Sel SEL-351R Falcon Скачать руководство пользователя страница 2

SEL-351R Falcon Data Sheet

Schweitzer Engineering Laboratories, Inc.

2

Functional Overview

Figure 1

Functional Diagram

Functional Replacement for Traditional Recloser Control

EZ Settings for Basic 
Recloser Functions

For traditional recloser functions, the SEL-351R Falcon
is easy to set. Only settings such as minimum trip pickup,
curve type, and reclose interval are necessary. These set-
tings are made at an EZ (easy) access level. SEL

OGIC

control equations cannot be changed at this access level.

Control logic is preconfigured at the factory. To
customize the logic for advanced functions, the SEL

OGIC

control equations must be reprogrammed.

Reclosing

The SEL-351R Falcon can reclose as many as four (4)
times. This allows as many as five (5) operations of any
combination of fast and delay curve overcurrent
elements. Each reclose interval can be set for as many as
999,999 cycles (more than 4.5 hours), if necessary.

After a reclose interval has timed out, the control waits a
user-set time (close power wait time) for the presence of
adequate Vac power before proceeding with the auto
reclose. The recloser needs either primary or secondary
voltage to provide the closing power, depending on how

the recloser is equipped. The Vac power into the
SEL-351R Falcon is an indication of the presence of this
primary or secondary voltage. The close power wait time
has the same 999,999-cycle setting range as the reclose
interval.

The reset times are set separately for reset timing for an
auto reclose and reset timing for a manual/remote close
from lockout. Traditionally, the reset time for a
manual/remote close from lockout is set for less than the
reset time for an auto-reclose. The reset times have the
same 999,999-cycle setting range.

Front-panel LEDs track the CONTROL STATE for
auto-reclosing: 

RESET

CYCLE

, or 

LOCKOUT

 (see Figure 14

and Table 4).

Sequence coordination logic is enabled to prevent the
SEL-351R Falcon from tripping on its fast curves for
faults beyond a downstream recloser.

Customize reclosing logic by using SEL

OGIC

 control

equations. Use programmable counters, latches, logic
functions, and analog compare functions to optimize
control actions.

ANSI NUMBERS/ACRONYMS AND FUNCTIONS 

25

Synchronism Check*

27

Undervoltage

50N

Neutral Overcurrent

50 (P, G, Q) 

Overcurrent (Phase, Ground, Neg. Seq.) 

51N

Neutral Time-Overcurrent

51 (P, G, Q) 

Time-Overcurrent (Phase, Ground, Neg. Seq.) 

59

Overvoltage

59 (P, G, Q) 

Overvoltage (Phase, Ground, Neg. Seq.) 

67N

Directional Neutral Overcurrent*

67 (P, G, Q) 

Directional Overcurrent (Phase, Ground, Neg. Seq.)* 

79

Autoreclosing

81 (O, U) 

Over-/Underfrequency 

85 RIO 

SEL M

IRRORED 

B

ITS

®

 Communications 

DFR

Event Reports

HMI

Operator Interface

LGC

SEL

OGIC

®

 Control Equations 

MET

High-Accuracy Metering

SER Sequential 

Events 

Recorder 

ADDITIONAL FUNCTIONS 

BRM Breaker 

Wear 

Monitor 

LDP

Load Data Profiling*

LOC

Fault Locator*

* Optional Feature

51N

50N

27

59

79

67N

50

P

G

Q

51

P

G

Q

Line

Bus

4

EIA-232
EIA-485

1

IRIG-B

R

esidual

S

3

1

27

81

O

U

59

P

G

Q

25

RECLOSER

*

*

67

P

G

Q

85

RIO

DFR

HMI

LGC

LOC

MET

SER

BRM

Содержание SEL-351R Falcon

Страница 1: ...BITS communi cations speeds protection and improves security Customize controls by using enhanced SELOGIC control equations for improved system operation Configurable front panel control labels simpl...

Страница 2: ...ose interval The reset times are set separately for reset timing for an auto reclose and reset timing for a manual remote close from lockout Traditionally the reset time for a manual remote close from...

Страница 3: ...y inverse class C extremely inverse long time inverse short time inverse Programmable curves user designed Four 4 programmable curves Optional 3 Phase Voltage connect to voltage channels V1 V2 and V3...

Страница 4: ...er wear monitor measures unfiltered ac current at the time of trip and the number of close to open operations as a means of monitoring this wear Every time the recloser trips the recloser control reco...

Страница 5: ...27 IRIG B SERIAL PORT 1 1 2 3 4 5 N C 7 8 SERIAL PORT 2 SERIAL PORT 3 OUT102 OUT101 OUT104 OUT103 OUT107 N C N C IN101 ALARM IN103 IN102 N C N C IN104 _ RECLOSER CONTROL I1 Z01 I2 Z02 I3 Z03 IN Z04 12...

Страница 6: ...ttings Create Application Designs that include the most commonly used relay features and settings for your system see Figure 6 and watch commissioning times drop drastically Figure 6 Example Applicati...

Страница 7: ...ress for 3 sec AUX 1 AUX 2 WAKE UP CLOSED RECLOSER OPEN RECLOSER TRIP CLOSE C B A LOCKOUT CYCLE CURVE FAST TAG HOT LINE PROBLEM BATTERY SUPPLY AC CURRENT HIGH 81 G SEF RESET A01 A04 A03 A02 A07 A06 A0...

Страница 8: ...CLE CURVE FAST TAG HOT LINE PROBLEM BATTERY SUPPLY AC CURRENT HIGH 81 G SEF RESET A01 A04 A03 A02 A07 A06 A05 A08 A11 A10 A09 A14 A13 A12 A23 A16 A15 A17 A18 A22 A20 A19 A21 A26 A25 A24 A28 A27 IRIG B...

Страница 9: ...digital quantities having a logical value of either 0 or 1 The terms assert or asserted refer to a Relay Word bit that has a value of 1 or is changing from 0 to 1 The terms deassert or deasserted refe...

Страница 10: ...ry monitor charger the SEL 351R Falcon can monitor battery voltage The SEL 351R Falcon puts itself to sleep if voltage falls to a user set threshold or if a user set timer times out after an extended...

Страница 11: ...n change most functions by programming to meet system requirements see Table 4 Use the optional configurable labels to customize the targets and control pushbuttons to best meet operational needs r Se...

Страница 12: ...le CYCLE The control is actively in the trip reclose cycle mode LOCKOUT All reclose attempts were unsuccessful A B C a A B or C phase involved in fault G Ground involved in fault SEF Sensitive earth f...

Страница 13: ...ol via serial communications These values shall be available for use in control logic Secure Communications The recloser control shall include an optional accessory for converting an EIA 232 serial po...

Страница 14: ...tored Close Circuit Points Monitored Trip Circuit Points B D C A E F IRIG B 1 2 3 4 5 N C 7 8 FRONT PANEL OPERATOR CONTROLS 28 Vdc 24 Vdc 24 Vdc or 36 Vdc 12 Vdc FRONT PANEL TARGET LEDS AC SUPPLY CONT...

Страница 15: ...Schweitzer Engineering Laboratories Inc SEL 351R Falcon Data Sheet 15 Relay Mounting Figure 16 SEL 351R Falcon Lift To Open Enclosure Dimensions and Mounting...

Страница 16: ...SEL 351R Falcon Data Sheet Schweitzer Engineering Laboratories Inc 16 Figure 17 SEL 351R Falcon Swing Open Enclosure Dimensions and Mounting...

Страница 17: ...ages Frequency and Rotation System Frequency 50 or 60 Hz Phase Rotation ABC or ACB Frequency Tracking Range 40 1 65 Hz Note Voltage connected to V1 required for frequency tracking Communications Ports...

Страница 18: ...ow pass analog filtering Net filtering analog plus digital rejects dc and all harmonics greater than the fundamental Protection and Control Processing Four times per power system cycle Battery Monitor...

Страница 19: ...20 C and at nominal system frequency unless noted otherwise Voltages VA VB VC VS 3V0 V1 V2 0 2 67 300 0 V wye connected Currents IA IB IC 1 A nominal 3 mA 0 1 0 1 20 A Temperature Coefficient 0 0002...

Страница 20: ...laws in its products including without lim itation software firmware and documentation The information in this document is provided for informational use only and is subject to change without notice...

Отзывы: