Removal from the rail DIN IEC EN 60715
As illustrated in Pic. 1b:
1) Move outwards the two hooks at the side
of the module by levering with a screwdriver.
2) Remove the module from the rail.
Insert in the rail DIN IEC EN 60715
1) Move outwards the two hooks on the rear
side of the module as shown in
. 1b.
Pic
2) Insert the module by aligning the IDC 10
back connector to the female connector on
the Seneca DIN IEC EN 60715 rail support.
3) To secure the module on the rail support
you must tighten the two hooks on the ends
of the IDC10 rear connector, as shown in Pic.
1a.
Pic. 1a
Z-4RTD
2
FAIL
x
x
x
RX
TX
USB
Y
PWR
x
13 14 15 16
1 2 3 4
5 6 7 8
9 10 11 12
Z-4
RT
D2
-1
4 R
TD
Inputs
1.5kV Isolated Module
M
AD
E
IN
ITA
LY
For maximum performance we recommend the use of special shielded cables, such as
the BELDEN 9841.
Installation rules
The module is designed to be installed in vertical position on a
In
rail DIN IEC EN 60715.
order to ensure optimum performance and the longest working life, the module(s) must be
supplied with adequate ventilation and no raceways or other objects must obstruct the
ventilation slots Never install modules above sources of heat; we recommend installation in
.
the lower part of the control panel
.
Bus
Length
Derivation
Length
Baud
rate
1200 m
2 m
115 kbps
Module2
Module1
Module3
Module4
Module5
Bus length
Ld = Derivation length
Ld
Terminator
Terminator
Connection rules for ModBUS
1) Install modules in the DIN rail
2) Connect the remote modules using cables of proper length.
The following table shows the data for length of cables:
-Bus length: maximum length of the MODBUS network. This is the
length of the
total
cables that connect the two modules on which the bus termination has been inserted.
-Derivation Length: maximum length of a derivation.