SEL-351R Falcon Data Sheet

5

Figure 4

Recloser Contact Wear Curve and Settings

Fault Locator

The SEL-351R Falcon provides an accurate estimate of
fault location even during periods of substantial load
flow. The fault locator uses fault type, replica line imped-
ance settings, and fault conditions to develop an estimate
of fault location without communications channels, spe-

cial instrument transformers, or prefault information.
This feature contributes to efficient dispatch of line
crews and fast restoration of service. The fault locator
requires three-phase voltage inputs.

Automation

Flexible Control Logic 
and Integration

The SEL-351R Falcon has three independently operated
serial ports: two EIA-232 ports and one optional
EIA-485 port on the side. The recloser control does not
require special communications software. Use any
system that emulates a standard terminal system.
Establish communication by connecting computers,
modems, protocol converters, printers, the SEL-3530
RTAC, an SEL-2032, SEL-2030 or SEL-2020
Communications Processor, SCADA serial port, and/or
RTU for local or remote communication.

Apply an SEL-2032 as the hub of a star network, with a
point-to-point fiber or copper connection between the
hub and the SEL-351R Falcon, as in Figure 5. The
SEL-2032 supports external communications links,
including the public switched telephone network for
engineering access to dial-out alerts and private line
connections of the SCADA system.

Figure 5

Example Communication System

SEL manufactures a variety of standard cables for
connecting this and other IEDs to a variety of external
devices. Consult your SEL representative for more
information on cable availability.

(COSP1, KASP1)

(COSP3, KASP3)

(COSP2, KASP2)

kA Interrupted (kA Axis)

Close-t

o-Open (

C/

O Axis

)

ASCII Reports 
Plus Interleaved 
Binary Data

Dial-Up ASCII Link

DNP SCADA Link

I1

Z 0 1

I2

Z02

I3

Z03

IN

Z04

12 V

Z 1 7

RET

Z1 8

BAT+

Z 1 9

BAT-

Z20

BAT   3A

F01

Z 2 1

N/C

Z25

GND

Z26

H

Z22

N

Z23

Z24

V1

Z05

V2

Z06

V3

Z07

N

Z08

VS

Z09

NS

Z10

F

Z 1 1

E

Z 1 2

C

Z 1 3

B/D

Z1 4

A

Z 1 5

RET

Z1 6

196-1215

ENABLED

CONTROL

TRIP

CONTROL STATE

SELECT

CANCEL

LAMP

TEST

EXIT

METER

EVENTS

STATUS

OTHER

SET

CNTRL

GROUP

TARGET

RESET

GROUND

RECLOSE

ENABLED

ENABLED

ENABLED

REMOTE

SETTINGS

ALTERNATE

LOCK

(press for 3 sec)

AUX 1

AUX 2

 

 

WAKE UP

 

CLOSED

RECLOSER

OPEN

RECLOSER

TRIP

CLOSE

C

B

A

LOCKOUT

CYCLE

CURVE

FAST

TAG

HOT LINE

PROBLEM

BATTERY

SUPPLY

AC

CURRENT

HIGH

81

 

G

SEF

RESET

A01

A04

A03

A02

A07

A06

A05

A08

A 1 1

A1 0

A09

A1 4

A 1 3

A 1 2

A23

A1 6

A1 5

A 1 7

A1 8

A22

A20

A1 9

A21

A26

A25

A24

A28

A27

IRIG-B

SERIAL PORT 1

1

2

3

4

5

N/C

7

8

SERIAL PORT 2

SERIAL PORT 3

OUT102

OUT101

OUT104

OUT103

OUT107

N/C

N/C

IN101

ALARM

IN103

IN102

N/C

N/C

IN104

+

_

RECLOSER CONTROL

I1

Z 0 1

I2

Z02

I3

Z03

IN

Z04

12 V

Z 1 7

RET

Z1 8

BAT+

Z 1 9

BAT-

Z20

BAT   3A

F01

Z 2 1

N/C

Z25

GND

Z26

H

Z22

N

Z23

Z24

V1

Z05

V2

Z06

V3

Z07

N

Z08

VS

Z09

NS

Z10

F

Z 1 1

E

Z 1 2

C

Z 1 3

B/D

Z1 4

A

Z 1 5

RET

Z1 6

196-1215

ENABLED

CONTROL

TRIP

CONTROL STATE

SELECT

CANCEL

LAMP

TEST

EXIT

METER

EVENTS

STATUS

OTHER

SET

CNTRL

GROUP

TARGET

RESET

GROUND

RECLOSE

ENABLED

ENABLED

ENABLED

REMOTE

SETTINGS

ALTERNATE

LOCK

(press for 3 sec)

AUX 1

AUX 2

 

 

WAKE UP

 

CLOSED

RECLOSER

OPEN

RECLOSER

TRIP

CLOSE

C

B

A

LOCKOUT

CYCLE

CURVE

FAST

TAG

HOT LINE

PROBLEM

BATTERY

SUPPLY

AC

CURRENT

HIGH

81

 

G

SEF

RESET

A01

A04

A03

A02

A07

A06

A05

A08

A 1 1

A 1 0

A09

A 1 4

A 1 3

A 1 2

A23

A 1 6

A 1 5

A 1 7

A 1 8

A22

A20

A 1 9

A21

A26

A25

A24

A28

A27

IRIG-B

SERIAL PORT 1

1

2

3

4

5

N/C

7

8

SERIAL PORT 2

SERIAL PORT 3

OUT102

OUT101

OUT104

OUT103

OUT107

N/C

N/C

IN101

ALARM

IN103

IN102

N/C

N/C

IN104

+

_

RECLOSER CONTROL

I1

Z 0 1

I2

Z02

I3

Z03

IN

Z04

12 V

Z 1 7

RET

Z18

BAT+

Z 1 9

BAT-

Z20

BAT   3A

F01

Z 2 1

N/C

Z25

GND

Z26

H

Z22

N

Z23

Z24

V1

Z05

V2

Z06

V3

Z07

N

Z08

VS

Z09

NS

Z10

F

Z 1 1

E

Z 1 2

C

Z 1 3

B/D

Z14

A

Z 1 5

RET

Z16

196-1215

ENABLED

CONTROL

TRIP

CONTROL STATE

SELECT

CANCEL

LAMP

TEST

EXIT

METER

EVENTS

STATUS

OTHER

SET

CNTRL

GROUP

TARGET

RESET

GROUND

RECLOSE

ENABLED

ENABLED

ENABLED

REMOTE

SETTINGS

ALTERNATE

LOCK

(press for 3 sec)

AUX 1

AUX 2

 

 

WAKE UP

 

CLOSED

RECLOSER

OPEN

RECLOSER

TRIP

CLOSE

C

B

A

LOCKOUT

CYCLE

CURVE

FAST

TAG

HOT LINE

PROBLEM

BATTERY

SUPPLY

AC

CURRENT

HIGH

81

 

G

SEF

RESET

A01

A04

A03

A02

A07

A06

A05

A08

A 1 1

A10

A09

A14

A 1 3

A 1 2

A23

A16

A15

A 1 7

A18

A22

A20

A19

A21

A26

A25

A24

A28

A27

IRIG-B

SERIAL PORT 1

1

2

3

4

5

N/C

7

8

SERIAL PORT 2

SERIAL PORT 3

OUT102

OUT101

OUT104

OUT103

OUT107

N/C

N/C

IN101

ALARM

IN103

IN102

N/C

N/C

IN104

+

_

RECLOSER CONTROL

I1

Z 0 1

I2

Z02

I3

Z03

IN

Z04

12 V

Z 1 7

RET

Z18

BAT+

Z 1 9

BAT-

Z20

BAT   3A

F01

Z 2 1

N/C

Z25

GND

Z26

H

Z22

N

Z23

Z24

V1

Z05

V2

Z06

V3

Z07

N

Z08

VS

Z09

NS

Z1 0

F

Z 1 1

E

Z 1 2

C

Z 1 3

B/D

Z14

A

Z 1 5

RET

Z16

196-1215

ENABLED

CONTROL

TRIP

CONTROL STATE

SELECT

CANCEL

LAMP

TEST

EXIT

METER

EVENTS

STATUS

OTHER

SET

CNTRL

GROUP

TARGET

RESET

GROUND

RECLOSE

ENABLED

ENABLED

ENABLED

REMOTE

SETTINGS

ALTERNATE

LOCK

(press for 3 sec)

AUX 1

AUX 2

 

 

WAKE UP

 

CLOSED

RECLOSER

OPEN

RECLOSER

TRIP

CLOSE

C

B

A

LOCKOUT

CYCLE

CURVE

FAST

TAG

HOT LINE

PROBLEM

BATTERY

SUPPLY

AC

CURRENT

HIGH

81

 

G

SEF

RESET

A01

A04

A03

A02

A07

A06

A05

A08

A 1 1

A 1 0

A09

A 1 4

A 1 3

A 1 2

A23

A 1 6

A 1 5

A 1 7

A 1 8

A22

A20

A 1 9

A21

A26

A25

A24

A28

A27

IRIG-B

SERIAL PORT 1

1

2

3

4

5

N/C

7

8

SERIAL PORT 2

SERIAL PORT 3

OUT102

OUT101

OUT104

OUT103

OUT107

N/C

N/C

IN101

ALARM

IN103

IN102

N/C

N/C

IN104

+

_

RECLOSER CONTROL

Содержание SEL-351R Falcon

Страница 1: ...BITS communi cations speeds protection and improves security Customize controls by using enhanced SELOGIC control equations for improved system operation Configurable front panel control labels simpl...

Страница 2: ...ose interval The reset times are set separately for reset timing for an auto reclose and reset timing for a manual remote close from lockout Traditionally the reset time for a manual remote close from...

Страница 3: ...y inverse class C extremely inverse long time inverse short time inverse Programmable curves user designed Four 4 programmable curves Optional 3 Phase Voltage connect to voltage channels V1 V2 and V3...

Страница 4: ...er wear monitor measures unfiltered ac current at the time of trip and the number of close to open operations as a means of monitoring this wear Every time the recloser trips the recloser control reco...

Страница 5: ...27 IRIG B SERIAL PORT 1 1 2 3 4 5 N C 7 8 SERIAL PORT 2 SERIAL PORT 3 OUT102 OUT101 OUT104 OUT103 OUT107 N C N C IN101 ALARM IN103 IN102 N C N C IN104 _ RECLOSER CONTROL I1 Z01 I2 Z02 I3 Z03 IN Z04 12...

Страница 6: ...ttings Create Application Designs that include the most commonly used relay features and settings for your system see Figure 6 and watch commissioning times drop drastically Figure 6 Example Applicati...

Страница 7: ...ress for 3 sec AUX 1 AUX 2 WAKE UP CLOSED RECLOSER OPEN RECLOSER TRIP CLOSE C B A LOCKOUT CYCLE CURVE FAST TAG HOT LINE PROBLEM BATTERY SUPPLY AC CURRENT HIGH 81 G SEF RESET A01 A04 A03 A02 A07 A06 A0...

Страница 8: ...CLE CURVE FAST TAG HOT LINE PROBLEM BATTERY SUPPLY AC CURRENT HIGH 81 G SEF RESET A01 A04 A03 A02 A07 A06 A05 A08 A11 A10 A09 A14 A13 A12 A23 A16 A15 A17 A18 A22 A20 A19 A21 A26 A25 A24 A28 A27 IRIG B...

Страница 9: ...digital quantities having a logical value of either 0 or 1 The terms assert or asserted refer to a Relay Word bit that has a value of 1 or is changing from 0 to 1 The terms deassert or deasserted refe...

Страница 10: ...ry monitor charger the SEL 351R Falcon can monitor battery voltage The SEL 351R Falcon puts itself to sleep if voltage falls to a user set threshold or if a user set timer times out after an extended...

Страница 11: ...n change most functions by programming to meet system requirements see Table 4 Use the optional configurable labels to customize the targets and control pushbuttons to best meet operational needs r Se...

Страница 12: ...le CYCLE The control is actively in the trip reclose cycle mode LOCKOUT All reclose attempts were unsuccessful A B C a A B or C phase involved in fault G Ground involved in fault SEF Sensitive earth f...

Страница 13: ...ol via serial communications These values shall be available for use in control logic Secure Communications The recloser control shall include an optional accessory for converting an EIA 232 serial po...

Страница 14: ...tored Close Circuit Points Monitored Trip Circuit Points B D C A E F IRIG B 1 2 3 4 5 N C 7 8 FRONT PANEL OPERATOR CONTROLS 28 Vdc 24 Vdc 24 Vdc or 36 Vdc 12 Vdc FRONT PANEL TARGET LEDS AC SUPPLY CONT...

Страница 15: ...Schweitzer Engineering Laboratories Inc SEL 351R Falcon Data Sheet 15 Relay Mounting Figure 16 SEL 351R Falcon Lift To Open Enclosure Dimensions and Mounting...

Страница 16: ...SEL 351R Falcon Data Sheet Schweitzer Engineering Laboratories Inc 16 Figure 17 SEL 351R Falcon Swing Open Enclosure Dimensions and Mounting...

Страница 17: ...ages Frequency and Rotation System Frequency 50 or 60 Hz Phase Rotation ABC or ACB Frequency Tracking Range 40 1 65 Hz Note Voltage connected to V1 required for frequency tracking Communications Ports...