SmartBox® 1 / SmartBox® 2 / SmartBox® 3
Part no. 28 100 57 d
11 / 16
13.Rounding
Automatically
Without
rounding
2 (0,02…200)
5 (0,05…500)
10 (0,1…1000)
20 (0,2…2000)
50 (0,5…5000)
100 (1…10000)
Default settings
minimal increments
Rounding increments in relation to the set volume
set with +/- keys
14.
–
17.Exit
Back to display mode
18.Language
Language:
German, English, French
+ / - / Enter
Names:
ESC
+ / - / Enter
Name Tank 1: Suggested name
Letters can be changed with
+ / - / Enter
19.Exit
Back to display mode
20.LCD
display
Contrast: 24
Set the contrast of the LCD display
21.Device
info
Displays information about
Software version: V4.00 (e. g.)
Serial number: Tank 1: SN=1234 (e. g.)
Gain: X0 = 4.05 mA; B = 1268 (Tank 1)
22.Test
current
Test function for the current mA value of the
measurement probe:
ADC = 28A0 = 04.00 mA
If level probe is not submerged, the value should
be close to 4 mA. Tolerance range is 3.7...4.3
mA. For larger deviations, see menu item 9.
23.Test
Relay
SBox 2+3
Rel1 ON / OFF
Relay test
24.Reset
ESC
Reset the device software:
Exit this function without executing it.
Restart
Initialisation. The device software restarts and
keeps all device settings.
Factory
settings
Complete reset of all parameters to the original
delivery status.
26.Exit
Back to display mode