NOTE
If the command is not recognized by the RTU, an error SMS will be sent:
“COMMAND NOT RECOGNIZED”
You can configure the RTU to send a confirmation (SMS or ring) when the command is successfully
completed.
CAUTION!
When a command is successfully completed, a ring can only be generated when a voice SIM is used
(data SIM do not permit voice call service).
21.
EMERGENCY MODE
I
t’s possible to disable the SEAL program ex
ecution setting ALL dip switches to ON at boot-up.
This emergency mode is useful if a SEAL program does not allow to connect to SEAL (for example because the
board will reboot continuously).
In emergency mode the SEAL program is not executed and the datalogger is stopped.
To enter in the emergency mode please follow these steps:
1)
Power Down Board
2)
Put ALL the dip switches to “ON”
3)
Power ON Board
4)
PWR led will flash until you exit from the emergency mode
5)
Now you can connect to SEAL and send a new program
For exit from the emergency mode:
1)
Power Down Board
2)
Put A
LL the dip switches to “OFF”
3)
Power ON Board
4)
Now the SEAL program is in execution