SERVICE | Apendix A
Doc #OI0003 Part #004122 Rev 04 2010
|
123
Product Specifications
Note: Selectronic reserve the right to change specifications without notice.
All ratings are at 40°C and nominal battery voltage unless otherwise stated. The product is
specified to a maximum altitude of 2000 metres.
SP PRO SERIES SPECIFICATIONS
SPMC 240–AU
SPMC 241–AU
SPMC 481–AU
SPMC 482–AU
SPMC 1201–AU
SPLC 1201-AU
Nominal battery voltage
24 V
24 V
48 V
48 V
120V
120V
Continuous, output power
Continuous, charge current
@ 25°C
2,800 W
105 A
4,000 W
146 A
4,500 W
83 A
7,000 W
125 A
7,000 W
50 A
18,000 W
125 A
Continious grid export power
rated output
20 second load rating
20 second output current
@ 40°C
7,500 W
28 A
10,500 W
40 A
12,000 W
47 A
18,000 W
70 A
18,000 W
70 A
30,000 W
125 A
1 minute output power
@ 40°C
5,400 W
7,600 W
8,700 W
13,000 W
13,000 W
25,000 W
60 minute output power
@ 40°C
3,200 W
4,700 W
5,300 W
8,000 W
8,000 W
19,000 W
DC input voltage range
20 - 34 V
20 - 34 V
40 - 68 V
40 - 68 V
100 - 170 V
100 - 170 V
TRANSFER SWITCH (Synchronous)
AC transfer current capacity
63 A
125 A
Max AC input source, (generator/grid)
15 kVA
30 kVA
Max total output to Load, AC inverter
15 kVA
30 kVA
AC transfer time
no-break
If grid fails
0 - 0.03 seconds
Battery charger type
Temperature compensated, 5 stage, power factor corrected with dual stage float
EFFICIENCy
DC consumption idle
6 W
DC consumption standby (Econo Mode)
12 - 20 W
n/a
ON with no load
31 W
36 W
37 W
40 W
38 W
75 W
Peak efficiency – all modes
95%
95%
95.5%
96%
96.5%
96%
10% load
90%
90.5%
91%
91%
91.5%
91%
20% load
92.5%
93%
94%
94%
94%
94%
50% load
94%
94.5%
95%
95.5%
96%
95.5%
100% load
90%
91%
92.5%
93%
93.5%
93%
AC OUTPUT (standalone)
Range
210 to 240 V+/- 0.5%
Regulation
<1% droop 0-100% rated load (<2% @ 150%, <5% @200%)
THD
<3% @ 0-200% rated load
Frequency
50 or 60 Hz +/-0.005% standalone
AC SOURCE (input)
Nominal voltage
240 V~
AC current (Recharge, Bypass & Normal modes)
63 A
125 A
Tolerance on nominal voltage
installer programmable 204 to 264 V~
Nominal input frequency
50/60 Hz
Tolerance on nominal frequency
installer progra/- 1% to 10%
Generator can be started by
battery SoC, DC voltage, battery load, unit temperature, time & remote control
FEATURES
Battery temperature sensor
Included
Mid point battery voltage sensing
Included
Inverter display
22 x LEDs with auto adjusting intensity.
Display indicates, charger status, remaining useable battery capacity, alarms, AC status.
AC status LEDs powered from AC voltage.
Generator control button. Output mode button. Alarm silence button.
Digital Inputs
4 off: Max 60 VDC ( Active > +6 V, Inactive < +3 V )
Shunt Inputs
2 off: +/-75 mV, adjustable 25 A to 500 A
Analogue Inputs
2 general purpose logged 0-60 V
n/a
Relay Outputs
4 off: 60 V, 500 mA
Digital outputs
3 off: 60 V, 5 mA
Communication ports
2 off RS232 with adjustable baud rate of up to 57600
Memory retention of settings & data
permanent
SP LINK configuration and monitoring software
Standard, allows configuration of parameters or customer can view LED display remotely.
Dimensions (mounted)
345 W x 545 H x 215 D
520 W x 870 H x
300 D
Weight
29 kg
34 kg
35 kg
40 kg
40 kg
105 kg
Circuit Breakers (AC Source, AC Load)
double pole 63 A
single pole 125 A
Standards
AS 62040.1.1-2003, CE pending
AS/NZS 61000-6-3 2007
AS/NZS 61000-6-4 2007
Grid Protection
AS 4777 2005
AS 4777 2005 pending
Protection
IP43
Warranty
5 to 7 years (country dependant)