35
Symptom
6:
Space
heating
capacity
shortage
at
low
outdoor
temperatures
Possible
causes
Corrective
action
Backup
heater
operation
is
not
activated.
Check
the
backup
heater
is
turned
‘on’.
Check
whether
or
not
the
thermal
protector
of
the
backup
heater
has
been
activated.
Check
whether
or
not
the
thermal
fuse
of
the
backup
heater
is
blown.
Too
much
heat
pump
capacity
is
used
for
heating
domestic
hot
water
(applies
only
to
installations
with
a
domestic
hot
water
tank).
Check
that
the
'space
heating
priority
temperature'
field
settings
are
configured
appropriately:
•
Make
sure
that
the
space
heating
priority
is
enabled
Error
codes
When
a
safety
device
is
activated,
the
user
interface
LED
will
be
flashing,
and
an
error
code
will
be
displayed.
A
list
of
all
errors
can
be
found
in
the
table
below.
Code
Failure
cause
E0
HE
outlet
sensor
failure
E1
Water
tank
temp
sensor
failure
E2
HE
inlet
sensor
failure
E3
Water
outlet
sensor
failure
E4
Outdoor
heat
exchanger
sensor
failure
E5
Outdoor
ambient
temp
sensor
failure
E6
TH
temp
sensor
failure
E7
TL
temp
sensor
failure
E8
Indoor
ambient
temp
sensor
failure
E9
T2
temp
sensor
failure
Ea
Communication
failure
between
indoor
and
controller
Eb
Communication
failure
between
indoor
and
outdoor
Ec
Indoor
EEPROM
failure
Ed
Controller
clock
IC
failure
EE
Controller
EEPROM
failure
P0
High
pressure
protection
P1
Low
pressure
protection
P2
Wrong
phase
sequence
protection
P3
Absence
phases
protection
P4
Water
flow
switch
failure
P5
Plate
heat
exchanger
too
low
temp.
protection
**
After
E
failure,
renew
the
safety
by
turning
the
unit
‘OFF’
and
back
‘ON’.
And
P
failure
will
renew
automatically
if
the
failure
is
eliminated.
***
In
case
this
procedure
for
resetting
the
safety
is
not
successful,
contact
your
local
dealer.
Содержание TERCAX-110
Страница 7: ...Luxury Air Source Heat Pump Monobloc System 6 Model AXAO 11HA...
Страница 8: ...Luxury Air Source Heat Pump Monobloc System 7 Model AXAO 14HA and AXAO 16HA 3...
Страница 12: ...Luxury Air Source Heat Pump Monobloc System 11 OVERVIEW OF THE UNIT External view AXAO 06HA and AXAO 08HA...
Страница 14: ...Luxury Air Source Heat Pump Monobloc System 13 External view AXAO 11HA...
Страница 16: ...Luxury Air Source Heat Pump Monobloc System 15 External view AXAO 14HA and AXAO 16HA 3...
Страница 20: ...Luxury Air Source Heat Pump Monobloc System 19 Model AXAO 11HA Refer to the attached wiring diagram in the unit...
Страница 21: ...Luxury Air Source Heat Pump Monobloc System 20 Model AXAO 14HA Refer to the attached wiring diagram in the unit...