Document  No.U087143

     

Date

Oct/18/2019 

 

Hydraulic Design Criteria 

The minimum required sprinkler flow rates for systems designed to NFPA 13D or 13R are given in TABLE A as a function of 
temperature rating and the maximum allowable coverage area. The sprinkler flow rate is the minimum required discharge from 
the most hydraulically demanding sprinkler from each of the total number of “design sprinklers” as specified in NFPA 13D or 
13R. 
For systems designed to NFPA 13, the number of designed sprinklers is to be the four most hydraulically demanding sprinklers. 
The minimum required discharge from each of the four sprinklers is to be the greater of the following: 

 

The  flow  rates  given  in  TABLE  A  for  NFPA  13D  and  13R as  a function  of  temperature rating  and  maximum  allowable 
coverage area. 

 

A minimum discharge of 0.1GPM/sq.ft. [4.07LPM/sq.m] over the “design area” comprised of the four most hydraulically 
demanding sprinklers for the actual coverage area being protected by the four sprinklers. 

 

TABLE A. NFPA 13D & 13R WET PIPE HYDRAULIC DESIGN CRITERIA for Model SS4451 

For systems with ceiling types smooth flat horizontal, or beamed, or sloped, in accordance with NFPA 13D, 13R or 13 as 
applicable.

 

Ordinary 

Temperature Rating 

162°F

 

(72°C) 

Intermediate 

Temperature Rating 

175°F

 

(79°C) 

Intermediate 

Temperature Rating 

205°F

 

(96°C) 

Maximum 
Coverage 

Area

(a)

 

Ft. × Ft. 
(m × m) 

Maximum 

Spacing 

Ft. 

(m) 

Flow

(b)

 

GPM 

(LPM) 

Pressure

(b)

 

PSI 

(bar) 

Flow

(b)

 

GPM 

(LPM) 

Pressure

(b)

 

PSI 

(bar) 

Flow

(b)

 

GPM 

(LPM) 

Pressure

(b)

 

PSI 

(bar) 

Deflector 

to 

Ceiling 

Installation 

Type 

Minimum 

Spacing 

Ft. 

(m) 

12×12 

(3.7×3.7) 

12 

(3.7) 

13 

(49.2) 

7.0 

(0.48) 

13 

(49.2) 

7.0 

(0.48) 

13 

(49.2) 

7.0 

(0.48) 

14×14 

(4.3×4.3) 

14 

(4.3) 

13 

(49.2) 

7.0 

(0.48) 

13 

(49.2) 

7.0 

(0.48) 

13 

(49.2) 

7.0 

(0.48) 

16×16 

(4.9×4.9) 

16 

(4.9) 

13 

(49.2) 

7.0 

(0.48) 

― 

― 

13 

(49.2) 

7.0 

(0.48) 

18×18 

(5.5×5.5) 

18 

(5.5) 

17 

(64.4) 

12.0 

(0.83) 

17 

(64.4) 

12.0 

(0.83) 

17 

(64.4) 

12.0 

(0.83) 

20×20 

(6.1×6.1) 

20 

(6.1) 

20 

(75.7) 

16.7 

(1.15) 

20 

(75.7) 

16.7 

(1.15) 

20 

(75.7) 

16.7 

(1.15) 

Smooth 

Ceilings 

1-1/16 to 4 

Inches. 

 

Beamed 

Ceilings 

per NFPA 
13D, 13R 

or 13 

Installed in 

beam 

1-1/16 to 

1-9/16 
inches 

below 

bottom of 

beam. 

Pendent   

or 

Recessed 

Pendent 

(2.4) 

(a)    For coverage area dimensions less than the above mentioned, it needs to use the minimum required flow for the 

Next Higher Coverage Area listed. 

(b)    Requirement is based on minimum flow in GPM/LPM from each sprinkler. The associated residual pressures are 

calculated using the nominal K-Factor. Refer to Hydraulic Design Criteria Section for details. 

 

Sprinkler Spacing Criteria 

The minimum spacing between sprinklers is 8 feet (2.4m). The maximum spacing between sprinklers cannot go beyond the 
coverage area calculated by using the specific hydraulic factors. (Ref. TABLE A) 

 
 
 
 
 
 
 
 

Содержание FR-RES

Страница 1: ...residential fire sprinkler systems are not a substitute for fire safety awareness or fire safety construction required by building codes WARNINGS The Model FR RES must be installed and maintained in a...

Страница 2: ...nk is comprised of two link halves that are joined together with a thin layer of solder When the rated temperature is reached the solder melts and the two link halves separate This leads to the water...

Страница 3: ...o cover a particular space The sprinkler must be secured in place by firmly fastening the sprinkler system piping to the structure If the sprinkler is not properly secured in position reaction forces...

Страница 4: ...ture Rating 162 F 72 C Intermediate Temperature Rating 175 F 79 C Intermediate Temperature Rating 205 F 96 C Maximum Coverage Area a Ft Ft m m Maximum Spacing Ft m Flow b GPM LPM Pressure b PSI bar Fl...

Страница 5: ...djustment of the D1 or D3 Recessed Escutcheon Re adjust the sprinkler fitting to correct the position Installing Procedure Install Model FR RES sprinklers by the steps and figures shown below Use only...

Страница 6: ...e 6 of 8 Document No U087143 Date Oct 18 2019 FIGURE 4 INSTALLATION CORRECT and INCORRECT FIGURE 5 INSTALLATION WRENCH and SOCKET A 1 2 drive ratchet not included is required for use with the Socket F...

Страница 7: ...on for maintenance of the fire protection system permission to close the main control valve must be obtained from the proper authorities and all affected parties by this action and must be informed be...

Страница 8: ...pection and testing of its compliance with this document as well as the standards of the National Fire Protection Association e g NFPA 25 and the regulations of any other authorities having jurisdicti...

Отзывы: