USER MANUAL
–
Z-GPRS3, Z-UMTS, Z-LOGGER3, Z-LTE-WW
16
When the logger is activated the RTU save data into an internal Flash, then send it to email server, ftp server,
http server or save them on MicroSD card.
When the internal Flash space is full the oldest data will be overwritten (circular buffer).
The files are in standard csv text format (w
indows excel ™ compatible).
There are 3 types of logs:
The Event Logger
,
The Data logger and the Data logger on Trigger
The internal flash stores at maximum of 8192 rows for the Event Logger, a new row will overwrite the oldest
(circular buffer).
The number of rows that the Data Logger can store in the internal flash depends from the TAGs size (16, 32 or
64 bits) and the number of tags.
Activating all the embedded tags the maximum number of rows that can be stored in the internal flash is 16384,
a new row will overwrite the oldest (circular buffer).
Activating all the embedded tags and all 100 Extended Tags at 32bit the maximum number of rows that can be
stored in the internal flash is 16384/8=2048, a new row will overwrite the oldest (circular buffer).
8.1.
THE EVENT LOGGER
The event logger works defining Events (Digital input/output Events, Blackout, Analog Alarms etc…)
with the
SEAL software configuration.
When an event is created a new row text (with the Timestamp) is inserted into the log, the event choosen must
be configured with the SEAL software.
The event logger can be sent a minimum of 1 time for day if files are sent to FTP, E-MAIL or microSD card.
NOTE:
If no events are generated, the Event logger file will be composed of only 1 row with the text :
INDEX
LEVEL
TIMESTAMP
SOURCE
MESSAGE
140
INFO
06/06/2016 00:00
SYS
OK: No Messages