Symptom
2:
The
unit
is
turned
‘on’
but
the
compressor
is
not
starting
(space
heating
or
domestic
water
heating)
Possible
causes
Corrective
action
The
unit
must
start
up
out
of
its
operation
range
(the
water
temperature
is
too
low).
In
case
of
a
low
water
temperature,
the
system
utilizes
the
backup
heater
to
reach
the
minimum
water
temperature
first.
•
Check
that
the
backup
heater
power
supply
is
correct
•
Check
that
the
backup
heater
thermal
fuse
is
closed.
•
Check
that
the
backup
heater
thermal
protector
is
not
activated.
•
Check
that
the
backup
heater
contactors
are
not
broken.
Symptom
3:
Pump
is
making
noise
(cavitation)
Possible
causes
Corrective
action
There
is
air
in
the
system.
Purge
air.
Water
pressure
at
pump
inlet
is
too
low.
•
Check
on
the
manometer
that
there
is
sufficient
water
pressure.
The
water
pressure
must
be
>0.3
bar
(water
is
cold),
>>0.3
bar
(water
is
hot).
•
Check
that
the
manometer
is
not
broken.
•
Check
that
the
expansion
vessel
is
not
broken.
•
Check
that
the
setting
of
the
pre
‐
pressure
of
the
expansion
vessel
is
correct
(refer
to:
"Setting
the
pre
‐
pressure
of
the
expansion
vessel").
Symptom
4:
The
water
pressure
relief
valve
opens
Possible
causes
Corrective
action
The
expansion
vessel
is
broken.
Replace
the
expansion
vessel.
The
water
volume
in
the
installation
is
too
high.
Make
sure
that
the
water
volume
in
the
installation
is
under
the
maximum
allowed
value
(refer
to:
"Checking
the
water
volume
and
expansion
vessel
pre
‐
pressure").
Symptom
5:
The
water
pressure
relief
valve
leaks
Possible
causes
Corrective
action
Dirt
is
blocking
the
water
pressure
relief
valve
outlet.
Check
for
correct
operation
of
the
pressure
relief
valve
by
turning
the
red
knob
on
the
valve
counter
clockwise:
•
If
you
do
not
hear
a
clacking
sound,
contact
your
local
dealer.
•
In
case
the
water
keeps
running
out
of
the
unit,
close
both
the
water
inlet
and
outlet
shut
‐
off
valves
first
and
then
contact
your
local
dealer.
Содержание TERCAX-110
Страница 7: ...Luxury Air Source Heat Pump Monobloc System 6 Model AXAO 11HA...
Страница 8: ...Luxury Air Source Heat Pump Monobloc System 7 Model AXAO 14HA and AXAO 16HA 3...
Страница 12: ...Luxury Air Source Heat Pump Monobloc System 11 OVERVIEW OF THE UNIT External view AXAO 06HA and AXAO 08HA...
Страница 14: ...Luxury Air Source Heat Pump Monobloc System 13 External view AXAO 11HA...
Страница 16: ...Luxury Air Source Heat Pump Monobloc System 15 External view AXAO 14HA and AXAO 16HA 3...
Страница 20: ...Luxury Air Source Heat Pump Monobloc System 19 Model AXAO 11HA Refer to the attached wiring diagram in the unit...
Страница 21: ...Luxury Air Source Heat Pump Monobloc System 20 Model AXAO 14HA Refer to the attached wiring diagram in the unit...