Document  No.U087143

     

Date

Oct/18/2019 

SENJU SPRINKLER CO., LTD. 

Residential, Pendent and Recessed Pendent Sprinkler

 

Model FR-RES    K-Factor: 4.9    SIN: SS4451 

 

 

 

 

GENERAL DESCRIPTION 

 

The Model FR-RES Residential Pendent and Recessed Pendent Sprinklers are fusible link type automatic sprinklers. They are 
durable and fast responding. The Model FR-RES is designed for residential occupancies and is perfect for use in homes, hotels 
and other living quarters. 

The  Model  FR-RES  is  to  be  used  in  wet  pipe  residential  sprinkler  systems  for  One-  and  Two-  Family  Dwellings  and 
Manufactured Homes per NFPA 13D; wet pipe residential sprinkler systems for Residential Occupancies up to and Including 
Four Stories in Height per NFPA 13R; or, wet pipe sprinkler systems for the residential portions of any occupancies per NFPA 
13. 

The Model FR-RES has a 4.9 (70.6 LPM/bar

1/2

) K-factor that meets the required residential flow rates with minimal residual 

pressure, which allows for smaller pipe sizes and water supply requirements. 
For  extended  installation  flexibility,  the  Model  FR-RES  provides  1/2  inch  (12.7mm)  vertical  adjustment  with  the  D1  or  D3 
Recessed Escutcheon.   

 

NOTICE 

The heat sensitivity and water distribution design of Model FR-RES allows for an increased chance of residents to 
escape  or evacuate in case  of a fire.  However, residential fire sprinkler systems are  not a substitute  for fire safety 
awareness or fire safety construction required by building codes. 

 

WARNINGS 

The  Model  FR-RES  must  be  installed  and  maintained  in  accordance  with  the  rules  stated  herein  as  well  as  in 
compliance with the applicable standards of the National Fire Protection Association regulations and the standards of 
any other authorities having jurisdiction. 
In the event of this condition, consult the authorities having jurisdiction for guidance and approval. 
Failure to do so may impair the integrity of these devices. 
It  is  the  responsibility  of  the  installing  contractor  to  provide  a  copy  of  this  document  to  the  owner  or  their 
representative, and in turn, it is the obligation of the owner to provide a copy of this document to a succeeding owner. 
The owner is responsible for maintaining their fire protection system and devices in proper operating condition. The 
installing contractor or sprinkler manufacturer should be contacted with any related questions. 

 
 

TECHNICAL DATA 

 

Approvals:

 c

UL

us

 Listed 

Sprinkler Identification Number (SIN): SS4451

 

Maximum Working Pressure: 175psi (12.1bar) 
Discharge Coefficient (Nominal K-Factor): K=4.9 GPM/psi

1/2

 (70.6 LPM/bar

1/2

Temperature Rating: 162°F (72°C), 175°F (79°C),

 

205°F (96°C) 

Color Code 

162°F (72°C): Uncolored 
175°F (79°C): White 
205°F (96°C): White 

Vertical Adjustment: 1/2” (12.7mm) 
Finishes 

Sprinkler: Natural Brass, White Painted, Black Painted, Chrome Plated 
Recessed Escutcheon: Brass Plated, White Painted, Black Painted, Chrome Plated 

 

Содержание FR-RES

Страница 1: ...residential fire sprinkler systems are not a substitute for fire safety awareness or fire safety construction required by building codes WARNINGS The Model FR RES must be installed and maintained in a...

Страница 2: ...nk is comprised of two link halves that are joined together with a thin layer of solder When the rated temperature is reached the solder melts and the two link halves separate This leads to the water...

Страница 3: ...o cover a particular space The sprinkler must be secured in place by firmly fastening the sprinkler system piping to the structure If the sprinkler is not properly secured in position reaction forces...

Страница 4: ...ture Rating 162 F 72 C Intermediate Temperature Rating 175 F 79 C Intermediate Temperature Rating 205 F 96 C Maximum Coverage Area a Ft Ft m m Maximum Spacing Ft m Flow b GPM LPM Pressure b PSI bar Fl...

Страница 5: ...djustment of the D1 or D3 Recessed Escutcheon Re adjust the sprinkler fitting to correct the position Installing Procedure Install Model FR RES sprinklers by the steps and figures shown below Use only...

Страница 6: ...e 6 of 8 Document No U087143 Date Oct 18 2019 FIGURE 4 INSTALLATION CORRECT and INCORRECT FIGURE 5 INSTALLATION WRENCH and SOCKET A 1 2 drive ratchet not included is required for use with the Socket F...

Страница 7: ...on for maintenance of the fire protection system permission to close the main control valve must be obtained from the proper authorities and all affected parties by this action and must be informed be...

Страница 8: ...pection and testing of its compliance with this document as well as the standards of the National Fire Protection Association e g NFPA 25 and the regulations of any other authorities having jurisdicti...

Отзывы: