Digital converter with four measuring channels , for platinum or nickel thermistors, which
are independent and isolated from each other.

Ÿ

1.5 kV

insulation between the inputs, the power supply and serial communication line.

A

Ÿ

Easy and fast wiring of power supply and serial communications by means of Seneca
bus for DIN rail IEC EN 60715.

Ÿ

Communication parameters can be configured by DIP-switch or through USB port from
PC or Android device.

Ÿ

1 RS485 serial communication port with MODBUS-RTU protocol, 32 nodes maximum.

Ÿ

Inputs protected against ESD.

Ÿ

High acquisition speed and possible r calibration on the field.

e

Ÿ

Measurement of thermistors: PT100, PT500, PT1000, NI100, with 4, 3 or 2 wires
wiring.

Ÿ

Measurement of temperature or resistance.

Ÿ

Eight level filter programmable in order to stabilise reading.

Ÿ

50 Hz or 60 Hz programmable frequency rejection filter.

Ÿ

The measurement available: floating point, reverse floating-point, fixed point at 16 bits,
tenths of degrees with sign for temperature, and tenths of Ohms or hundreds of Ohms
for resistance.

Ÿ

Three selectable acquisition speeds (two with 13 bit resolution, one with 14 bit resolution).

Ÿ

Programmable value in case of fault or freezing of last reading.

Ÿ

Compensation of three wire resistor on the average value of the connection resistor.

Technical Specifications

Input

PT100 - EN 60751/A2 (ITS-90)

Input

PT500 - EN 60751/A2 (ITS-90)

Measuring range:

-200 – +650 °C

Measuring range:

-200 – +750 °C

Resistance range:

18.5 Ω – 330 Ω

Resistance range:

92.5 Ω – 1800 Ω

Fault signalling:

Rx <18 Ω, Rx >341 Ω

Fault signalling:

Rx < 90 Ω, Rx > 1851 Ω

Current on sensor:

875 A nominal

m

Current on sensor:

333 A nominal

m

Resistance of cables:

20 Ω maximum per wire

Resistance of cables:

30 Ω maximum per wire

Input

PT1000 - EN 60751/A2 (ITS-90)

Input

NI100

Measuring range:

-200 – +210 °C

Measuring range:

-60 – +250 °C

Resistance range:

185 Ω – 1800 Ω

Resistance range:

69 Ω – 295 Ω

Fault signalling:

Rx <180 Ω, Rx >1851 Ω Fault signalling:

Rx <60 Ω, Rx >301 Ω

Current on sensor:

333 A nominal

m

Current on sensor:

875 A nominal

m

Resistance of cables:

30 Ω maximum per wire

Resistance of cables:

30 Ω maximum per wire

Rear IDC10 connector (port RS485)

Front Micro USB

1200 – 115200 Baud.

2400 Baud, Address 01, Parity NO, Stop bit 1,
Delay on the answer NO, Time Out 3 s

Protocol

Modbus-RTU

Protocol

Modbus-RTU

MI00441

-3

-E

N

Содержание Z-4RTD2

Страница 1: ... duplication and reproduction are forbidden The content of the present documentation refers to products and technologies described herein Such data can be modified and supplemented for technical and orcommercialreasons SENECA s r l Via Austria 26 35127 PADOVA ITALY Tel 39 049 8705355 8705359 Fax 39 049 8706287 Configuration software and manuals on our site www seneca it Technical support support s...

Страница 2: ...hms for resistance Three selectable acquisition speeds two with 13 bit resolution one with 14 bit resolution Programmable value in case of fault or freezing of last reading Compensationofthreewireresistorontheaveragevalueoftheconnectionresistor Technical Specifications Input PT100 EN 60751 A2 ITS 90 Input PT500 EN 60751 A2 ITS 90 Measuring range 200 650 C Measuring range 200 750 C Resistance range...

Страница 3: ... a s l Storage temperature 20 85 C Protection index IP20 Connections Removable 4 way screw terminals max 1 5 mm 3 5 mm pitch 2 Rear IDC10 connector for DIN rail IEC EN 60715 Micro USB on the front Overall dimensions Box Dimensions and weight W 17 5 mm H 102 5 mm D 112 mm 120g Box PA6 black Insulations Standards The instrument complies with the following standards EN61000 6 4 electromagnetic emissi...

Страница 4: ...maximum performance we recommend the use of special shielded cables such as the BELDEN 9841 Installation rules The module is designed to be installed in vertical position on a In rail DIN IEC EN 60715 order to ensure optimum performance and the longest working life the module s must be supplied with adequate ventilation and no raceways or other objects must obstruct the ventilation slots Never ins...

Страница 5: ...ances 10 m between module and probe Remember that this connection introduces a measurement error equal to the resistance of the connection cables 3 WIRES A connection to be used for medium distances 10 m between module and probe The instrument compensates the connection of the resistance cables To ensure correct compensation the cables must have the same resistance 4 WIRES A connection to be used ...

Страница 6: ...ase the noise rejection from the mains power line and to reduce measuring noise Filter IIR exponential with programmable time constant able to dampen fluctuations If an input variation is higher than threshold then both filters are forced to quickly adapt to T the new value stabilising it only later on The filter is set with the three least significant bits of registers MODBUS 40037 40 refer to se...

Страница 7: ...neca it prodotti z 4rtd2 CU A MICRO OTG CU A MICROB Connection with micro USB port for configuration via APP Connection with micro USB port for configuration via PC CU A MICROB PC Z 4RTD2 FAIL RX TX USB PWR 1314 15 16 1 2 3 4 5 6 7 8 9 10 1112 Factory Configuration Configuration of the default parameters in the module The instrument is configured at the factory with all the DIP switch in position ...

Страница 8: ...ycling of materials will help to conserve natural resources For more detailed information about the recycling of this product please contact your local city office wastedisposalserviceorthèretailstorewhereyoupurchasedthisproduct Front LED indications LED STATUS Description PWR Green On The device is powered correctly FAIL Yellow On Fault Low supply faulty channel faulty sensor internal communicati...

Отзывы: