background image

MI00551-8-EN

INSTALLATION MANUAL

6/8

ELECTRICAL CONNECTIONS

The installation of this appliance must only be carried out by qualified personnel.

Check that the device plate data (measurement voltage, auxiliary power supply voltage, measurement current, frequency) 

match the actual data of the network to which the instrument is connected. In the wiring, strictly observe the insertion 

diagram; inaccuracy in the connections inevitably causes false measurements or damage to the instrument.

Once the instrument is connected, complete the installation with the device configuration.

Grounding of the TA sensors is possible with negative cable connection.

 

Current measurement is only possible using current transformers.

It is advisable to insert a delayed 1 A fuse as shown in the diagrams below.

CAUTION

CONNECTIONS FOR ROGOWSKI SENSORS

CONNECTIONS FOR CURRENT OUTPUT TA

SINGLE-PHASE (with load division)

THREE-PHASE: 4 wires

THREE-PHASE: 3 wires

SINGLE-PHASE (with load division)

THREE-PHASE: 4 wires

THREE-PHASE: 3 wires

43  44  45  46 47  48  49  50  51  52  53  54  55

+U  +I    - +U  +I    - +U  +I    -

N  L3  L2  L1

N

L1

L2

L3

Volt. Input

S1/k

S1/k

S1/k

P1/k

P1/k

P1/k

43  44  45  46 47  48  49  50  51  52  53  54  55

+U  +I    - +U  +I    - +U  +I    -

N  L3  L2  L1

N

L1

L2

L3

Volt. Input

43  44  45  46 47  48  49  50  51  52  53  54  55

+U  +I    - +U  +I    - +U  +I    -

N  L3  L2  L1

Volt. Input

N

L2

L3

L1

43  44  45  46 47  48  49  50  51  52  53  54  55

+U  +I    - +U  +I    - +U  +I    -

N  L3  L2  L1

Volt. Input

N

L2

L3

L1

S1/k

S1/k

S1/k

P1/k

P1/k

P1/k

43  44  45  46 47  48  49  50  51  52  53  54  55

+U  +I    - +U  +I    - +U  +I    -

N  L3  L2  L1

L1

L2

L3

Volt. Input

43  44  45  46 47  48  49  50  51  52  53  54  55

+U  +I    - +U  +I    - +U  +I    -

N  L3  L2  L1

L1

L2

L3

Volt. Input

S1/k

S1/k

S1/k

P1/k

P1/k

P1/k

CAUTION

Rogowski sensor inputs are inverted.

Please refer to the Rogowski sensor manual for electrical 

connections.

Содержание R203

Страница 1: ...Take appropriate measures during any operation PRELIMINARY WARNINGS The word WARNING preceded by the symbol indicates conditions or actions that put the user s safety at risk The word ATTENTION preceded by the symbol indicates conditions or actions that might damage the instrument or the connected equipment The warranty shall become null and void in the event of improper use or tampering with the ...

Страница 2: ...ed DATA LOGGER Flashing Data Logger function enabled ON Data Logger function disabled STS Status On Set IP address powered module Flashing Waiting for the IP address from the DHCP powered module WIRING ERROR Flashing Wiring error Off Correct wiring RX On RS485 connection anomaly Flashing Reception of data packet completed on RS485 TX Flashing Transmission of data packet completed on RS485 ETH TRF ...

Страница 3: ... manual for the error limits ROGOWSKI ANALOGUE INPUT Class base prec Network frequency 50 60 Hz Voltmeter 0 5 Ammeter 0 5 wattmeter 1 Rogowski supplied by Seneca 100 mV correspond to 1000 A 50 Hz sinusoidal 120 mV correspond to 1000 A 60 Hz sinusoidal Maximum measurable current 3 kA 50 Hz 2 5 kA 60 Hz Precision after calibration 1 see chapter Rogowski sensor Linearity 0 2 Accuracy is guaranteed in...

Страница 4: ...a correct measurement calibrate the Rogowski sensor by writing the calibration coefficient in the corresponding Modbus register see the user manual Example if the sensor is supplied with a characteristic of 90 mV 1000 A on the calibration register corresponding to the phase in which the Rogowski sensor is applied the value to be set is 1000 90 10 NOTE ON ACCURACY The product has a nominal accuracy...

Страница 5: ... 0 20 mA For the electrical connections screened cables are recommended There is no isolation between RS485 and retransmitted output It is necessary to program the outputs to use them correctly Voltage Applied current Supply current external DIGITAL OUTPUT The device has two digital outputs Capacity Imax 50 mA Vmax 28V See the user manual for the functions Reversible polarity V 10 11 12 A 10 11 12...

Страница 6: ... shown in the diagrams below CAUTION CONNECTIONS FOR ROGOWSKI SENSORS CONNECTIONS FOR CURRENT OUTPUT TA SINGLE PHASE with load division THREE PHASE 4 wires THREE PHASE 3 wires SINGLE PHASE with load division THREE PHASE 4 wires THREE PHASE 3 wires 43 44 45 46 47 48 49 50 51 52 53 54 55 U I U I U I N L3 L2 L1 N L1 L2 L3 Volt Input S1 k S1 k S1 k P1 k P1 k P1 k 43 44 45 46 47 48 49 50 51 52 53 54 55...

Страница 7: ...Y IP ADDRESS The default module IP address is static 192 168 90 101 WEB SERVER To access the maintenance Web Server with the factory IP address above use the following credentials Account User admin Password admin Password Admin admin L1 N 43 46 N L1 44 45 46 L1 L2 L3 L3 L2 L1 L1 L2 L3 N L3 L2 L1 43 44 45 46 43 44 45 46 47 48 49 50 51 52 53 54 55 U I U I U I N L3 L2 L1 N L1 L2 L3 Volt Input S1 k S...

Страница 8: ...he incorrect connections The LAN fault bypass function allows you to keep the connection between the two Ethernet ports of the device ON in the event of a power failure If a device turns off the chain is not interrupted and the devices downstream of the switched off one will still be accessible This function has a limited duration the connection remains active for a few days typically 4 The fault ...

Отзывы: