ATSEL HMI User Manual
group, If recipe index is Modify Internal Register LW60803 can achieve recipe switch-
over of recipe group.
Numerical input and display address of recipe ingredients is using the internal recipe
register address. Such as the above recipe, there are 8 ingredients, the system internal
address is RWI0-RWI7 from top to bottom if connects corresponding PLC address just
needs to input the corresponding variables, such as VW0, VW2, VW4 etc. Recipe’s
uploading, downloading or saving can be achieved in the function button.
Data transmission
Function introduction
Data Transmission is used for the data exchange between external device and HMI
or between device and device.
Click Data Transmission in Project Manager to pop up the data transmission list as
below.
1. Click "Add", you can add data transmission. At present, maximum number entries is
100. Triggered type is interval trigger and minimum time unit is 200ms, the data types
which can be transfered is bit, word, double word, and the maximum transmission data
size by each trigger is 100(bit, word, double word)
a
)
Interval: 1~100
(
* 20ms
)
b
)
Address type: bit, word, double word
c
)
Address length: 1~100, the data size of each transmission, unit is the type chosen at
"address type"
d
)
Source address/ Destination address: the transmission direction is from source
address to destination address, this type of chosen register must be same as the address
set in "Address type".
2. After setting, click "confirm", add this set entry into the list.