MI00551-8-EN
INSTALLATION MANUAL
6/8
ELECTRICAL CONNECTIONS
The installation of this appliance must only be carried out by qualified personnel.
Check that the device plate data (measurement voltage, auxiliary power supply voltage, measurement current, frequency)
match the actual data of the network to which the instrument is connected. In the wiring, strictly observe the insertion
diagram; inaccuracy in the connections inevitably causes false measurements or damage to the instrument.
Once the instrument is connected, complete the installation with the device configuration.
Grounding of the TA sensors is possible with negative cable connection.
Current measurement is only possible using current transformers.
It is advisable to insert a delayed 1 A fuse as shown in the diagrams below.
CAUTION
CONNECTIONS FOR ROGOWSKI SENSORS
CONNECTIONS FOR CURRENT OUTPUT TA
SINGLE-PHASE (with load division)
THREE-PHASE: 4 wires
THREE-PHASE: 3 wires
SINGLE-PHASE (with load division)
THREE-PHASE: 4 wires
THREE-PHASE: 3 wires
43 44 45 46 47 48 49 50 51 52 53 54 55
+U +I - +U +I - +U +I -
N L3 L2 L1
N
L1
L2
L3
Volt. Input
S1/k
S1/k
S1/k
P1/k
P1/k
P1/k
43 44 45 46 47 48 49 50 51 52 53 54 55
+U +I - +U +I - +U +I -
N L3 L2 L1
N
L1
L2
L3
Volt. Input
43 44 45 46 47 48 49 50 51 52 53 54 55
+U +I - +U +I - +U +I -
N L3 L2 L1
Volt. Input
N
L2
L3
L1
43 44 45 46 47 48 49 50 51 52 53 54 55
+U +I - +U +I - +U +I -
N L3 L2 L1
Volt. Input
N
L2
L3
L1
S1/k
S1/k
S1/k
P1/k
P1/k
P1/k
43 44 45 46 47 48 49 50 51 52 53 54 55
+U +I - +U +I - +U +I -
N L3 L2 L1
L1
L2
L3
Volt. Input
43 44 45 46 47 48 49 50 51 52 53 54 55
+U +I - +U +I - +U +I -
N L3 L2 L1
L1
L2
L3
Volt. Input
S1/k
S1/k
S1/k
P1/k
P1/k
P1/k
CAUTION
Rogowski sensor inputs are inverted.
Please refer to the Rogowski sensor manual for electrical
connections.