страница 6: ...e 6 of 8 Document No U087143 Date Oct 18 2019 FIGURE 4 INSTALLATION CORRECT and INCORRECT FIGURE 5 INSTALLATION WRENCH and SOCKET A 1 2 drive ratchet not included is required for use with the Socket F...

Страница 7: ...on for maintenance of the fire protection system permission to close the main control valve must be obtained from the proper authorities and all affected parties by this action and must be informed be...

Страница 8: ...pection and testing of its compliance with this document as well as the standards of the National Fire Protection Association e g NFPA 25 and the regulations of any other authorities having jurisdicti...

Отзывы: