Document  No.U087143

     

Date

Oct/18/2019 

DESIGN CRITERIA 

 

The herein stated rules for use and installation of Model FR-RES are provided by the manufacturer and must be strictly 
implemented for safe and full results. Only the D1 or D3 Recessed Escutcheon, as applicable, is to be used for recessed 
pendent installations. D1 Recessed Escutcheons are not listed for use with the 205°F heads. D3 Recessed Escutcheons are 
required for the 205°F heads. 

 

NOTES 

Residential Fire Sprinkler Systems should only be designed and installed by individuals who are completely familiar 
with automatic sprinkler system design, installation procedures, and techniques. 
Several criteria may apply to the installation and usage of each sprinkler. Consequently, it is recommended that the 
sprinkler  system  designer  review  and  develop  a  working  understanding  of  the  complete  list  of  criteria  prior  to 
initiating the design of the sprinkler system. 
Questions concerning sprinkler installation and usage criteria, which are not covered by the following instructions, 
should be submitted to your contracted company. Include sketches and technical details, as appropriate. 
In  some  instances,  the  requirements  of  this  document  may  concern  specifications  which  are  more  stringent,  and 
which take precedence over those specified in NFPA 13, 13D, 13R or by the authority having jurisdiction. 
The spray from the sprinkler is distributed radially outward and downward from the sprinkler deflector. Consequently, 
the sprinklers must be located such that there will be no blind spaces shielded from spray by partitions, room dividers, 
overhangs or other parts of the dwelling structure. 
The  number  of  sprinklers  within  each  compartment  (as  defined  by  NFPA  13,  13D  or  13R)  must  be  kept  as  few  as 
possible. Do NOT use more sprinklers than necessary to cover a particular space. 
The sprinkler must be secured in place by firmly fastening the sprinkler system piping to the structure. If the sprinkler 
is not properly secured in position, reaction forces resulting from sprinkler operation could alter its orientation and its 
water distribution pattern. 
 

Obstruction to Water Distribution 

Locations of sprinklers must follow the obstruction rules of NFPA 13, 13D and 13R for Residential Sprinklers. 
 

General Service Conditions 

The Model FR-RES must only be utilized in WET PIPE sprinkler systems. 

 

Heat Source Criteria 

Refer to NFPA 13D, 13R or 13 for the requirements relating to the prevention of possible activation of the Heat Responsive 
Element of Model FR-RES, due to the exposure of a heat source other than an actual fire. 

         

Available Sprinkler Temperature Ratings 

Sprinkler Temperature Classification 

Sprinkler Nominal Temperature Rating  Maximum Ambient Ceiling Temperature 

Ordinary 

162°F (72°C) 

100°F (38°C) 

Intermediate 

175°F (79°C) 
205°F (96°C) 

150°F (66°C) 

 

Precautionary Warnings for Corrosive Environments 

Model  FR-RES  sprinklers  should  not  be  installed  where  they  may  be  subjected  to  a  corrosive  environment  including  the 
following: 

(1) Chlorine ion and Chloride environment. 

Stress  corrosion  cracking  may  be  caused  by  exposure  to environments  with  Chlorine  ion  and  Chloride.  Exposure  to  this 
environment may result in sprinklers operating under Non-Fire conditions or Not Operating when exposed to an actual fire. 

(2) Sprinkler system piping with Copper. 

Sprinkler systems should be constructed in compliance with the applicable standards and the requirements for copper piping 
when copper piping is used in the sprinkler system. (Reference standards NFPA 13, ASTM B813, B828, and CDA (Copper 
Development Association) – Solder Joint) 
All residual flux must be removed from the interior and exterior of the copper piping by thoroughly flushing before installation 
of the Sprinkler Heads. Otherwise, residues of flux may cause corrosion and leakage in the sprinkler system. 

 
 
 

Содержание FR-RES

Страница 1: ...residential fire sprinkler systems are not a substitute for fire safety awareness or fire safety construction required by building codes WARNINGS The Model FR RES must be installed and maintained in a...

Страница 2: ...nk is comprised of two link halves that are joined together with a thin layer of solder When the rated temperature is reached the solder melts and the two link halves separate This leads to the water...

Страница 3: ...o cover a particular space The sprinkler must be secured in place by firmly fastening the sprinkler system piping to the structure If the sprinkler is not properly secured in position reaction forces...

Страница 4: ...ture Rating 162 F 72 C Intermediate Temperature Rating 175 F 79 C Intermediate Temperature Rating 205 F 96 C Maximum Coverage Area a Ft Ft m m Maximum Spacing Ft m Flow b GPM LPM Pressure b PSI bar Fl...

Страница 5: ...djustment of the D1 or D3 Recessed Escutcheon Re adjust the sprinkler fitting to correct the position Installing Procedure Install Model FR RES sprinklers by the steps and figures shown below Use only...

Страница 6: ...e 6 of 8 Document No U087143 Date Oct 18 2019 FIGURE 4 INSTALLATION CORRECT and INCORRECT FIGURE 5 INSTALLATION WRENCH and SOCKET A 1 2 drive ratchet not included is required for use with the Socket F...

Страница 7: ...on for maintenance of the fire protection system permission to close the main control valve must be obtained from the proper authorities and all affected parties by this action and must be informed be...

Страница 8: ...pection and testing of its compliance with this document as well as the standards of the National Fire Protection Association e g NFPA 25 and the regulations of any other authorities having jurisdicti...

Отзывы: