background image

Page

5  of  8 

Document  No.U087143

     

Date

Oct/18/2019 

INSTALLATION 

 
The Model FR-RES must be installed in accordance with the following instructions: 
 

NOTES 

Do  not  use  any  sprinklers  which  have  been  subjected  to  potential  mechanical  damage.  Do  not  use  any  sprinklers 
which show deformation or cracking in either the Sprinkler or the Protector. 
Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the 
potential for damage to the sprinklers that could cause improper operation or non-operation. 
The Protector must remain on the sprinkler during installation. After the installation is completed, the Protector must 
be removed to place the sprinkler in service. 
Use a torque of 7 to 14 ft·lbs (9.5 to 19.0 N·m) to achieve a 1/2 inch NPT sprinkler joint. If you exceed the recommended 
maximum torque, this could result in damage to the sprinkler inlet, which may lead to leakage from the sprinkler. 

Use only Wrench FR-S or Socket FR-H for installation of Model FR-RES sprinklers. Use of any other wrench or socket 
is prohibited and may cause damage to the sprinkler. 

Do not over or under tighten the sprinkler due to an inadequate adjustment of the D1 or D3 Recessed Escutcheon. 
Re-adjust the sprinkler fitting to correct the position. 

   

 

Installing Procedure 

Install Model FR-RES sprinklers by the steps and figures shown below. Use only D1 or D3 Recessed Escutcheons with Model 
FR-RES sprinklers. (D1 Recessed Escutcheons are not listed for use with the 205°F heads. D3 Recessed Escutcheons are 
required for the 205°F heads.) Use of any other recessed escutcheon is prohibited and may void the warranty and approvals. 
Model FR-RES sprinklers are only to be installed in the pendent position with the waterway perpendicular to the ceiling. 

 

Step 1 

Install the Inner Ring of the D1 or D3 Recessed Escutcheon over the sprinkler threads, as applicable. (Ref. Figure 3 and 4) 

 

Step 2 

Apply pipe-thread sealant to the threads. Begin hand-tightening the sprinkler into the sprinkler fitting in the pendent position. 

 

Step 3 

Using the Socket FR-H or Wrench FR-S, tighten the sprinkler into the sprinkler fitting with a torque of 7 to 14 ft·lbs

 

(9.5 to 19.0 

N·m). (Ref. Figure 5) 
A 1/2" drive ratchet (not included) is required for use with the Socket FR-H. 

 

Step 4 

Remove the Protector by hand. (Ref. Figure 6) 
Slide on the Outer Ring of the D1 or D3 Recessed Escutcheon over the Sprinkler and push the Outer Ring over the Inner 
Ring until its flange comes in contact with the ceiling. (Ref. Figure 7) 

 

 

 

 

FIGURE 3. PENDENT and RECESSED PENDENT SPRINKLER

 

 
 

Содержание FR-RES

Страница 1: ...residential fire sprinkler systems are not a substitute for fire safety awareness or fire safety construction required by building codes WARNINGS The Model FR RES must be installed and maintained in a...

Страница 2: ...nk is comprised of two link halves that are joined together with a thin layer of solder When the rated temperature is reached the solder melts and the two link halves separate This leads to the water...

Страница 3: ...o cover a particular space The sprinkler must be secured in place by firmly fastening the sprinkler system piping to the structure If the sprinkler is not properly secured in position reaction forces...

Страница 4: ...ture Rating 162 F 72 C Intermediate Temperature Rating 175 F 79 C Intermediate Temperature Rating 205 F 96 C Maximum Coverage Area a Ft Ft m m Maximum Spacing Ft m Flow b GPM LPM Pressure b PSI bar Fl...

Страница 5: ...djustment of the D1 or D3 Recessed Escutcheon Re adjust the sprinkler fitting to correct the position Installing Procedure Install Model FR RES sprinklers by the steps and figures shown below Use only...

Страница 6: ...e 6 of 8 Document No U087143 Date Oct 18 2019 FIGURE 4 INSTALLATION CORRECT and INCORRECT FIGURE 5 INSTALLATION WRENCH and SOCKET A 1 2 drive ratchet not included is required for use with the Socket F...

Страница 7: ...on for maintenance of the fire protection system permission to close the main control valve must be obtained from the proper authorities and all affected parties by this action and must be informed be...

Страница 8: ...pection and testing of its compliance with this document as well as the standards of the National Fire Protection Association e g NFPA 25 and the regulations of any other authorities having jurisdicti...

Отзывы: