USER MANUAL
–
Z-GPRS3, Z-UMTS, Z-LOGGER3, Z-LTE-WW
38
41003
…
41203
1002
…
1202
External
Variables Tags
-
READ/WRITE
Use the compile output window
for Tags address position
49001
9000
COMMAND
UNSIGNED 16
BITS
READ/WRITE
Command Register
(see Table with supported
commands)
17.2.
MODBUS ADDRESSES TABLE (Z-UMTS HW2 from firmware 3.0.3/Z-LTE/Z-LTE-WW)
ADDRRESS OFFSET
TAG
REGISTER TYPE
RO/RW
INFO
40001
0
MACHINE ID
UNSIGNED 16
READ ONLY
INTERNAL CODE
40002
1
FIRMWARE CODE
UNSIGNED 16
READ ONLY
INTERNAL CODE
40003
2
FIRMWARE MAJOR
REVISION
UNSIGNED 16
READ ONLY
(EXAMPLE 204 = 2.04)
40004
3
FIRMWARE MINOR
REVISION
UNSIGNED 16
READ ONLY
In decimal format
KMMBB
Where:
K=4= Bugfix Release
K=3= New Release
MM = Minor Revision
BB = Build
Example:
Value = 40110
4 = Bugfix Release
01 = Minor revision 1
10 = Build 10
40008
7
DIGITAL INPUTS
AND SIGNALS
BIT
READ ONLY
Digital Inputs
Bit 0 = INPUT1 VALUE
Bit 1 = INPUT2 VALUE
Bit 2 = INPUT3 VALUE
Bit 3 = INPUT4 VALUE
Bit 7 = EXTERNAL POWER
Bit 8 = BATTERY GOOD
40009
8
DIGITAL OUTPUTS
BIT
READ ONLY
Bit 14 = DIGITAL OUTPUT 1
VALUE
Bit 15 = DIGITAL OUTPUT 2
VALUE
40015
14
CLOCK YEAR
SIGNED 16 BITS
READ ONLY
Year
40016
15
CLOCK MONTH
UNSIGNED 8 BITS
READ ONLY
Bit from 0 to 7 (LSB)
40017
16
CLOCK DAY
UNSIGNED 8 BITS
READ ONLY
Bit from 0 to 7 (LSB)
40017
16
CLOCK HOURS
UNSIGNED 8 BITS
READ ONLY
Bit from 8 to 15 (MSB)
40018
17
CLOCK MINUTES
UNSIGNED 8 BITS
READ ONLY
Bit from 0 to 7 (LSB)
40018
17
CLOCK SECONDS
UNSIGNED 8 BITS
READ ONLY
Bit from 8 to 15 (MSB)
40023
22
Totalizer value 1 LSW
UNSIGNED 16
BITS
READ ONLY
Less significant 16 bits
40024
23
Totalizer value 1
MSW
UNSIGNED 16
BITS
READ ONLY
Most significant 16 bits